ABB EV3 Energy Meter User Manual

June 13, 2024
ABB

ENERGY METER
EV3
User Manual
Document ID: 9AKK107991A1347
Revision: A 2020-12-01

EV3 Energy Meter

Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB Spa. ABB Spa assumes no responsibility for any errors that may appear in this document.
In no event shall ABB Spa be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, nor shall ABB Spa be liable for incidental or consequential damages arising from use of any software or hardware described in this document.
Copyrights
This document and parts thereof must not be reproduced or copied without written permission from ABB Spa, and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
© Copyright 2020 ABB Spa. All rights reserved.
Trademarks
ABB Spa is a registered trademark of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
Contact
ABB SpA
Via Dell’industria, 18
20009 – Vittuone – Milano
Italy
Tel. +39 02 2415 0000

General Information

1.1 Responsibility
The owner or provider is responsible for the proper use of the device. The installation, putting into operation and reinstallation of the meter is only allowed to be done by electrically skilled persons, which got knowledge about the contents of this user manual.
1.2 Common safety instructions
For installation, setting into operation and installation of the device the local requirements for safety requirements must be observed.
Danger
Inappropriate use of parts under high voltage may lead to grave injuries and accidents, which may be fatal even with 230V.
The conductors which are connected to the device must be disconnected to the mains during assembling and installation. It must be used a prevention for being switched on accidentally.
The device is not allowed to be used out of specifications.
1.3 Service and warranty instructions
Damaged devices can’t be repaired by you. The warranty and liability will be terminated with opening the device. The same applies to damages caused by external influences.
For the device no servicing is required.
1.4 Disposal (product end of life information)

This meter was designed and built by ABB to provide many years of service and is backed by our commitment to provide high quality support. When it eventually reaches the end of its serviceable life, it should be disposed in accordance with local or national legislation.
1.5 Environment
This meter is designed for indoor or in a cabinet environment only (avoiding extreme weather conditions) in accordance with EN50470-1 and EN50470-3, with the terminal cover fitted.
1.6 Service and Warranty
This meter product is warranted against defects in material and workmanship for a period of one year from date of shipment. During the warranty period ABB will at its option, either repair or replace products which prove to be defective. For warranty service or repair, this product must be returned to a service facility designated by ABB. ABB does not warrant that the operation of the meter or firmware will be uninterrupted or error free.
Damaged devices can’t be repaired by you. The warranty and liability will be terminated with opening the device. The same applies to damages caused by external influences.
For the device no servicing is required.
1.7 Cyber Security Disclaimer
EV meter is designed to be connected and to communicate information and data via a network interface, which should be connected to a secure network. It is your sole responsibility to provide and continuously ensure a secure connection between the product and your network or any other network (as the case may be) and to establish and maintain appropriate measures (such as but not limited to the installation of firewalls, application of authentication measures, encryption of data, installation of antivirus programs, etc.) to protect the meter, the network, its system and interfaces against any kind of security breaches, unauthorized access, interference, intrusion, leakage and/or theft of data or information. ABB S.p.A. and its affiliates are not liable for damages and/or losses related to such security breaches, unauthorized access, interference, intrusion, leakage and/or theft of data or information.
Although ABB S.p.A. provides functionality testing on the products and updates that we release, you should institute your own testing program for any product updates or other major system updates (to include but not limited to code changes, configuration file changes, third party software updates or patches, hardware change out, etc.) to ensure that the security measures that you have implemented have not been compromised and system functionality in your environment is as expected.
1.8 Symbols

| Danger through Electric Voltages
The symbol indicates warnings, which may lead to personal injuries or death if it is ignored. Take all necessary precautions to avoid
danger!
---|---
**| Warning
The symbol indicates warnings to a possible dangerous situation which may lead to personal injuries or damage to properties.
Avoid dangerous situations!
|
Attention!
“Attention” indicates warnings, which may lead to damage of properties if not observed.
|
Notice**
“Notice” indicates important information in the manual.

Technical data

2.1 Abbreviations

+A Import active energy (to customer)
-A Export active energy (from customer)
EN European Standard
Imp/kWh Quantity of pulses each kWh
LCD Liquid Crystal Display
LED Light Emitting Diode
OBIS Object Identification System
+P Import active power
-P Export active power

2.2 Technical specifications

Type Three phase direct

Voltage
Nominal voltage Un| 3×230/400 Vac
Voltage range| 0.8 – 1.15Un
Frequency
Nominal frequency fn| 50 Hz
Frequency range| 0.98 – 1.02 fn
Current
Reference current Iref = Ib = 10 Itr| 5 A
Maximum current Imax| 65A
Minimum current Imin| 0.25 A
Starting current Ist| £ 0.004 Ib
Accuracy
Cl. B| Class B in compliance with EN 50470-3
Measuring Active Energy
Two Energy Directions| +A/-A
Meter constant
LED-Output| 1000 Imp/kWh
Display
LCD| 7 digit
Life cycle| > 12 years
RS485- Data Interface
Connector| 3P meter: Three screws type
Parameter| 9600/19200/38400 bps, 8E1
Communication protocol| Modbus RTU
Power Consumption
Voltage circuit| < 0.7 W / 5.5 VA at Un
Current circuit| < 0.015 VA at Ib
Temperature Range
Typical Operation| -30°C to +70°C
Storage| -40°C to +85°C
EMC Properties
Isolation| 4 kV AC, 50 Hz, 1min
High Voltage| 7kV, Impulse 0.1/2000 µs
Housing
Dimension| DIN-Rail 90x70x62 mm
Material| fiber-glass reinforced Polycarbonate (flame resistant EN 62053-21)
Class of protection| II
Degree of protection| IP21 (IP 51 in protective enclosure)
Weight
Weight| appr. 0,26 kg
Environment
Mechanical environment| Class M1 as per 2014/32/EU Directive.
Electromagnetic environment| Class E2 as per 2014/32/EU Directive.

Tab. 1: Technical Properties
2.2.1 Technical Standards
EN 50470-1:
Electricity metering equipment (AC) -Part 1: General requirements, test and test conditions Metering equipment (class indexes A, B, and C);
EN 50470-3: Electricity metering equipment (AC) -Part 3: Particular requirement Static meters for active energy (class indexes A, B, and C);
EN 50022: Low voltage switchgear and control gear for industrial use; mounting rails, top hat rails, 35 mm wide, for snap-on mounting of equipment
IEC 62053-21: Static meters for active energy (classes 1 and 2)
IEC 62052-11: Electricity metering equipment (AC)-General requirements, tests and test conditions –part 11: metering equipment

Dimension, Assembling and Installation EV3 012-100

3.1 Assembling and dimensions
The meter constructed for assembling on DIN-rail TH 35-7.5 according to IEC 60715. ABB EV3 Energy Meter - Assembling and
dimensions

Nr Element
1 Meter Hook
2 User Buttons
3 LCD
4 DIN Rail
5 Meter cover
6 Meter case
7 Terminal block with cover

ABB EV3 Energy Meter - Assembling and dimensions 1 3.2 InstallationABB EV3 Energy Meter - Assembling and dimensions
2 The connection diagram printed on the housing needs to be considered connecting the meter to the mains power.

Terminal| Terminal Nr| Terminal- [mm]| Terminal screw| Torque M [Nm]
---|---|---|---|---
Current In L1| 1| 6,3 x 5,6 (L x W)| M4 Pozidrive PZ2| 1,2 Nm< M <1,5Nm
Current Out L1| 3
Current In L2| 4
Current Out L2| 6
Current In L3| 7
Current Out L3| 9
Voltage N| 10
RS485 Interface GND| 21| 6,3 x 5,6 (L x W)| M3 Pozidrive PZ2| 0,5 Nm <M <0,7Nm
RS485 Interface B| 22
RS485 Interface A| 23

Warning
The requirements of the net provider need to be full filled.
Selective hedges have to be used according requirements of the net providers.
Attention!
Damage of the terminals due to high torque
The specified maximum torques must not be exceeded!
Ensure that the connected lines are fixed with the needed torque compliant to EN 60999 for a safe connection. The needed torque depends on the type of used lines and the maximum current.
3.3 Protection Housing
As indicated in image 11 the cover of the terminal blocks can be sealed after installation. The assembled meter base and meter cover will be protected against unauthorized opening with a manufacturer label (format 8×20 mm, corner radius 0.5 mm) on both sides of the housing. ABB EV3 Energy Meter -
SealingImportant
Warranty and accuracy are void if sealing labels are removed.
3.4 EV3ABB EV3 Energy Meter - EV3 Nameplate

Nr Element Function
1 Terminal block with cover sealable terminal cover
2 Meter number with barcode 128
3 User buttons Information describe in chapter 7
4 LCD 7 digits with additional symbols
5 Meter type
6 LED test LED 1000 Imp/kWh
7 Technical nominal data
8 3 phase 4 Wire
Protection class ![Icon](https://manuals.plus/wp-

content/uploads/2022/05/Screenshot_3-305.png)
Two energy directions| Import (+A) and Export (-A) energy measurement
Security symbol|
9| Firmware version|
10| Number approval document year of certification| CE sign, year of certification, named body for MID approval
11| Manufacture year|

LCD-Display

The LCD has the following format:
– LCD size: 37.5 mm × 17 mm
– Digit size: 3.38 mm × 1,53 mmABB EV3 Energy Meter - LCD-
Display7: LCD-Display

Nr Element Function
1 Unit unit of the displayed value (kWh, W, V, A)
2 Values according defined display list
3 Indication of phase voltages Symbol off: loss of phase

Symbol is flashing: reverse sequence, reverse polarity,

Lx >1.15Un or Lx<0.8Un.

4| Indication current direction| Export
| | Import
5| OBIS Code| Identifier of the displayed value

User Buttons

ABB EV3 Energy Meter - User Buttons

Nr Element Function
1 Button „Up“ – Switch backlight of the LCD ON

– Scrolling the display items
– Enter display ALT Mode
2| Button „Down“| – Switch backlight of the LCD ON
– Scrolling the display items
– Enter display ALT Mode

The detailed functions of the buttons to switch into the different display modes is explained under the chapter 8.4 Display Modes.

Test LED

The meter has one pulse LED for active energy with 1000 Imp/kWh.
The ON-time of a pulse is 40 ms.

Components

7.1 Block diagramABB EV3 Energy Meter - Block
diagram

Current measuring: Manganin shunt
Voltage measuring: Resistor divider
A/D: Analog to digital converter for the sampled voltage and current
MCU: Micro Controller Unit
Communication interface: RS485-Interface
Data storage EV3: nonvolatile storage for energy register +A/-A and meter

parameter in EEPROM.
Display EV3:| LCD with 7 digits
LED Pulse output:| Active energy +A and -A, 1000 Imp/kWh

Functionality

8.1 Measurement
The meter measures three phase active energy with accuracy class B.
The meter provides registers for total import, total export and net energy.
Additionally, each phase L1, L2 and L3 for import and export energy are measured.
The measurement of the energy is based on the measured power according the following calculations:
Ptotal = PL1 + PL2 + PL3
Ptotal> 0: counting energy for +A
Ptotal< 0: counting energy for -A
8.1.1 Instantaneous parameter measurements
The instantaneous values can be read out via RS485 interface.

  • Voltage and current
  • Power factor
  • Active power
  • Frequency

8.2 Display Modes
The meter support three different display modes:
– AUTO Mode
– ALT Mode
8.2.1 Status DiagramABB EV3 Energy Meter - Status
Diagram No Button pressed t > ns: the parameter n can be set via data interface
10 Status diagram display mode
After power on the meter shows for 2s self-check status and goes on to the AUTO-Mode.
With the user buttons it can be changed between the different modes.
8.2.2 AUTO Mode and ALT Mode
In the AUTO Mode and ALT Mode all values which may be used for energy are displayed. This part of the display list can’t be changed by the user with any interface of the meter.
The display lists can be expanded with additional values by the user via the RS485 interface and a parameter setting program. Each list can have 32 entries.
The different values are displayed with the following formats and units:

Type of value Format unit
Energy x.xx kWh
Power x.xx W
Voltage x.x V
Current x.xx A
Power Factor x.xxx
Frequency x.xx
Firmware Version
Checksum

Tab. 7: Format/Unit Displayed Values
In the AUTO Mode the next value of the defined list is displayed automatically with a settable time period.
In the ALT Mode the next value is displayed after a user button was pressed.
8.3 Fatal Error
The meter has implemented a self-monitoring system. If the meter recognizes improper operation so that billing relevant values may not be used anymore it displays “–FF–” This status will be indicated with current display items flashing (1Hz).
8.4 Backlight EV3
Backlight will be on after pressing button, it’s useful to read meter through LCD when it in dark environment. Light on time is configurable from 5s to 60 seconds.
The back light will be turned off unconditionally if the voltage is less than 0.8Un.

RS485 Interface & Registers

Default Modbus settings:
Baud rate = 9600 (settable)
Device Address = 1 (settable)
Parity = Even (not settable)
Registers are listed in document 9AKK107991A9529