Danfoss AMI 140 Electric Drive User Guide

June 4, 2024
Danfoss

Danfoss AMI 140 Electric Drive User Guide

Warnings

Warning icons
Tools

Safety Notes

To avoid injury of persons and damages to the device, it is absolutely necessary to read and observe these instructions carefully.

Necessary assembly, start-up, and maintenance work must be performed by qualified and authorized personnel only.

Please comply with the instructions of the system manufacturer or system operator.

Disposal

This product should be dismantled and its components sorted, if possible, in various groups before recycling or disposal.
Always follow the local disposal regulations.

Mounting

Mounting

The actuator should be mounted with the valve stem in either horizontal position or pointing upwards.

Check the valve’s neck. The actuator should be in stem up position ①

(factory setting). Ensure that the actuator is mounted securely on the valve body.

The actuator is fixed to the valve body by means of a ribbed nut which requires no tools for mounting. The ribbed nut should be tightened by hand.

Wiring

AC 24 V
Connect via safety isolating transformer.

  1. Wiring
    Wiring

  2. Jumper setting
    sw=OFF actuator retracted
    sw=ON actuator extracted
    sw=OFF actuator extracted (pushed)
    sw=ON actuator retracted (pulled)
    default setting for use with AB-QM valv
    Wiring
    Jumper setting
    sw=OFF actuator retracted
    sw=ON actuator extracted
    sw=OFF actuator extracted (pushed)
    sw=ON actuator retracted (pulled)
    default setting for use with AB-QM valve
    Wiring

Do not touch anything on the PCB!
Switch off the power line before wire the actuator! Lethal voltage!

Do not remove the cover before the power supply is fully switched off

Wire the actuator according to the wiring diagram ①.
Set the jumper according to the electrical scheme ②.
Connect to power supply ③.

Connecting actuator to controller

Parallel connection of two or more actuators in not allowed.

Manual override

Manual override 
Manual override 
Manual override 

Do not remove the cover before the power supply is fully switched off.

  • Remove the cover ①.
  • Insert the Allen key 6 into the spindle ②.
  • Press and hold the button (on the bottom side of the actuator) during manual override ③.
  • Pull out the tool ④.
  • Place cover back on the actuator ⑤.
  • Electrically connect the actuator acc. to the wiring diagram.

Remark:
A ‘click’ sound after energising the actuator means that the gear wheel has jumped into normal position.

Part Name Hazardous Substances Table
Lead (Pb) Mercury (Hg)
Polybrominated biphenyls (PBB) Polybrominated diphenyl ethers (PBDE)
Connecting nut X

O: Indicates that this hazardous substance contained in all of the homogeneous material for this part is below the limit requirement in GB/T 26572;
X: Indicates that this hazardous substance contained in at least one of the homogeneous material for this part is above the limit requirementw in GB/T 26572;

Danfoss A/S
Climate Solutions • danfoss.com • +45 7488 2222

Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals