ABB EV3 Energy Meter User Manual
- June 13, 2024
- ABB
Table of Contents
ENERGY METER
EV3
User Manual
Document ID: 9AKK107991A1347
Revision: A 2020-12-01
EV3 Energy Meter
Disclaimer
The information in this document is subject to change without notice and
should not be construed as a commitment by ABB Spa. ABB Spa assumes no
responsibility for any errors that may appear in this document.
In no event shall ABB Spa be liable for direct, indirect, special, incidental
or consequential damages of any nature or kind arising from the use of this
document, nor shall ABB Spa be liable for incidental or consequential damages
arising from use of any software or hardware described in this document.
Copyrights
This document and parts thereof must not be reproduced or copied without
written permission from ABB Spa, and the contents thereof must not be imparted
to a third party nor used for any unauthorized purpose. The software or
hardware described in this document is furnished under a license and may be
used, copied, or disclosed only in accordance with the terms of such license.
© Copyright 2020 ABB Spa. All rights reserved.
Trademarks
ABB Spa is a registered trademark of the ABB Group. All other brand or product
names mentioned in this document may be trademarks or registered trademarks of
their respective holders.
Contact
ABB SpA
Via Dell’industria, 18
20009 – Vittuone – Milano
Italy
Tel. +39 02 2415 0000
General Information
1.1 Responsibility
The owner or provider is responsible for the proper use of the device. The
installation, putting into operation and reinstallation of the meter is only
allowed to be done by electrically skilled persons, which got knowledge about
the contents of this user manual.
1.2 Common safety instructions
For installation, setting into operation and installation of the device the
local requirements for safety requirements must be observed.
Danger
Inappropriate use of parts under high voltage may lead to grave injuries and
accidents, which may be fatal even with 230V.
The conductors which are connected to the device must be disconnected to the
mains during assembling and installation. It must be used a prevention for
being switched on accidentally.
The device is not allowed to be used out of specifications.
1.3 Service and warranty instructions
Damaged devices can’t be repaired by you. The warranty and liability will be
terminated with opening the device. The same applies to damages caused by
external influences.
For the device no servicing is required.
1.4 Disposal (product end of life information)
This meter was designed and built by ABB to provide many years of service and
is backed by our commitment to provide high quality support. When it
eventually reaches the end of its serviceable life, it should be disposed in
accordance with local or national legislation.
1.5 Environment
This meter is designed for indoor or in a cabinet environment only (avoiding
extreme weather conditions) in accordance with EN50470-1 and EN50470-3, with
the terminal cover fitted.
1.6 Service and Warranty
This meter product is warranted against defects in material and workmanship
for a period of one year from date of shipment. During the warranty period ABB
will at its option, either repair or replace products which prove to be
defective. For warranty service or repair, this product must be returned to a
service facility designated by ABB. ABB does not warrant that the operation of
the meter or firmware will be uninterrupted or error free.
Damaged devices can’t be repaired by you. The warranty and liability will be
terminated with opening the device. The same applies to damages caused by
external influences.
For the device no servicing is required.
1.7 Cyber Security Disclaimer
EV meter is designed to be connected and to communicate information and data
via a network interface, which should be connected to a secure network. It is
your sole responsibility to provide and continuously ensure a secure
connection between the product and your network or any other network (as the
case may be) and to establish and maintain appropriate measures (such as but
not limited to the installation of firewalls, application of authentication
measures, encryption of data, installation of antivirus programs, etc.) to
protect the meter, the network, its system and interfaces against any kind of
security breaches, unauthorized access, interference, intrusion, leakage
and/or theft of data or information. ABB S.p.A. and its affiliates are not
liable for damages and/or losses related to such security breaches,
unauthorized access, interference, intrusion, leakage and/or theft of data or
information.
Although ABB S.p.A. provides functionality testing on the products and updates
that we release, you should institute your own testing program for any product
updates or other major system updates (to include but not limited to code
changes, configuration file changes, third party software updates or patches,
hardware change out, etc.) to ensure that the security measures that you have
implemented have not been compromised and system functionality in your
environment is as expected.
1.8 Symbols
| Danger through Electric Voltages
The symbol indicates warnings, which may lead to personal injuries or death if
it is ignored. Take all necessary precautions to avoid
danger!
---|---
**| Warning
The symbol indicates warnings to a possible dangerous situation which may lead
to personal injuries or damage to properties.
Avoid dangerous situations!
| Attention!
“Attention” indicates warnings, which may lead to damage of properties if not
observed.
| Notice**
“Notice” indicates important information in the manual.
Technical data
2.1 Abbreviations
+A | Import active energy (to customer) |
---|---|
-A | Export active energy (from customer) |
EN | European Standard |
Imp/kWh | Quantity of pulses each kWh |
LCD | Liquid Crystal Display |
LED | Light Emitting Diode |
OBIS | Object Identification System |
+P | Import active power |
-P | Export active power |
2.2 Technical specifications
Type | Three phase direct |
---|
Voltage
Nominal voltage Un| 3×230/400 Vac
Voltage range| 0.8 – 1.15Un
Frequency
Nominal frequency fn| 50 Hz
Frequency range| 0.98 – 1.02 fn
Current
Reference current Iref = Ib = 10 Itr| 5 A
Maximum current Imax| 65A
Minimum current Imin| 0.25 A
Starting current Ist| £ 0.004 Ib
Accuracy
Cl. B| Class B in compliance with EN 50470-3
Measuring Active Energy
Two Energy Directions| +A/-A
Meter constant
LED-Output| 1000 Imp/kWh
Display
LCD| 7 digit
Life cycle| > 12 years
RS485- Data Interface
Connector| 3P meter: Three screws type
Parameter| 9600/19200/38400 bps, 8E1
Communication protocol| Modbus RTU
Power Consumption
Voltage circuit| < 0.7 W / 5.5 VA at Un
Current circuit| < 0.015 VA at Ib
Temperature Range
Typical Operation| -30°C to +70°C
Storage| -40°C to +85°C
EMC Properties
Isolation| 4 kV AC, 50 Hz, 1min
High Voltage| 7kV, Impulse 0.1/2000 µs
Housing
Dimension| DIN-Rail 90x70x62 mm
Material| fiber-glass reinforced Polycarbonate (flame resistant EN 62053-21)
Class of protection| II
Degree of protection| IP21 (IP 51 in protective enclosure)
Weight
Weight| appr. 0,26 kg
Environment
Mechanical environment| Class M1 as per 2014/32/EU Directive.
Electromagnetic environment| Class E2 as per 2014/32/EU Directive.
Tab. 1: Technical Properties
2.2.1 Technical Standards
EN 50470-1: Electricity metering equipment (AC) -Part 1: General
requirements, test and test conditions Metering equipment (class indexes A, B,
and C);
EN 50470-3: Electricity metering equipment (AC) -Part 3: Particular
requirement Static meters for active energy (class indexes A, B, and C);
EN 50022: Low voltage switchgear and control gear for industrial use;
mounting rails, top hat rails, 35 mm wide, for snap-on mounting of equipment
IEC 62053-21: Static meters for active energy (classes 1 and 2)
IEC 62052-11: Electricity metering equipment (AC)-General requirements, tests
and test conditions –part 11: metering equipment
Dimension, Assembling and Installation EV3 012-100
3.1 Assembling and dimensions
The meter constructed for assembling on DIN-rail TH 35-7.5 according to IEC
60715.
Nr | Element |
---|---|
1 | Meter Hook |
2 | User Buttons |
3 | LCD |
4 | DIN Rail |
5 | Meter cover |
6 | Meter case |
7 | Terminal block with cover |
3.2 Installation The connection diagram printed on the housing needs to be considered connecting the meter to the mains power.
Terminal| Terminal Nr| Terminal- [mm]| Terminal
screw| Torque M [Nm]
---|---|---|---|---
Current In L1| 1| 6,3 x 5,6 (L x W)| M4 Pozidrive PZ2| 1,2 Nm< M <1,5Nm
Current Out L1| 3
Current In L2| 4
Current Out L2| 6
Current In L3| 7
Current Out L3| 9
Voltage N| 10
RS485 Interface GND| 21| 6,3 x 5,6 (L x W)| M3 Pozidrive PZ2| 0,5 Nm <M <0,7Nm
RS485 Interface B| 22
RS485 Interface A| 23
Warning
The requirements of the net provider need to be full filled.
Selective hedges have to be used according requirements of the net providers.
Attention!
Damage of the terminals due to high torque
The specified maximum torques must not be exceeded!
Ensure that the connected lines are fixed with the needed torque compliant to
EN 60999 for a safe connection. The needed torque depends on the type of used
lines and the maximum current.
3.3 Protection Housing
As indicated in image 11 the cover of the terminal blocks can be sealed after
installation. The assembled meter base and meter cover will be protected
against unauthorized opening with a manufacturer label (format 8×20 mm, corner
radius 0.5 mm) on both sides of the housing. Important
Warranty and accuracy are void if sealing labels are removed.
3.4 EV3
Nr | Element | Function |
---|---|---|
1 | Terminal block with cover | sealable terminal cover |
2 | Meter number | with barcode 128 |
3 | User buttons | Information describe in chapter 7 |
4 | LCD | 7 digits with additional symbols |
5 | Meter type | |
6 | LED | test LED 1000 Imp/kWh |
7 | Technical nominal data | |
8 | 3 phase 4 Wire | |
Protection class | ![Icon](https://manuals.plus/wp- |
content/uploads/2022/05/Screenshot_3-305.png)
Two energy directions| Import (+A) and Export (-A) energy measurement
Security symbol|
9| Firmware version|
10| Number approval document year of certification| CE sign, year of
certification, named body for MID approval
11| Manufacture year|
LCD-Display
The LCD has the following format:
– LCD size: 37.5 mm × 17 mm
– Digit size: 3.38 mm × 1,53 mm7: LCD-Display
Nr | Element | Function |
---|---|---|
1 | Unit | unit of the displayed value (kWh, W, V, A) |
2 | Values | according defined display list |
3 | Indication of phase voltages | Symbol off: loss of phase |
Symbol is flashing: reverse sequence, reverse polarity,
Lx >1.15Un or Lx<0.8Un.
4| Indication current direction| Export
| | Import
5| OBIS Code| Identifier of the displayed value
User Buttons
Nr | Element | Function |
---|---|---|
1 | Button „Up“ | – Switch backlight of the LCD ON |
– Scrolling the display items
– Enter display ALT Mode
2| Button „Down“| – Switch backlight of the LCD ON
– Scrolling the display items
– Enter display ALT Mode
The detailed functions of the buttons to switch into the different display modes is explained under the chapter 8.4 Display Modes.
Test LED
The meter has one pulse LED for active energy with 1000 Imp/kWh.
The ON-time of a pulse is 40 ms.
Components
7.1 Block diagram
Current measuring: | Manganin shunt |
---|---|
Voltage measuring: | Resistor divider |
A/D: | Analog to digital converter for the sampled voltage and current |
MCU: | Micro Controller Unit |
Communication interface: | RS485-Interface |
Data storage EV3: | nonvolatile storage for energy register +A/-A and meter |
parameter in EEPROM.
Display EV3:| LCD with 7 digits
LED Pulse output:| Active energy +A and -A, 1000 Imp/kWh
Functionality
8.1 Measurement
The meter measures three phase active energy with accuracy class B.
The meter provides registers for total import, total export and net energy.
Additionally, each phase L1, L2 and L3 for import and export energy are
measured.
The measurement of the energy is based on the measured power according the
following calculations:
Ptotal = PL1 + PL2 + PL3
Ptotal> 0: counting energy for +A
Ptotal< 0: counting energy for -A
8.1.1 Instantaneous parameter measurements
The instantaneous values can be read out via RS485 interface.
- Voltage and current
- Power factor
- Active power
- Frequency
8.2 Display Modes
The meter support three different display modes:
– AUTO Mode
– ALT Mode
8.2.1 Status Diagram No Button pressed t > ns: the parameter n can be set via
data interface
10 Status diagram display mode
After power on the meter shows for 2s self-check status and goes on to the
AUTO-Mode.
With the user buttons it can be changed between the different modes.
8.2.2 AUTO Mode and ALT Mode
In the AUTO Mode and ALT Mode all values which may be used for energy are
displayed. This part of the display list can’t be changed by the user with any
interface of the meter.
The display lists can be expanded with additional values by the user via the
RS485 interface and a parameter setting program. Each list can have 32
entries.
The different values are displayed with the following formats and units:
Type of value | Format | unit |
---|---|---|
Energy | x.xx | kWh |
Power | x.xx | W |
Voltage | x.x | V |
Current | x.xx | A |
Power Factor | x.xxx | — |
Frequency | x.xx | — |
Firmware Version | — | |
Checksum | — |
Tab. 7: Format/Unit Displayed Values
In the AUTO Mode the next value of the defined list is displayed
automatically with a settable time period.
In the ALT Mode the next value is displayed after a user button was pressed.
8.3 Fatal Error
The meter has implemented a self-monitoring system. If the meter recognizes
improper operation so that billing relevant values may not be used anymore it
displays “–FF–” This status will be indicated with current display items
flashing (1Hz).
8.4 Backlight EV3
Backlight will be on after pressing button, it’s useful to read meter through
LCD when it in dark environment. Light on time is configurable from 5s to 60
seconds.
The back light will be turned off unconditionally if the voltage is less than
0.8Un.
RS485 Interface & Registers
Default Modbus settings:
Baud rate = 9600 (settable)
Device Address = 1 (settable)
Parity = Even (not settable)
Registers are listed in document 9AKK107991A9529
References