Features
- AC input range selectable by switch
- Withstand 300VAC surge input for 5 second
- Up to 200% peak power capability
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Compliance to IEC/BS EN/EN61558-1 and 62368-1
- Withstand 5G vibration test
- LED indicator for power on
- No load power consumption<1W
- Over voltage category III(OVC III)
- High operating temperature up to 70 C
- Operating altitude up to 2000 meters
- High efficiency, long life and high reliability
- 3 years warranty
Applications
- Industrial automation machinery
- Industrial control system
- Mechanical and electrical equipment
- Electronic instruments, equipments or apparatus
- For inductive and capacitive load
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx
Description
LRS-200N2 series is a 200W single-output enclosed type power supply with 30mm
of low profile design. Adopting the input of 115VAC or 230VAC (select by
switch), the entire series provides an output voltage line of 12V, 24V, 36V
and 48V. In addition to the high efficiency up to 90%, the design of metallic
mesh case enhances the heat dissipation of LRS-200N2 that the whole series
operates from -25°C through 70 C under air convection without a fan.
Delivering an extremely low no load power consumption (less than 0.75W), it
allows the end system to easily meet the worldwide energy requirement. LRS-
200N2 has the complete protection functions and 5G anti-vibration capability;
it is complied with the international safety regulations such as IEC/UL
62368-1. LRS-200N2 series serves as a high price-to-performance power supply
solution for various industrial applications. Moreover, LRS- 200N2 can provide
200% short-duration peak power for motor applications and electromechanical
loads requiring much higher power during start-up.
Model Encoding
SPECIFICATION
MODEL| LRS-200N2-12| LRS-200N2.24| LRS-200N2-36| LRS-
200N2-48
---|---|---|---|---
OUTPUT| DC VOLTAGE| 12V| 24V| 36V| 48V
RATED CURRENT| 17A| 8.8A| 5.9A| 4.4A
CURRENT RANGE| 0 ∼ 17A| 0 ∼ 8.8A| 0 ∼ 5.9A| 0 ∼ 4.4A
RATED POWER| 204W| 211.2W| 212.4W| 211.2W
RIPPLE Si NOISE (max.) Hotel| 150mVp-p| 1 50mVp-p| 200mVp-p| 20 OrnVp-p
VOLTAGE ADJ. RANGE| 10.2 ∼ 118V| 21.6 ∼ 28.8V| 32.4 ∼ 39.6V| 43.2 ∼ 52.8V
VOLTAGE TOLERANCE Note.3| ±1.5%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION Note.4| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION Note.5| ±1.0%| ±0.5%| ±0.5%| ±0.5%
SETUP, RISE TIME| 1300ms, 50ms/23 OVAC 1 300ms,50ms/11 5VAC at full load
HOLD UP TIME (Typ.)| 16ms/230VAC 1 2ms/115VAC at full load
INPUT| VOLTAGE RANGE| 90 ∼ 1 32VAC 1180 ∼ 264VAC by switch 240 ∼ 370VDC
(switch on 230VAC)
FREQUENCY RANGE| 47 ∼ 63Hz
EFFICIENCY (Typ.)| 88.%| 190.%| 190.%| 90%
AC CURRENT (Typ.)| 4.1A/115VAC 2.4A/230VAC
INRUSH CURRENT (Typ.)| COLD STAR 6 0A/11 5VAC 6 0A/230VAC
LEAKAGE CURRENT| <2mA / 240VAC
PROTECTION| OVER LOAD| Output power >105% rated for more than 5 seconds then
shut down Op voltage, re-power on to recover
Ou put power >200% rated, hiccup mode, recovers automatically after fault
condition is removed
OVER VOLTAGE| 13.8 ∼ 1 6.2V| 1 28.8 ∼ 33.6V| 141.4 ∼ 46.8V| 1 55.2 ∼ 64.8V
Shut down and latch off o/p voltage, re-power on to recover.
OVER TEMPERATURE| Shut down and latch off o/p voltage, re-power on to recover.
ENIRCNNENT| WORKING TEMP.| -25∼ +70°C (Refer to “Derating Curve)
WORKING HUMIDITY| 2 0∼ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40∼ +85°C, 10- 95% RH
TEMP. COEFFICIENT| ±0.03%/°C (0- 50°C )
VIBRATION| 10 ∼ 50 0Hz, 56 10min./1cycle, 60min. each along X, Y. Z axes
OVER VOLTAGE CATEGORY| III: According to EN61558, EN50178, EN60664-1,
EN62477-1; altitude up to 2000 meters
SAFETY| SAFETY STANDARDS| IEC/UL 62368-1, BSMI CNS14 336-1,EAC TP TC 004,BIS
IS13252(Part1): 2010/IEC 60950-1: 2005;
BS EN/EN61558-1, BS EN61558-2-16 Designed by BS/EN/EN62368-1, AS/NZS
61558.1/2.16, AS/NZS 62368.1
WITHSTAND VOLTAGE| UP-0/P:3.75KVAC I/P-FG:2KVAC 0/P-FG:0.5KVAC
ISOLATION RESISTANCE| UP-0/P, I/P-FG, 0/P-FG:1 00M Ohms / 500VDC / 25°C/ 7 0%
RH
EMC EMISSION| Compliance to BSMI CNS13438, EAC TP TC 020
EMC IMMUNITY| Compliance to BS EN/EN55035, EAC TPTC 020
OTHERS| MTBF| 2 089.1K hrs min. Telcordia SR-332 (Bellcore) ; 24 3.6Khrs min.
MIL-HDBK-21 7F (2 5 C )
DIMENSION| 215’11 510mm (L*VV’H)
PACKING| 0.66Kg; 15pcs/10.7Kg/0.67CU FT
NOTE| 1.All parameters NOT specially mentioned are measured at 230VAC input,
rated bad and 25°C of ambient temperature.
2.Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted
pair-wire terminated with a 0.1uf & 47uf parallel capacibr. a Length of set up
time is measured at cold first start. Turning ON/OFF the power supply eery
quickly may lead to increase of the set up time.
4. This power supply does not meet the harmonic current requirements outlined
by BS EN/EN61000-3-2. Please do not use this power supply under the following
conditions:
a)the end-devices is used within the European Union, and
b)the end-devices is connected to public mains supply with 220Vac or greater
rated nominal voltage, and
c)the power supply is:
– installed in end-devices with average or continuous input power greater than
75W, or
– belong Y3 part of a lighting system
Exception:
Power supplies used within the following end-devices do not need to fulfill BS
ENEN61000-3-2
a)professional equipment with a total rated input power greater than 1000W;
b)symmetrically controlled heating elements with a rated paver less than or
equal b 200W
5. RCM is on voluntary basis and meets relevant IEC or AS/NZS standards
complying with AS/NZS 4417.1.
※ Product Liability Disclaimer : For detailed information, please refer to
https://Avww.meanwell.com/serviceDisclaimer.aspx
Block Diagram
Derating Curve
Static Characteristics
Function
Manual
- Peak Powe
Mechanical Specification
Case No. 207
Unit:mm Terminal Pin No. Assignment:
Pin No. | Assignment | Pin No. | Assignment |
---|---|---|---|
1 | AC/L | 4~6 | DC OUTPUT -V |
2 | AC/N | 7~9 | DC OUTPUT +V |
3 | FG **** |