Danfoss ICAD 600A Control Valve Actuator User Guide
- June 13, 2024
- Danfoss
Table of Contents
Quick Start Guide
Before you start using ICAD:
ICAD 600A Control Valve Actuator
Quick
Start Guide
ICAD 600A / ICAD 1200A
24 Volt d.c. ONLY
Ref. | Colour | Description | |
---|---|---|---|
A | Black | – | Common Alarm |
B | Brown | – | ICM fully open |
C | Red | – | ICM fully closed |
D | Orange | – | GND ground |
E | Yellow | + | 0/4 – 20 mA Input |
F | Green | + | 0/2-10y input or digital input for on/off control |
G | Blue | + | 0/4 – 20 mA Output |
Digital Ouput
I | Black | + | Fail safe supply Battery / UPS* 19 V d.c. |
---|---|---|---|
II | White | + | Supply voltage 24 V d.c. |
III | Brown | – |
- Uninterruptable Power Supply
Please observe cable voltage drop
24 Volt d.c. ONLY
Distance between the applied d.c. transformer and the ICAD terminal box may cause a voltage drop. Cross section of cables and size of d.c. transformer must be calculated so that the voltage at all time at the ICAD terminal box*, both during standstill and during
operation of ICAD, is within this range:
Prefabricated ICAD cable length | 1.5 m | 3 m | 10 m | 15 m |
---|---|---|---|---|
Code number | 027H0426 | 027H0438 | 027H0427 | 027H0435 |
Voltage ICAD terminal Min. | 21 | 22 | 23 | 24 |
(600A/1200A) [V d.c.] Max. | 26. |
- Do not measure inside the ICAD itself.
Note:
If the keypad is not operated within 20 seconds; time out will automatically
exit programming mode.
Programming the ICAD
DKRCI.PI.HV0.J4.02 / 520H4887 / 027R9801