BRADFORD WHITE RE1 Lowboy Electric Water Heater Owner’s Manual

June 13, 2024
Bradford White

BRADFORD WHITE RE1 Lowboy Electric Water Heater

BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-
product

Product Information

The Residential Electric and Light Duty Commercial Electric Water Heaters are designed for residential and light-duty commercial use. The models covered by this manual include upright models, lowboy models, utility models, and wall- hung models. The manual provides troubleshooting guidance and instructions for service, which should only be performed by qualified service providers. This service manual is specifically for Bradford White residential electric and light-duty commercial electric water heaters.

Product Usage Instructions

  1. Introduction: This section provides an overview of the manual and its purpose.
  2. Tools: The following tools are recommended for performing service and maintenance on the water heaters:
    • Phillips Head Screw Driver
    • Thermometer
    • Drain Hose
    • Various Hand Tools: Pipe Wrench, Channel Locks, Pliers (common & needle nose), Wire cutters, Wire Strippers, Flash Light.
  3. General Information: This section includes commonly used formulas, such as calculating amps using watts and volts for single-phase units.
  4. The sequence of Operation: This section provides detailed information on the operation of the water heaters based on different scenarios:
    • Single Element Operation
    • Double Element Non-Simultaneous Single Phase
    • Double Element Simultaneous Single Phase 4 wire Service
    • Double Element Non-Simultaneous 3-Phase
    • Double Element Simultaneous 3-Phase
    • Double Element Non-Simultaneous Single Phase Off Peak
  5. Troubleshooting: This section provides troubleshooting guidance for identifying and resolving issues with the water heaters.
  6. Line Voltage and High Limit ECO Testing: This section provides instructions for testing the line voltage and high limit ECO of the water heaters.
  7. Heating Element Testing: This section provides instructions for testing the heating elements of the water heaters.
  8. Light-Duty Commercial Thermostat Testing: This section provides instructions for testing the thermostat of light-duty commercial water heaters.
  9. Thermostat Removal and Replacement: This section provides instructions for removing and replacing the thermostat of the water heaters.
  10. Heating Element Removal and Replacement: This section provides instructions for removing and replacing the heating elements of the water heaters.
  11. DipTube and Anode Inspection and Replacement: This section provides instructions for inspecting and replacing the diptube and anode of the water heaters.
  12. Generic Parts List: This section provides a list of generic parts for reference.
  13. Service Procedure: This section provides specific service procedures for different models of water heaters.

Note:
If a diagnosis cannot be made using the methods described in this service manual, it is recommended to contact the Bradford White Technical Support Group for further assistance.

Models Covered by This Manual:

Residential:

  • RE1, RE2 & RE3 Upright Models.
  • RE1 & RE2 Lowboy Models.
  • RE1 Utility Models.
  • RE1 Wall Hung Models.

Light Duty:

  • LE Upright Models.
  • LE Utility Models.
  • LE Lowboy.
  • LE Wall Hung.

Introduction

  • This service manual is designed to aid service and maintenance professionals on the function, proper diagnosis and repair of Bradford White residential electric and light duty commercial electric water heaters.
  • The text and illustrations in this manual provide step by step instructions to facilitate proper operation and troubleshooting procedures. Contact the Bradford White Technical Support Group immediately if diagnosis can not be made using the methods described in this service manual.

Tools

  • Multi Meter
  • 1-½ Deep Well Socket
  • ¼” Nut Driver
  • Phillips Head Screw Driver
  • Thermometer
  • Drain Hose

Various Hand Tools: Pipe Wrench, Channel Locks, Pliers (common & needle nose), Wire cutters, Wire Strippers, Flash Light.

GENERAL INFORMATION

Commonly Used Formulas

  • Amps = Watts/Volts (for single phase units) Example: 4500W/240V = 18.75A
  • Amps = Watts/Volts x 1.732 (for balanced 3 phase units) Example: 4500W/240V x 1.732 = 10.82A
  • Watts = Amps x Volts Example: 18.75A x 240V = 4500W
  • Ohms = Volts2/Watts Example: (240V) / 4500W = 12.8 Ohms

Common Service Wire Configurations

BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig-
\(1\)

Wattage Limitations at Various Voltages

  • Residential Electric Upright RE2 & RE3 Series (Non-Simultaneous Operation)
  • Residential High-Efficiency Upright RE2 Series (Non-Simultaneous Operation)
  • Residential Electric Lowboy RE2 Series (Non-Simultaneous Operation)
Maximum Wattage Element Upper/Lower Voltage
3,000 3,000/3,000 120
6,000 6,000/6,000 208, 240
6,000 6,000/6,000 277, 480
  • Residential Electric Upright RE2 & RE3 Series (Simultaneous Operation)
  • Residential High-Efficiency Upright RE2 Series (Simultaneous Operation)
  • Residential Electric Lowboy RE2 Series (Simultaneous Operation)
  • Light Duty Commercial Electric LE Series (Non-Simultaneous Operation)
  • Light Duty Commercial Electric LE Series (Simultaneous Operation)
Maximum Wattage Element Upper/Lower Voltage
3,000 1,500/1,500 120
10,000 5,000/5,000 208
11,000 5,500/5,500 240
12,000 6,000/6,000 277, 480
  • Residential Electric Utility Series (Single Element Operation)
  • Light Duty Utility Series (Single Element Operation)
Maximum Wattage Single Element Voltage
3,000 3,000 120
6,000 6,000 208, 240
6,000 6,000 277
6,000 6,000 480

Surface Mounted Thermostats
Surface-mounted thermostats are mounted into a bracket that holds the thermostat against the side of the tank. Surface-mounted thermostats respond to tank surface temperatures to sense a call for heat, set point temperature settings and high limit (ECO) activation. It is important that the entire back surface of the thermostat is in full contact or flush with the tank. Improperly mounted thermostats will lead to improper water heater operation.

BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig-
\(2\)

Direct Immersion “Screw-in” Type Heating Element

BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig-
\(3\)

SEQUENCE OF OPERATION

Residential and light duty commercial electric water heaters are designed to operate using several different operating modes. The common modes and sequence of operation are as follows:

  1. Single Element Operation.
  2. Double Element Non-Simultaneous Operation (single phase).
  3. Double Element Non-Simultaneous Operation (3 phase).
  4. Double Element Simultaneous Operation (single phase).
  5. Double Element Simultaneous Operation (3 phase).

Sequence of Operation- Single Element Operation.

  1. Line voltage is applied across terminals L1 & L3 of the thermostat. ECO is closed, so there is voltage at terminal L4 and to one side of the element.
  2. Tank is cold therefore thermostat is closed at terminal T2 (calling for heat). This completes the circuit and allows current to flow through the element.
  3. When the thermostat is satisfied, it opens at terminal T2 interrupting current flow through the element. System is now in stand-by mode, waiting for the next call for heat.

Non-simultaneous and Simultaneous Operation
Double-element electric water heaters are designed to operate in either Non- Simultaneous or Simultaneous mode.

Non-Simultaneous Mode:
Allows only one heating element to operate at a time. For example, when the tank is cold, the upper element is energized first, heating the top of the tank. Only when the upper thermostat is satisfied, the upper element is de- energized and power is directed to the lower thermostat, energizing the lower element and heating the bottom portion of the tank until the lower thermostat is satisfied. As hot water is drawn off the tank, it is replaced with cold water delivered through the diptube to the bottom of the tank. When the tank cools at the lower thermostat level, the lower thermostat will call for heat, energizing the lower element. If enough hot water is drawn from the tank, the top portion of the tank cools and the upper thermostat will call for heat, de- energizing the lower element and allowing only the top element to energize until the upper thermostat is satisfied.

Simultaneous mode:
Allows both heating elements to operate at the same time. That is, if either thermostat (upper or lower) is calling for heat, the corresponding heating element is energized independent of the other.

Sequence of Operation – Double Element, Non-Simultaneous Operation, Single Phase.

  1. Line voltage is applied across terminals L1 & L3 of the upper thermostat. ECO is closed, so there is voltage at terminal L4 and to one side of the upper and lower elements.
  2. Tank is cold. Therefore, the thermostats are closed at terminals T2 & 2 (calling for heat). The circuit is complete through the upper thermostat only, allowing current to flow through upper element.
  3. When the upper thermostat is satisfied, it opens at terminal T2, interrupting current flow through the upper element. Terminal T4 closes, allowing voltage to pass to terminal 1 of the lower thermostat. This completes the circuit through the lower thermostat and allows current flow through the lower element.
  4. When the lower thermostat is satisfied, it opens at terminal 2, interrupting current flow through lower element. The system is now in stand-by mode waiting for the next call for heat.BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(8\)

A 4-wire, double-element heater wired for simultaneous operation is essentially two single-element systems operating independently. The heaters are wired internally with two independent circuits, one circuit for each thermostat/element combination. When installed using a two-wire service, the blue and red (or white) wires will be connected together, likewise black and yellow wires will be connected together.

Sequence of Operation
Double Element, Simultaneous Operation, Single Phase, 4 wire service installation.

  1. Line voltage from circuit one is applied across terminals L1 & L3 of the lower thermostat. Likewise, line voltage from circuit two is applied across terminals L1 & L3 of the upper thermostat. ECO in both upper and lower thermostat is closed, so there is voltage at terminal L4 of each thermostat and to one side of the upper and lower elements.
  2. Tank is cold therefore both thermostats are closed at terminal T2 (calling for heat). This completes the circuit through the thermostats and allows current to flow through the elements.
  3. When either thermostat is satisfied, it will open at terminal T2, interrupting current flow through the corresponding element. As both thermostats satisfy, the system will be in stand-by mode waiting for the next call for heat. Thermostats will operate independent of each other.

Sequence of Operation
Double Element, Non-Simultaneous Operation, 3 Phase.

  1. Line voltage is applied across terminals L1 & L3 of upper thermostat. Likewise, Line voltage is applied to terminal L3 of lower thermostat. ECO in both upper & lower thermostat is closed, so there is voltage at terminal L4 of both thermostats and to one side of both upper & lower elements.
  2. Tank is cold therefore both thermostats are closed at terminal T2 (calling for heat). The circuit is complete through the upper thermostat only allowing current to flow through the upper element. ****
  3. When the upper thermostat is satisfied, it opens at terminal T2 interrupting current flow through upper element, and closes at terminal T4 allowing voltage to pass to terminal L1 of lower thermostat. This completes the circuit through the lower thermostat allowing current flow through lower element.
  4. When the lower thermostat is satisfied, it opens at terminal T2 interrupting the current flow through the lower element. The system is now in stand-by mode waiting for the next call for heat.
  5. The lower thermostat/element combination will generally cycle on and off more often than the upper. In some cases, such as a cold tank or in high-demand periods, the upper thermostat will call for heat (opening at terminal T4 and closing at terminal T2) prior to the lower thermostat being satisfied. This will interrupt current flow through the lower thermostat and element and allow current to flow through the upper element only. When the upper thermostat is satisfied, it resumes operation as described in sequence #3 above.

Sequence of Operation
Double Element, Simultaneous Operation, 3 Phase.

  1. Line voltage is applied across terminals L1 & L3 of upper thermostat. Line voltage also extends to terminal L1 of lower thermostat. Also, line voltage is applied to terminal L3 of lower thermostat. ECO in both upper & lower thermostat is closed, so there is voltage at terminal L4 of both thermostats and to one side of both upper & lower elements.
  2. Tank is cold therefore both thermostats are closed at terminal T2 (calling for heat). This completes the circuit through the thermostats and allows current to flow through the elements.
  3. When either thermostat is satisfied, it will open at terminal T2, interrupting current flow through the corresponding element. As both thermostats satisfy, the system will be in stand-by mode waiting for the next call for heat. Thermostats will operate independently of the other.

Some electric utility companies will offer discounts for using electricity during “Off Peak” Times of the day. The system allows the use of an “Off Peak” meter, which interrupts power to the lower element during high power demand periods.

Sequence of Operation
Double Element, Non-Simultaneous Operation, Single Phase, Off Peak.

  1. Line voltage is applied across terminals L1 & L3 of the upper thermostat. Line voltage from off peak meter is supplied to terminal L1 of lower thermostat. ECO in the upper thermostat is closed, so there is voltage at terminal L4 of upper thermostat and to one side of the upper element.
  2. Tank is cold therefore both thermostats are closed at terminal T2 (calling for heat). The circuit is complete through the upper thermostat only, allowing current to flow through upper element.
  3. When the upper thermostat is satisfied, it opens at terminal T2 interrupting current flow through upper element and closes at terminal T4 allowing voltage to pass to one side of the lower element. This completes the circuit through the lower thermostat and off-peak meter allowing current flow through the lower element.
  4. When the lower thermostat is satisfied, it opens at terminal T2 interrupting current flow through the lower element. The system is now in stand-by mode waiting for the next call for heat
  5. During peak power demand periods as determined by the local utility, the off-peak meter will interrupt power to terminal L1 of the lower thermostat. Only the top thermostat/element combination is allowed to operate during this period.BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(17\)

TROUBLESHOOTING

The most common cause for improper electric water heater operation can be linked to heating element failure.
When troubleshooting an electric water heater with the incidence of “No Hot Water” or “Insufficient Amount of Hot Water,” It’s always a good idea to check the heating elements first by following the procedure on page 15.

Common Heating Element Failures:

  1. Dry Firing. The element may be partially submerged in water or most likely, completely exposed with no water in the tank. In some cases, sediment or lime buildup around an element can eventually cause an air pocket, and within seconds, result in a dry-fired element. At this point the element becomes inoperative. When element replacement is required, be sure the tank is full of water prior to energizing the water heater.

  2. Grounded Element. An element with a short circuit to the ground will in most cases cause the circuit breaker in the service panel to open or shut off. In some cases, there may not be enough current draw for the circuit breaker to open. This will allow the heating element to be in continuous operation resulting in overheated water, limited only by the ECO or Energy Cut Out. Repeated actuation of the ECO is
    usually the result of a grounded element.

  3. Sediment build-up. Slow hot water recovery can usually be traced back to sediment or lime build-up around the heating element. Sediment build-up can also over time cause a dry-fired element.

Figure 1 , below shows a common “Screw-In” type heating element identifying certain features commonly referred to throughout this manual.

BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig-
\(18\)

Quick Step Plan to Hot Water

WARNING
High voltage exposure. Use caution when making voltage checks to avoid personal injury.

  1. TURN OFF power to the water heater and check all wire connections to ensure they are tight and corrosion-free.
  2. Turn power “ON” and determine that service voltage is present, and the high limit (ECO) has not been actuated (see procedure on page 14).
  3. Check for inoperative heating elements (see procedure on page 15).
  4. Check for proper thermostat operation (see procedures beginning on page 16). NOTE: Thermostat testing procedures assume items 2 and 3 above are in working order.

BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig-
58

SERVICE PROCEDURE RE-I Line Voltage & High Limit (ECO) Testing

Line Voltage Testing

WARNING
High voltage exposure. Use caution when making voltage checks to avoid personal injury.

  1. Turn “OFF” power to the water heater.
  2. Remove access cover(s) from the front of the water heater. Remove insulation and plastic cover from the thermostat.
  3. Set multi-meter to “Volts AC.”
  4. Turn the power “ON” to the water heater.
  5. Check voltage across terminals L1 & L3 of the upper thermostat (see Figure 2).
    • The rated voltage IS present, and power to the water heater is okay.
    • The rated voltage is NOT present, Check the circuit breaker at the service panel.

High Limit (ECO) Testing

  1. Check voltage across terminals L1 & L4 upper thermostat (see Figure 3).
    • Rated Voltage IS present, ECO is okay.
    • Rated voltage NOT present, proceed to step 2.
  2. Turn the power “OFF” to the water heater and firmly press the ECO reset button on the thermostat(s). Turn power “ON” and recheck voltage across terminals L1 & L4 of the upper thermostat (see Figure 3).
    • Rated voltage IS present, the ECO has previously opened indicating the water in the tank, at some point did overheat, check the following:
    1. The thermostat must be in full contact with the tank.
    2. Be sure the heating element(s) is not shorted to ground (see page 15).
    3. Proper thermostat operation (see procedures beginning on page 16).
    • Rated voltage NOT present, water in the tank may be overheated.
    1. If the water is hot, turn “OFF” power to the water heater and flow water through the tank to cool below the set point of the upper thermostat. Recheck voltage per step 1.
    2. If the water is cool, Replace the upper thermostat.

Heating Element Testing

Testing For Open Or Burned Out Element

WARNING
High voltage exposure. Be sure power is turned OFF to the water heater prior to performing this procedure.

  • Step 1. TURN OFF POWER TO THE WATER HEATER
  • Step 2. Remove access cover(s) from front of the water heater. Remove insulation and plastic cover from the thermostat.
  • Step 3. Disconnect wires from the heating element(s).
  • Step 4. Set multi-meter to “ohms” setting.
  • Step 5. Touch probes of multi-meter to screw terminals of the heating element(s)(see Figure 4).
  • Step 6. Reading should be 12.8 ohms (±6%) for a 240 volt, 4500 watt element: Ohms = Volts2 Watts

A reading outside the range using the formula beyond (±6%), indicates a bad element and the element must be replaced.

Testing For Heating Element Short Circuit To Ground

  • Step 1. TURN OFF THE POWER TO THE WATER HEATER
  • Step 2. Remove access cover(s) from the front of the water heater. Remove insulation and plastic cover from the thermostat.
  • Step 3. Disconnect wires from the heating element(s).
  • Step 4. Set multi-meter to “ohms” setting.

The terminal of the heating element and the other on the element flange (see Figure 5). There should be no reading on the ohm meter. Any reading indicates a grounded element and the element must be replaced. Repeat this step for the other screw terminal.

Residential Thermostat Testing

Single Element Operation or Double Element, 4 Wire, Simultaneous, Single Phase Operation

WARNING
High voltage exposure. Use caution to avoid personal injury during this procedure.

Water In Tank Is Cold With Power ON

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Turn power “ON” to water heater.
  3. Set multi-meter to “Volts AC.”
  4. Check across terminals L4 and T2 of thermostat (see Figure 6).
    • A) Rated voltage NOT present, Recheck ECO. If ECO is okay, replace thermostat.
    • B) Rated voltage IS present, proceed to next step.
  5. Check across element terminals (see Figure 7).
    • A) Rated voltage NOT present, check wire connections from thermostat to element.
    • B) Rated voltage IS present, Repeat element testing see page 15.

Water Temperature In Tank Is Above Thermostat Setting

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Turn power “ON” to water heater.
  3. Set multi-meter to “Volts AC.”
  4. See Figure 6 above, check across terminals L4 and T2 of thermostat.
    • A) Rated voltage IS present, replace thermostat.
    • B) Rated voltage NOT present, thermostat is okay.
    • C) Lower than rated voltage IS present, recheck for grounded element (see page 15).BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(23\)

Double Element, Non-Simultaneous, Single Phase Operation.

WARNING
High voltage exposure. Use caution to avoid personal injury during this procedure.

Water In Tank Is Cold With Power ON.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Turn power “ON” to the water heater.
  3. Set multi-meter to “Volts AC.”
  4. Check across terminals L4 and T2 of the upper thermostat (see Figure 8).
  5. Rated voltage NOT present, Recheck ECO. If ECO is okay, replace the thermostat.
  6. Rated voltage IS present, proceed to the next step.
  7. Check across element terminals (see Figure 9).
  8. Rated voltage NOT present, check wire connections from the thermostat to the element.
  9. Rated voltage IS present, Repeat element testing see page 15.BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(24\)

Tank Does Not Deliver Enough Hot Water.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Turn the power “ON” to the water heater and set the multi-meter to “Volts AC.”
  3. Adjust the temperature setting of the upper thermostat to the highest setting. The water temperature in tank must be below the thermostat setting for this test.
  4. See Figure 8 above, check the voltage across terminals L4 and T2 of upper thermostat.
    • Rated voltage IS present, okay, the upper thermostat is calling for heat. Go to step 5 below.
    • Rated voltage NOT present, replace the upper thermostat.
  5. Adjust the temperature setting of the upper thermostat to the minimum setting. The water temperature in the tank must be above the thermostat setting for this test.
  6. Check voltage across terminals L4 and T4 of the upper thermostat (see Figure 10).
    • Rated voltage NOT present, replace the upper thermostat.
    • The rated voltage IS present, thermostat is okay. Go to step 7 on the next page.
  7. Check voltage across terminal L4 of the upper thermostat and terminal 1 of lower thermostat (see Figure 11).
    • Rated voltage NOT present, – check wire connection between thermostats.
    • Rated voltage IS present, okay, go to step 8.
  8. Adjust the lower thermostat to the highest setting. The water temperature in the tank must be below the lower thermostat setting for this test.
  9. Check voltage across terminal L4 of the upper thermostat and terminal 2 of the lower thermostat (see Figure 12).
    • Rated voltage NOT present, replace the lower thermostat.
    • The rated voltage IS present, thermostat is okay.

WARNING
Be sure thermostats are reset to their original temperature settings as found prior to thermostat testing

The water Temperature In the Tank Is Above the Thermostat Setting.

  1. This procedure assumes Line voltage, ECO and elements are in working order.
  2. Adjust the upper and lower thermostats to the lowest setting.
  3. Turn the power “ON” to the water heater and set the multi-meter to “Volts AC.”
  4. Check across terminals L4 and T2 of the upper thermostat (see Figure 8 on page 17).
    • Rated voltage IS present, replace the upper thermostat.
    • Rated voltage NOT present, upper thermostat is okay. Go to step 5 below.
    • Lower than rated voltage IS present, recheck for grounded upper element (see page 15).
  5. Check across terminals L4 and 2 of the lower thermostat (see Figure 12).
    • Rated voltage IS present, replace the lower thermostat.
    • Rated voltage NOT present, lower thermostat is okay.
    • Lower than rated voltage IS present, recheck for grounded lower element (see page 15).

Double Element, Non-Simultaneous, Three Phase Operation.

WARNING
High voltage exposure. Use caution to avoid personal injury during this procedure.

Water In Tank Is Cold With Power ON.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Turn the power “ON” to the water heater.
  3. Set multi-meter to “Volts AC.”
  4. Check across terminals L4 and T2 of the upper thermostat (see Figure 13).
    • Rated voltage NOT present, recheck ECO. If ECO is okay, replace the thermostat.
    • Rated voltage IS present, proceed to the next step.
  5. Check across element terminals (see Figure 14).
    • Rated voltage NOT present, check wire connections from the thermostat to the element.
    • Rated voltage IS present, repeat element testing, see page 15.BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(28\)

Tank Does Not Deliver Enough Hot Water.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Turn the power “ON” to the water heater and set the multi-meter to “Volts AC.”
  3. Adjust the temperature setting of the upper thermostat to the highest setting. The water temperature in tank must be below thermostat setting for this test.
  4. See Figure 13 above, check the voltage across terminals L4 & T2 of the upper thermostat.
    • Rated voltage IS present, okay, the upper thermostat is calling for heat. Go to step 5 below.
    • Rated voltage NOT present, replace the upper thermostat.
  5. Adjust the temperature setting of the upper thermostat to the minimum setting. The water temperature in tank must be above the thermostat setting for this test.
  6.  Check voltage across terminals T4 of the upper thermostat & L3 of the lower thermostat (see Figure 15).
    • Rated voltage NOT present, replace the upper thermostat.
    • The rated voltage IS present, upper thermostat is okay. Go to step 7 on next page.
  7. Check voltage across terminals L1 & L3 of the lower thermostat (see Figure 16).
    • Rated voltage NOT present, check wire connection between thermostats.
    • Rated voltage is present, okay, go to step 8.
  8. Adjust lower thermostat to the highest setting. The water temperature in the tank must be below the lower thermostat setting for this test.
  9. Check voltage across terminal L4 & T2 of the lower thermostat (see Figure 17).
    • Rated voltage NOT present, recheck ECO (see page 14). If ECO is okay, replace the lower thermostat.
    • Rated voltage IS present, thermostat is ok. Check wire connection to the lower element. If the connection is okay, recheck the lower element (see page 15).

WARNING
Be sure thermostats are reset to their original temperature settings as found prior to thermostat testing

The water Temperature In the Tank Is Above the Thermostat Setting.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Adjust the upper and lower thermostats to the lowest setting.
  3. Turn the power “ON” to the water heater and set the multi-meter to “Volts AC.”
  4. Check across terminals L4 and T2 of the upper thermostat (see Figure 13 on page 19).
    • Rated voltage IS present, replace the upper thermostat.
    • Rated voltage NOT present, upper thermostat is okay. Go to step 5 below.
    • Lower than rated voltage IS present, recheck for grounded upper element (see page 15).
  5. Check across terminals L4 and T2 of the lower thermostat (see Figure 17).
    • Rated voltage IS present, replace the lower thermostat.
    • Rated voltage NOT present, lower thermostat is okay.
    • Lower than rated voltage IS present, recheck for grounded lower element (see page 15).

Double Element, Simultaneous, Three Phase Operation.

WARNING
High voltage exposure. Use caution to avoid personal injury during this procedure.

Water In Tank Is Cold Or Not Enough Hot Water With Power ON.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Adjust temperature setting for both thermostats to the highest setting.
  3. Turn power “ON” to water heater.
  4. Set multi-meter to “Volts AC.”
  5. Check across terminals L4 and T2 of upper thermostat (see Figure 18).
    • Rated voltage NOT present, recheck ECO (see page 14). If ECO is okay, replace thermostat.
    • Rated voltage IS present, proceed to next step.
  6. Check across upper element terminals (see Figure 19).
    • Rated voltage NOT present, check wire connections from thermostat to element.
    • Rated voltage IS present, repeat element testing see page 15.BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(32\)
  7. Check across terminals L1 & L3 of lower thermostat (see Figure 20).
    • Rated voltage NOT present, check wire connections from upper to lower thermostats.
    • Rated voltage IS present, okay, go to step 7.
  8. Check across terminals L4 and T2 of lower thermostat (see Figure 21).
    • Rated voltage NOT present, recheck ECO (see page 14). If ECO is okay, replace thermostat.
    • Rated voltage IS present, proceed to next step.
  9. Check across lower element terminals.
    • Rated voltage NOT present, check wire connections from thermostat to element.
    • Rated voltage IS present, repeat element testing see page 15.BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(33\)

WARNING
Be sure thermostats are reset to their original temperature settings as found prior to thermostat testing

Water Temperature In Tank Is Above Thermostat Setting.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Adjust upper and lower thermostat to the lowest setting.
  3. Turn power “ON” to water heater.
  4. Set multi-meter to “Volts AC.”
  5. Check across terminals L4 and T2 of upper thermostat (see Figure 22).
    • Rated voltage IS present, replace upper thermostat.
    • Rated voltage NOT present, upper thermostat is okay. Go to step 6 below.
    • Lower than rated voltage IS present, recheck for grounded upper element (see page 15).
  6. Check across terminals L4 and T2 of lower thermostat (see Figure 23).
    • Rated voltage IS present, replace lower thermostat.
    • Rated voltage NOT present, lower thermostat is okay.
    • Lower than rated voltage IS present, recheck for grounded lower element (see page 15).

Double Element, Non-Simultaneous, Single Phase, Off Peak Operation.

Water In Tank Is Cold With Power ON.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Turn power “ON” to water heater.
  3. Set multi-meter to “Volts AC.”
  4. Check across terminals L4 and T2 of upper thermostat (see Figure 24).
    • Rated voltage NOT present, recheck ECO (see page 14). If ECO is okay, replace thermostat.
    • Rated voltage IS present, proceed to next step.
  5. Check across element terminals (see Figure 25).
    • Rated voltage NOT present, check wire connections from thermostat to element.
    • Rated voltage IS present, Repeat element testing see page 15.BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(36\)

Tank Does Not Deliver Enough Hot Water.

  1. This procedure assumes line voltage, ECO and elements are in working order. Be sure OFF PEAK meter has not interrupted line voltage.
  2. Turn power “ON” to water heater and set multi-meter to “Volts AC.”
  3. Adjust temperature setting of upper & lower thermostat to the highest setting. Water temperature in tank must be below thermostat setting for this test.
  4. See Figure 24 above. Check voltage across terminals L4 & T2 of upper thermostat.
    • Rated voltage IS present, okay, upper thermostat is calling for heat. Go to step 5 below.
    • Rated voltage NOT present, replace upper thermostat.
  5. Adjust temperature setting of upper thermostat to the minimum setting. Water temperature in tank must be above thermostat setting for this test.
  6. Check voltage across terminals T4 of upper thermostat & L1 of lower thermostat (see Figure 26).
    • Rated voltage NOT present, replace upper thermostat.
    • Rated voltage IS present, upper thermostat is okay. Go to step 7 on next page.
  7. Check voltage across terminal T4 of upper thermostat & T2 of lower thermostat. (see Figure 27).
    • Rated voltage NOT present, replace lower thermostat.
    • Rated voltage is present, okay, go to step 8.
  8. Check voltage across lower element (see Figure 28).
    • Rated voltage NOT present, check wire connections between thermostats & element.
    • Rated voltage IS present, repeat element testing see page 15.BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(38\)

WARNING
Be sure thermostats are reset to their original temperature settings as found prior to thermostat testing

Water Temperature In Tank Is Above Thermostat Setting.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Adjust upper and lower thermostats to the lowest setting.
  3. Turn power “ON” to water heater and set multi-meter to “Volts AC.”
  4. Check across terminals L4 and T2 of upper thermostat (see Figure 24 on page 23).
    • Rated voltage IS present, replace upper thermostat.
    • Rated voltage NOT present, upper thermostat is okay. Go to step 5 below.
    • Lower than rated voltage IS present, recheck for grounded upper element (see page 15).
  5. Check across terminals T4 of upper thermostat and T2 of lower thermostat (see Figure 27 above).
    • Rated voltage IS present, replace lower thermostat.
    • Rated voltage NOT present, lower thermostat is okay.
    • Lower than rated voltage IS present, recheck for grounded lower element (see page 15).

Light Duty Commercial Thermostat Testing

Double Element, Non-Simultaneous, Single Phase Operation.

WARNING
High voltage exposure. Use caution to avoid personal injury during this procedure.

Water In Tank Is Cold With Power ON.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Turn power “ON” to water heater.
  3. Set multi-meter to “Volts AC.”
  4. Check across terminals L4 and T2 of upper thermostat (see Figure 29).
    • Rated voltage NOT present, recheck ECO (see page 14). If ECO is okay, replace thermostat.
    • Rated voltage IS present, proceed to next step.
  5. Check across element terminals (see Figure 30).
    • Rated voltage NOT present, check wire connections from thermostat to element.
    • Rated voltage IS present, repeat element testing see page 15.BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(39\)

Tank Does Not Deliver Enough Hot Water.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Turn power “ON” to water heater and set multi-meter to “Volts AC.”
  3. Adjust temperature setting of upper & lower thermostat to the highest setting. Water temperature in tank must be below thermostat setting for this test.
  4. See Figure 29 above. Check voltage across terminals L4 & T2 of upper thermostat.
    • Rated voltage IS present, okay, upper thermostat is calling for heat. Go to step 5 below.
    • Rated voltage NOT present, replace upper thermostat.
  5. Adjust temperature setting of upper thermostat to the minimum setting. Water temperature in tank must be above thermostat setting for this test.
  6. Check voltage across terminals L3 & T4 of upper thermostat (see Figure 31).
    • Rated voltage NOT present, replace upper thermostat.
    • Rated voltage IS present, upper thermostat is okay. Go to step 7 on next page.
  7. Check voltage across terminal L3 of upper thermostat & T2 of lower Thermostat. (see Figure 32).
    • Rated voltage NOT present, replace lower thermostat.
    • Rated voltage is present, okay, go to step 8.
  8. Check voltage across lower element (see Figure 33).
    • Rated voltage NOT present, Check wire connections between thermostats & element.
    • Rated voltage IS present, repeat element testing see page 15.BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(41\)

WARNING
Be sure thermostats are reset to their original temperature settings as found prior to thermostat testing

Water Temperature In Tank Is Above Thermostat Setting.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Adjust upper and lower thermostat to the lowest setting.
  3. Turn power “ON” to water heater and Set multi-meter to “Volts AC.”
  4. See Figure 32 above. Check across terminal L3 of upper thermostat & T2 of lower thermostat.
    • Rated voltage IS present, replace lower thermostat.
    • Rated voltage NOT present, okay, go to step 5 below.
    • Lower than rated voltage IS present, recheck for grounded lower element see page 15.
  5. Check across terminal L4 & T2 of upper thermostat (see Figure 34).
    • Rated voltage IS present, replace upper thermostat.
    • Rated voltage NOT present, upper thermostat is okay.
    • Lower than rated voltage IS present, recheck for grounded upper element see page 15.

Double Element, Simultaneous, Single Phase Operation.

Water In Tank Is Cold Or Not Enough Hot Water With Power ON.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Adjust temperature setting for both thermostats to the highest setting.
  3. Turn power “ON” to water heater.
  4. Set multi-meter to “Volts AC.”
  5. Check across terminals L4 and T2 of upper thermostat (see Figure 35).
    • Rated voltage NOT present, recheck upper ECO (see page 14). If ECO is okay, replace upper thermostat.
    • Rated voltage IS present, proceed to next step.
  6. Check across upper element terminals (see Figure 36).
    • Rated voltage NOT present, check wire connections from thermostat to upper element.
    • Rated voltage IS present, repeat element testing see page 15.
  7. Check across terminal L3 of upper thermostat and T2 of lower thermostat (see Figure 37).
    • Rated voltage NOT present, check ECO (see page 14) & wire connections at upper & lower thermostats. If okay, replace lower thermostat.
    • Rated voltage IS present, proceed to next step.
  8. Check across lower element terminals (see Figure 38).
    • Rated voltage NOT present, check lower element wire connections to the thermostats.
    • Rated voltage IS present, repeat lower element testing see page 15BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(43\)BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(44\)

WARNING
Be sure thermostats are reset to their original temperature settings as found prior to thermostat testing

Water Temperature In Tank Is Above Thermostat Setting.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Adjust upper and lower thermostat to the lowest setting.
  3. Turn power “ON” to water heater.
  4. Set multi-meter to “Volts AC.”
  5. Check across terminals L4 and T2 of upper thermostat (see Figure 39).
    • Rated voltage IS present, replace upper thermostat.
    • Rated voltage NOT present, upper thermostat is okay. Go to step 6 below.
    • Lower than rated voltage IS present, recheck for grounded upper element see page 15.
  6. Check across terminal L3 of upper thermostat and T2 of lower thermostat (see Figure 40).
    • Rated voltage IS present, replace lower thermostat.
    • Rated voltage NOT present, lower thermostat is okay.
    • Lower than rated voltage IS present, recheck for grounded lower element see page 15.

Double Element, Non-Simultaneous, Three Phase Operation.

Water In Tank Is Cold With Power ON.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Turn power “ON” to water heater.
  3. Set multi-meter to “Volts AC.”
  4. Check across terminals L4 and T2 of upper thermostat (see Figure 41).
    • Rated voltage NOT present, recheck upper ECO. If ECO is okay, replace thermostat.
    • Rated voltage IS present, proceed to next step.
  5. Check across element terminals (see Figure 42).
    • Rated voltage NOT present, check wire connections from thermostat to element.
    • Rated voltage IS present, repeat element testing see page 15.BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(47\)

Tank Does Not Deliver Enough Hot Water.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Turn power “ON” to water heater and set multi-meter to “Volts AC.”
  3. Adjust temperature setting of upper & lower thermostat to the highest setting. Water temperature in tank must be below thermostat setting for this test.
  4. See Figure 41 above. Check voltage across terminals L4 & T2 of upper thermostat.
    • Rated voltage IS present, okay, upper thermostat is calling for heat. Go to step 5 below.
    • Rated voltage NOT present, replace upper thermostat.
  5. Adjust temperature setting of upper thermostat to the minimum setting. Water temperature in tank must be above thermostat setting for this test.
  6. Check voltage across terminals L3 & T4 of upper thermostat (see Figure 43).
    • Rated voltage NOT present, replace upper thermostat.
    • Rated voltage IS present, upper thermostat is okay. Go to step 7 on next page.
  7. Check voltage across terminal L1 of upper thermostat & T2 of lower thermostat. (see Figure 44).
    • Rated voltage NOT present, Replace lower thermostat.
    • Rated voltage is present, okay, go to step 8.
  8. Check voltage across lower element (see Figure 45).
    • Rated voltage NOT present, check wire connections between thermostats & element.
    • Rated voltage IS present, repeat element testing see page 15.BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(49\)

WARNING
Be sure thermostats are reset to their original temperature settings as found prior to thermostat testing

Water Temperature In Tank Is Above Thermostat Setting.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Adjust upper and lower thermostat to the lowest setting.
  3. Turn power “ON” to water heater and Set multi-meter to “Volts AC.”
  4. See Figure 44 above. Check across terminal L1 of upper thermostat & T2 of lower thermostat.
    • Rated voltage IS present, replace lower thermostat.
    • Rated voltage NOT present, okay, go to step 5 below.
    • Lower than rated voltage IS present, recheck for grounded lower element.
  5. Check across terminal L4 & T2 of upper thermostat (see Figure 46).
    • Rated voltage IS present, replace upper thermostat.
    • Rated voltage NOT present, upper thermostat is okay.
    • Lower than rated voltage IS present, recheck for grounded upper element, see page 15.

Double Element, Simultaneous, Three Phase Operation.

WARNING
High voltage exposure. Use caution to avoid personal injury during this procedure.

Water In Tank Is Cold Or Not Enough Hot Water With Power ON.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Adjust temperature setting for both thermostats to the highest setting.
  3. Turn power “ON” to water heater.
  4. Set multi-meter to “Volts AC.”
  5. Check across terminals L4 and T2 of upper thermostat (see Figure 47).
    • Rated voltage NOT present, recheck upper ECO (see page 14). If ECO is okay, replace upper thermostat.
    • Rated voltage IS present, proceed to next step.
  6. Check across upper element terminals (see Figure 48).
    • Rated voltage NOT present, check wire connections from thermostat to upper element.
    • Rated voltage IS present, repeat element testing see page 15BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(51\)
  7. Check across terminal L4 of lower thermostat and T2 of lower thermostat (see Figure 49).
    • Rated voltage NOT present, check ECO (see page 14) & wire connections at upper & lower thermostats. If okay, replace lower thermostat.
    • Rated voltage IS present, proceed to next step.
  8. Check across lower element terminals (see Figure 50).
    • Rated voltage NOT present, check lower element wire connections to thermostat.
    • Rated voltage IS present, repeat lower element testing see page 15.BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(52\)

WARNING
Be sure thermostats are reset to their original temperature settings as found prior to thermostat testing

Water Temperature In Tank Is Above Thermostat Setting.

  1. This procedure assumes line voltage, ECO and elements are in working order.
  2. Adjust upper and lower thermostat to the lowest setting.
  3. Turn power “ON” to water heater.
  4. Set multi-meter to “Volts AC.”
  5. Check across terminals L4 and T2 of upper thermostat (see Figure 51).
    • Rated voltage IS present, replace upper thermostat.
    • Rated voltage NOT present, upper thermostat is okay. Go to step 6 below.
    • Lower than rated voltage IS present, recheck for grounded upper element see page 15.
  6. Check across terminals L4 & T2 of lower thermostat (see Figure 52).
    • Rated voltage IS present, replace lower thermostat.
    • Rated voltage NOT present, lower thermostat is okay.
    • Lower than rated voltage IS present, recheck for grounded lower element.1

Thermostat Removal and Replacement

WARNING
High voltage exposure. Be sure power is “OFF” when performing this procedure.

Thermostat Removal

  1. Turn power “OFF” to water heater.
  2. Remove access cover and insulation.
  3. Remove plastic thermostat protector from thermostat.
  4. Disconnect wires from thermostat terminals. It may be necessary to label wires for proper re-connection to new thermostat.
  5. Note thermostat temperature setting for proper setting of new thermostat.
  6. Slide thermostat upwards and out of mounting bracket.

Thermostat Replacement

  1. Use a stiff brush to remove any debris or loose scale from tank surface where new thermostat will be installed.
  2. Slide new thermostat down into thermostat bracket until it snaps into place. IMPORTANT! Thermostat must sit completely flat or flush to tank surface. An improperly installed thermostat will cause improper water heater operation.
  3. Refer to the wire diagram located on the inside of the access cover and reconnect wires to the thermostat. Be sure wire connections are snug and corrosion free. Do not over tighten, doing so may damage thermostat.
  4. Set thermostat to the original thermostat setting found on the old thermostat.
  5. Re-install plastic thermostat protector.
  6. Re-install insulation and access cover.
  7. Restore power to water heater and verify proper heater operation.BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(55\)

Heating Element Removal and Replacement

WARNING

  • High voltage exposure. Be sure power is “OFF” when performing this procedure.
  • Heater components and stored water may be HOT when performing the following steps in this procedure. Take necessary precaution to prevent personal injury.

Heating Element Removal

  1. Turn power “OFF” To water heater.

  2. Turn off cold water supply to heater. Connect hose to drain spigot of water heater and route to an open drain. Open a nearby hot water faucet to vent heater for draining. Open drain spigot of water heater and allow heater to drain
    to a point below the element(s).

  3. Close drain spigot and remove hose.

  4. Remove access cover and insulation.

  5. Remove plastic thermostat protector from thermostat.

  6. Disconnect wires from element terminals.

  7. Remove element from tank using 1-½ deep well socket or appropriate wrench. Unscrew element counter-clockwise to remove from tank.

  8. Be sure to remove old element gasket from the tank. It is not recommended to be re-used.

Heating Element Replacement

  1. Check element terminal block for proper electrical rating. NOTE: Some elements have dual ratings, be sure to check all surfaces of the element terminal block (see illustration below).
  2. Apply new element gasket to the new element. Be sure gasket is seated flat against element flange without rolls or gaps (see illustration below).
  3. Clean any debris from element fitting on tank. Lubricate element threads as needed with thread lubricant.
  4. Thread new element clockwise into tank. Tighten element using 1-½ deep well socket or appropriate wrench. Do not over tighten, over tightening may damage element gasket.
  5. Reconnect wires to element, be sure wires are snug and corrosion free. Do not over tighten, doing so may damage terminal block.
  6. Resume water supply to heater, be sure tank is full of water and check for leaks.
  7. Re-install plastic thermostat protector.
  8. Re-install insulation and access cover.
  9. To resume operation, BE SURE TANK IS FULL OF WATER and restore power to water heater. Verify proper heater operation.BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig- \(56\)

Dip Tube and Anode Inspection and Replacement

Diptube Inspection and Replacement

WARNING
Heater components and stored water may be HOT when performing the following steps in this procedure. Take necessary precaution to prevent personal injury.

  • Step 1. Turn power “OFF” to water heater.
  • Step 2. Turn off cold water supply to heater. Connect hose to drain spigot of water heater and route to an open drain. Open a nearby hot water faucet to vent heater for draining. Open drain spigot of water heater and allow heater to drain to a point below the inlet connection nipple.
  • Step 3. Close drain spigot and remove hose.
  • Step 4. Disconnect inlet nipple from plumbing system.
  • Step 5. With an appropriate wrench, remove inlet nipple/dip tube from the water heater. Use caution not to damage nipple threads.
  • Step 6. Visually inspect inlet nipple/dip tube. Inlet nipple/dip tube should be free of cracks and any blockage. Hydro-jets located near the bottom of the dip tube should be open and free of any blockage. Anti-siphon hole located approximately 6″ from the bottom of nipple, should be free of any blockage. Any damage such as cracks, restriction due to deformation or unintentional holes are not field repairable and the inlet nipple/dip tube must be replaced.
  • Step 7. Upon completion of inspection or subsequent replacement, reinstall inlet nipple/dip tube into heater. Ensure pipe dope is used on the nipple’s threads. Connect nipple to plumbing system, close spigot and remove drain hose, resume water supply and refill heater with water.
  • Step 8. To resume operation, BE SURE TANK IS FULL OF WATER and turn power “ON” to water heater.

Anode Inspection and Replacement

  • Step 1. Turn power “OFF” to water heater.
  • Step 2. Turn off cold water supply to heater. Connect hose to drain spigot of water heater and route to an open drain. Open a nearby hot water faucet to vent heater for draining. Open drain spigot of water heater and allow heater to drain to a point below the outlet connection nipple.
  • Step 3. Close drain spigot and remove hose.
  • Step 4. Disconnect outlet nipple from plumbing system.
  • Step 5. With an appropriate wrench, remove outlet nipple/anode from the water heater. Use caution not to damage nipple threads.
  • Step 6. Visually inspect outlet nipple/anode. Outlet nipple/anode should show signs of depletion, this is normal. If depletion is ½ of the original anode diameter (original diameter approximately ¾”), replacement is recommended. If any of the steel core of the anode is exposed, replacement is recommended.
  • Step 7. Upon completion of inspection or subsequent replacement, reinstall outlet nipple/anode into heater. Ensure pipe dope is used on the nipple’s threads. Connect nipple to plumbing system, close spigot and remove drain hose, resume water supply and refill heater with water.
  • Step 8. To resume operation, BE SURE HEATER IS FULL OF WATER and turn power “ON” to water heater.

Generic Parts List

BRADFORD-WHITE-RE1-Lowboy-Electric-Water-Heater-fig-
\(57\)

  1. T&P Relief Valve
  2. Heat Trap Insert (Outlet)
  3. Hot Water Outlet/Anode
  4. Cover Conduit/Ground
  5. Junction Box Cover
  6. Heat Trap Insert (Inlet)
  7. Cold Water Inlet Diptube
  8. Upper Thermostat Protector
  9. Upper Thermostat
  10. Thermostat Mounting Bracket
  11. Heating Element
  12. Element Gasket
  13. Access Cover
  14. Lower Thermostat Protector
  15. Lower Thermostat (59T)
  16. Brass Drain Valve
  17. Thermostat w/High Limit (59T/66T)
  18. ASSE Approved Mixing Device
  19. Kit Heat Trap

Contact Information

United States

Canada

For U.S. and Canada field service, contact your professional installer or local Bradford White sales representative.

International

©2022, Bradford White Corporation, USA. All rights reserved.

www.bradfordwhite.com.