SVEN RT-500 UPS for Prolonged Power Supply
BUYER RECOMMENDATIONS
- Unpack the device carefully. Make sure there are no accessories left in the box. Check up the device for damage; if the product was damaged during transportation, address the firm which carried out the delivery; if the product functions incorrectly address the dealer at once.
- Do not switch on the speaker system immediately after you bring it into a room from an environment with a negative temperature! After unpacking, the speaker system should be kept in conditions of room temperature for at least 4 hours
- Before installing and using the speaker system, read this manual carefully and keep it for future reference.
- Shipping and transportation equipment is permitted only in the original container.
- Does not require special conditions for realization.
- Dispose of in accordance with regulations for the disposal of household and computer equipment.
- The date of manufacture of the product is indicated on the box.
PRECAUTIONS
Before operating this device, please carefully read the following safety instructions:
- Connect/disconnect the battery produced when the UPS is disconnected from the mains.
- Before the operation, a battery should be charged (the battery is not included) for at least 12 hours. For this purpose, the UPS should be switched on without load.
- If a battery is discharged completely or the UPS has not been operated for more than three months, the battery should be charged completely as well. Failure to comply with storage rules of batteries will result in their service life decrease.
- The connected load power must not exceed the rated power indicated in the technical specifications table.
- Place the UPS in closed rooms with the regulated temperature and humidity of the air. The UPS case temperature can rise during its operation, it is a normal phenomenon.
- Do not open the battery: escaped electrolyte is dangerous for the skin and eyes.
- Disconnect the UPS from the mains before connection/disconnection of load cables to the UPS to avoid electric shock.
- In case of an emergency, turn off the UPS and disconnect the power cord from the mains.
- It is strictly prohibited to open the device case ― there is a high voltage inside. In case of any problems, connect to the service center. The list of authorized service centers is available on www.sven.fi.
- UPS should be serviced by qualified specialists only.
- It is strictly prohibited to use the UPS under the following conditions:
- outdoors;
- in a dusty environment containing highly inflammable gases;
- at a temperature higher than 40 °C or lower than 5 °C
- at the relative humidity level higher than 90 %;
- indirect sunlight or close to heating elements;
- in places with elevated vibration.
- In case of fire use a powder fire extinguisher only, as using water can cause electric shock.
Try to install the UPS in close proximity to a power supply, in such way it will be easier to un-plug the device as may be required.
Note. Periodic maintenance of the device is recommended, as well as periodic control of the battery state to provide the device’s operability.
Caution! There is high voltage inside on isolated components, which can result in electric shock.
PACKAGE CONTENTS
- Uninterruptible power supply — 1 pc
- Operation Manual — 1 pc
- Warranty card — 1 pc
TECHNICAL DESCRIPTION
Operating principle
- Models of SVEN RТ are designed to operate with lead-acid maintenance-free 12 V batteries of AGM type.
- Models of RТ series fall in the line-interactive uninterruptible power supply of continuous action with prolonged backup time. The principle of their operation is based on the transformation of the direct current of external batteries to alternating current. The current waveform at the output is the regular sinusoidal wave.
- Its primary function is the power supply for household and industrial equipment, which is critical to the input current waveform (boiler equipment, automation systems with equipment with program control (servers, databases, etc.) with medical equipment).
- The device is equipped with an automatic voltage regulator (AVR). The built-in regulator enables to provide correct power supply at the overvoltage/Undervoltage of the mains without going to the battery operation mode.
- The automatic start function provides automatic switching on when there is a power supply. With input voltages 160 V or less, as well as 260 V or more the automatic start is not activated.
- The three-stage switch of charging current enables the user to connect batteries of different capacities depending on the required time to provide the power backup. It is recommended for the battery with a capacity 20–50 А·h to use the position L (3–5 A) of the switch, with the capacity of 50–100 А·h to use the position M (7–9 A), with the capacity 100–200 А·h to use the position Н (13–15 A).
Recommendations regarding the selection of batteries
- Select the capacity of a battery (batteries) depending on the connected load power and re-quired time of power standby, see the table 1 below. Based on the selected capacity, choose a certain battery (batteries).
- Storage conditions of batteries must conform to the requirements of the battery producer.
Table 1. Selection of batteries
RT-1000
RT-500|
Battery capacity| Load 100 W| Load 200 W| Load
300 W
| Load
400 W
| Load
480 W
| Load
500 W
| Load 600 W
12V/50 А·h| 3 h| 1.5 h| 0.7 h| 0.5 h| 0.4 h| 0.4 h| 0.3 h
12V/75 А·h| 5 h| 2.3 h| 1.5 h| 1 h| 0.8 h| 0.8 h| 0.5 h
12V/100 А·h| 7 h| 3 h| 2 h| 1.5 h| 1 h| 1 h| 0.7 h
12V/150 А·h| 12 h| 5 h| 3 h| 2 h| 1.5 h| 1.5 h| 1 h
12V/200 А·h| 15 h| 7 h| 4.5 h| 3 h| 2.5 h| 2.5 h| 2 h
We recommend using SVEN SV12170, SVEN SV12500, and SVEN SV121000 batteries.
Notes. When two or more batteries are used, they should be of one type
and have the same capacity (if their capacities are different, the batteries
will have different internal resistance and due to this the charge level will
be different). Batteries should be connected in parallel when several
batteries are used simultaneously. Additional cables (to be purchased
separately) will be required to connect extra batteries. When two or more
batteries are connected, the plus terminal of one battery is connected to the
plus terminal of the other battery, minus terminals of batteries are con-
nected similarly. The connecting cables must have a sufficient cross-section
and a minimum length.
Features
- Continuous action with prolonged backup time.
- Built-in automatic voltage regulator.
- Pure Sine Wave.
- Microprocessor control.
- Protection against short circuits in connected load to UPS, as well as against overload.
- Protection against overvoltage or Undervoltage in the mains.
- IP-20 ingress protection.
- Three-stage switch of charging current.
- Self-diagnosis after switching on.
- Indication of operation modes on LCD display.
- Mode switchover time 8 msec.
- Automatic start function.
- Low noise level.
Description
- OUTPUT VOLTAGE: output voltage indicator.
- INPUT VOLTAGE: input current indicator.
- LOADING CAPACITY: device load indicator.
- BATTERY: battery charge level indicator.
- BACKUP: operation mode from battery It lights, when there is no input voltage or its value goes beyond its rate.
- CHECK error indicator.
- UTILITY: mains operation indicator.
- OVERLOAD: overload indicator.
- LCD display.
- Signal: sound signal on/off switch.
- UPS on/off switch.
- Audio alarm: on/off switch of all sound signals.
- Fuse: resettable automatic temperature fuse (presto reset).
- Output ~230 V: socket.
- Input: a built-in power cord.
- 12 V DC: built-in cables to connect the battery.
- Charging current: switch to select charging current for the battery.
CONNECTION AND OPERATION
- Place the set (UPS + batteries) in an appropriate position with proper ventilation (free space around the UPS must be not less than 25 cm).
- Set the three-position switch q on the rear panel of UPS in position, which corresponds to the capacity of a connected battery, according to table 2.
- Connect the battery to the UPS using built-in cables p, observe the polarity.
Fig. 4. The rear panel of RT-1000
ATTENTION! Sparkling is allowed at the touch of power terminals during
battery connection to the UPS. Before the first UPS use, the battery should be
charged without load for not less than 12 hours (full charge time may vary
depending on the capacity and discharge of the connected battery level).
- After that connect the UPS to the grounded single-phase network with the help of a power cable
- The LCD display will be switched on, and the buzzer beeps 4 times. The output voltage indicator will display the figure “230”. You don’t need to turn on the UPS after its connection to the network with the button k, the “autostart” function will start it automatically.
- The battery must be charged. To do this, the UPS is to be in a switched-on position till the battery is charged completely (5 segments of the battery indicator must light).
- Connect devices-consumers to the UPS when it is switched off. To do this, insert plugs of consumers into UPS sockets n.
- Insert the UPS plug into a socket once more, the “autostart” function will start it automatically. LCD display i will turn on, buzzer beeps 4 times shortly. The figure “230” will be displayed on the output voltage indicator a. Then turn on the connected devices using their switch-es (turn on the most powerful device first and the most low-powered should be last turned on the last).
Notes. When the occasion requires disconnecting the UPS enforced, unplug devices-consumers and turn off the UPS in the manner aforesaid. Press and hold the button h within 4 seconds to restart the UPS. The buzzer beeps four times and the output voltage indicator will display the figure “230”. If the UPS is not used for a long time, the battery is to be charged once every three months. We recommend reading the manufacturer’s manual for the proper maintenance of the battery. If the UPS is not used for a long time, unplug it and disconnect the battery set. As this up has the autostart function, a power supply failure will result in the UPS automatic starting.
Cold start function
The UPS can be switched on without connection to the mains using the cold
start function. In order to switch on the UPS, press and hold down the button
k within 4 sec. The buzzer beeps four times, the output voltage indicator
displays the figure “230” and the power will be supplied to devices-consumers.
Note. It is not recommended to use the cold start function when the
connected load is large.
Sound alarm and protection
- At the instant the UPS starts to use power from batteries (when there is a power failure), it beeps 4 times. Then the UPS beeps every 30 seconds when it operates from batteries. This function can be switched off. To do this, press and hold down the button j within 2 sec., the buzzer beeps one time and the signals will be over. When beeps are required, repeat the procedure. You can also to turn off all sound signals by pressing the button l on the rear panel of UPS. Press the button l to turn on all sound signals.
- If the battery capacity is low (while operating from batteries), the UPS beeps every second. When the batteries are fully discharged UPS will frequently beeps for 20 seconds and then turns off automatically. If you turn off the button beeps l, the signal low battery charge will not supply.
- When the battery residual voltage is lower than 10.5 V, the UPS is switched off. When the load is too high (110–120 %), the UPS delivers frequent intermittent warning beeps within 20 sec., then it will turn off the load automatically. When the load is 120 % or more the UPS delivers a single beep and then it is turned off automatically.
- When the UPS protection is activated, load the power supply, and turn on the device again by pressing the front panel button.
Three-stage switch of charging current
It enables the user to connect batteries of different capacities depending on
the required time of providing backup power.
Table 2. The selection of the charging current for a battery depends on its
capacity
Battery capacity | Charging current | Switch position |
---|---|---|
from 20 to 50 А·h | low (3 A ~ 5 A) | L |
from 50 to 100 А·h | middle (7 A ~ 9 A) | M |
from 100 to 200 А·h | high (13 A ~ 15 A) | H |
Storage conditions
- The temperature and humidity conditions on premises, where the device placement is intended, must correspond to the norms indicated in the Technical Specifications table.
- The UPS must be stored with batteries fully charged.
Storage conditions of batteries should comply with the manufacturer’s requirements.
TROUBLESHOOTING
Problem | Cause | Solution |
---|
The UPS is connected
to the mains,
but the indicator does
not light.
| 1. The button k is not pressed.
2. Input fuse has come into action.
3. Unreliably connected cables.
| 1. Press button k.
2. Switch off the load. Press the fuse button. If the UPS operation is normal, check the load power.
3. Check cable connections to batteries.
The UPS beeps and operates
in the off-line mode even with normal voltage in the mains.
| 1. The UPS found depressions or surges in input voltage
and has gone to the standby
mode.
2. Input fuse has come
into action.
3. Poor contact in the UPS
connection circuits to the mains.
| 1. It is normal phenomenon.
The UPS protects
the equipment against voltage
disorders of the mains.
2. Disconnect the load. Press the fuse button. If the UPS operation is normal, check the load capacity.
3. Check the UPS connection reliability to the mains.
The UPS operates
from the mains,
but does not operate in the off-line mode.
| 1. Batteries are discharged greatly.
2. Defective batteries.
3. The UPS is to be repaired.
4. Unreliably connected cables.
| 1. Disconnect all equipment
and charge batteries in full.
2. Replace batteries.
3. Consult with the service
center.
4. Check cable connections to batteries.
The UPS beeps long during operation from the mains.| Overload.| Decrease the connected load
power.
The UPS
does not provide the expected time of operation
in the off-line mode
or it is switched off.
| 1. Batteries are discharged greatly.
2. Defective batteries.
3. Unreliably connected cables.
| 1. Charge batteries in full.
2. Replace batteries.
3. Check the connection reliability of cables to batteries.
If none of the above methods can solve the problem, please seek professional advice at your nearest service center. Never attempt to repair the product yourself.
TECHNICAL SPECIFICATIONS
Models
Parameters
| RT-500| RT-1000
---|---|---
Total power, VА| ≤ 500| ≤ 1000
Active power, W| ≤ 300| ≤ 600
Overload protection acting, % of the rated power| 120
Input voltage, V| ~145–280 ± 5 %
Output voltage, V| ~230 ± 10 %
Frequence, Hz (input/output)| 50/50
Number of phases| 1
Coefficient of efficiency (during operation from batteries), %| 65
Operation mode| continuous, long-lasting
Output voltage
waveform
| Normal conditions and AVR| regular sinusoid
Operation mode from batteries
Protection| AVR operation mode| against high voltage/undervoltage, overload,
short circuit
Operation mode from batteries| against discharge, overload, short circuit
Cooling type| passive/active
Beeps| on/off low battery charge, overload,
error
Switching time, msec| ≤ 8
Battery:
plug-in external (optional)
| Type| non-serviceable leakproof lead-acid batteries
Voltage, V| 12
Charging rate, A| low (3 ~ 5); middle (7 ~ 9); high (13 ~ 15)
Environment temperature in the operating mode, °C| -5 to +40
Humidity, %| 10 ~ 90, without condensation
Noise level, dB| 45
Dimensions, mm| 300 × 270 × 140
Weight, kg| 6.2| 9.9
Notes. Technical specifications given in this table are supplemental information and cannot give occasion to claims. Technical specifications and package contents are subject to change without notice due to the improvement of SVEN production.