NUX HSR-2D-2A Single Phase Solid State Relay
Instruction Manual
HSR-2D-2A Single Phase Solid State Relay
Single-Phase Solid State Relay
HSR-2D/2A
INSTRUCTION MANUAL
Thank you for purchasing Han young Nix products. Please read the instruction manual carefully before using this product, and use the product correctly. Also, please keep this instruction manual where you can view it any time.
Safety information
Please read the safety information carefully before the use, and use the
product correctly.
The alerts declared in the manual are classified into Danger, Warning and
Caution according to their importance
DANGER Indicates an imminently hazardous situation which, if not avoided,
will result in death or serious injury
WARNING Indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury
CAUTION Indicates a potentially hazardous situation which, if not
avoided, may result in minor injury or property damage
DANGER
The input/output terminals are subject to electric shock risk. Never let the
input/output terminals come in contact with your body or conductive
substances.
WARNING
- When used in equipment with a high risk of personal injury or property damage (examples: medical devices, nuclear control, ships, aircrafts, vehicles, railways, combustion devices, safety devices, crime/disaster prevention equipment etc.) install double safety devices and prevent accidents. Failure to do so may result in fire, personnel accident or property damage.
- Please read the safety information carefully before the use, and use the product correctly.
- If there is a possibility that a malfunction or abnormality of this product may lead to a serious accident, install an appropriate protection circuit on the outside and plan to prevent accidents.
- Please supply the rated power voltage, in order to prevent product breakdowns or malfunctions.
- To prevent electric shocks and malfunctions, do not supply power until the wiring is completed.
- Please disassemble the product after turning OFF the power.
- Any use of the product other than those specified by the manufacturer may result in personal injury or property damage.
- Please use this product after installing it to a panel, because there is a risk of electric shock.
CAUTION
- Please make sure that the product specifications are the same as you ordered.
- Please use the product in places where corrosive gases (especially harmful gases, ammonia, etc.) and flammable gases are not generated.
- Please use the product in places without liquids, oils, chemicals, steam, dust, salt, iron, etc. (pollution degree 1 or 2).
- Please avoid places where large inductive interference, static electricity, magnetic noise are generated.
- Please avoid places with heat accumulation caused by direct sunlight, radiant heat, etc.
- When water enters, short circuit or fire may occur, so please inspect the product carefully.
- Do not connect anything to the unused terminals.
- For DC types, please wire correctly, after checking the polarity of the terminals.
- When using the SSR, the product may be damaged if the specified heat sink is not used. Be sure to use the specified heat sink.
- When disposing of the product, treat it as industrial waste.
Suffix code
Model | Code | Content |
---|---|---|
HSR | ||
Control phase | 2 | |
Icnopnutrtol voltage | D | |
A |
Rated load current
| 10| | | | 10 A
20| | | | 20 A
30| | | | 30 A
40| | | | 40 A
50| | | | 50 A
70| | | | 70 A
Rated load voltage| 2| | | 90 – 264 VAC
4| | | 90 – 480 VAC
Operation method (switching mode)| Z| | Zero cross switching
R| | Random switching
Heat sink| –| Without heat sink
-T| With heat sink (only for 50A, 70A)
Specifications
■ DC input type (low voltage)
Classification| HSR-2D102Z| HSR-2D202Z| HSR-2D302Z| HSR-2D402Z| HSR-2D502Z|
HSR-2D702Z
---|---|---|---|---|---|---
HSR-2D102R| HSR-2D202R| HSR-2D302R| HSR-2D402R| HSR-2D502R| HSR-2D702R
Input
| Power voltage Operating| 5 – 24 VDC
voltage range Impedance| 4 – 32 VDC Max. 4 ㏀
Operating voltage| Min. 3 VDC
Reset voltage| Max. 1.5 VDC
Input current| Constant current method: 10 ㎃ (±3)
Rated load voltage| 100 – 240 VAC
Output
| Rated load voltage| 90 – 264 VAC
Load voltage range| 90 – 480 VAC
Peak voltage
(non-repetition)| 800 V| 1200 V| 1200 V| 1200 V| 1200 V| 1200 V
Rated load current| 10 A| 20 A| 30 A| 40A| 50A| 70A
Frequency| 50/60㎐
Surge current| 170A| 250 A| 350 A| 370 A| 580 A| 580 A
Leakage current| Max. 20 ㎃| Max. 20 ㎃| Max. 20 ㎃| Max. 20 ㎃| Max. 20 ㎃| Max.
20 ㎃
ON state voltage drop| 1.3 V| 1.6 V| 1.8 V| 1.8 V| 1.8 V| 1.8 V
Min. operating current| 1 A| 1 A| 1 A| 1 A| 0.5 A| 0.5 A
Response
speed| Zero cross switching| 1/2 cycle +1 ㎳ max.
Random switching| Max. 1 ms
Insulation resistance| 500 VDC, 100 ㏁ (input/output and among cases)
Dielectric strength| 2500 VAC (60 ㎐ for one minute)
Vibration resistance| 10 – 55 ㎐, double amplitude: 1.5 ㎜, Each X· Y· Z axis
for 2 hours
Shock resistance| 1000 ㎨ (about 100 G), Each X· Y· Z axis for 3 times
Storage temperature| -30 ~ 90 ℃
Ambient temperature & humidity| -20 ~ 80 ℃, 45 ~ 85 % R.H.
Approval| |
Weight (g)| 150
※ Weight when packed
DC input type (high voltage)
Classification| HSR-2D104R| HSR-2D204R| HSR-2D304R| HSR-2D404R| HSR-2D504R|
HSR-2D704R
---|---|---|---|---|---|---
HSR-2D104R| HSR-2D204R| HSR-2D304R| HSR-2D404R| HSR-2D504R| HSR-2D704R
Input
| Power voltage
Operating| 5 – 24 VDC
voltage range| 4 – 32 VDC
Impedance| Max. 4 ㏀
Operating voltage| Min. 3 VDC
Reset voltage| Max. 1.4 VDC
Input current| Constant current method: 10 ㎃ (±3)
Output
| Rated load voltage| 100 – 440 VAC
Load voltage range
Peak vole age| 90 – 480 VAC
(non-repetition)| 800 V| 1200 V| 1200 V| 1200 V| 1200 V| 1200 V
Rated load current| 10 A| 20 A| 30 A| 40 A| 50 A| 70 A
Frequency| 50/60 ㎐
Surge current| 170 A| 250 A| 350 A| 370 A| 580 A| 580 A
Leakage current| Max. 20 ㎃| Max. 20 ㎃| Max. 20 ㎃| Max. 20 ㎃| Max. 20 ㎃| Max.
20 ㎃
ON state voltage drop| 1.3 V| 1.6 V| 1.8 V| 1.8 V| 1.8 V| 1.8 V
Min. operating current| 1 A| 1 A| 1 A| 1 A| 0.5 A| 0.5 A
Ressppeoendse| Zero cross switching| 1/2 cycle + 1 ㎳ max.
Random switching| Max. 1 ms
Insulation resistance| 500 VDC, 100 ㏁ (input/output and among cases)
Dielectric strength| 2500 VAC (60 ㎐ for one minute)
Vibration resistance| 10 – 55 ㎐, double amplitude: 1.5 ㎜, Each X· Y· Z axis
for 2 hours
Shock resistance| 1000 ㎨ (about 100 G), Each X· Y· Z axis for 3 times
Storage temperature| -30 ~ 90 ℃
Ambient temperature & humidity| -20 ~ 80 ℃, 45 ~ 85 % R.H.
Approval| | –
Weight (g)| 150
※ Weight when packed
■ AC input type (low voltage)
Classification| HSR-2A102Z| HSR-2A202R| HSR-2A302R| HSR-2A402R| HSR-2A502R|
HSR-2A702R
---|---|---|---|---|---|---
HSR-2A102R| HSR-2A202R| HSR-2A302R| HSR-2A402R| HSR-2A502R| HSR-2A702R
Input
| Power voltage Operating| 100 – 240 VAC
voltage range| 90 – 264 VAC
Impedance| Max. 40 ㏀
Operating voltage| Min. 72 VAC| Min. 72 VAC| Min. 72 VAC| Min. 72 VAC| Min. 75
VAC| Min. 75 VAC
Reset voltage| Max. 40 VAC
Input current| 240 VAC / 9 ㎃(±4)
Output
| Rated load voltage| 100 – 240 VAC
Load voltage range| 90 – 264 VAC
Peak voltage
(non-repetition)| 600 V| 600 V| 600 V| 600 V| 800 V| 800 V
Rated load current| 10 A| 20 A| 30 A| 40 A| 50 A| 70 A
Frequency| 50/60 ㎐
Surge current| 170 A| 250 A| 350 A| 370 A| 580 A| 580 A
Leakage current| 15 ㎃| 15 ㎃| 15 ㎃| 15 ㎃| Max. 20 ㎃| Max. 20 ㎃
ON state voltage drop| 1.3 V| 1.6 V| 1.8 V| 1.8 V| 1.8 V| 1.8 V
Min. operating current| 1 A| 1 A| 1 A| 1 A| 0.5 A| 0.5 A
Response
speed| Zero cross switching| 1/2 cycle +1 ㎳ max.
Random switching| Max. 1 ms
Insulation resistance| 500 VDC, 100 ㏁ (input/output and among cases)
Dielectric strength| 2500 VAC (60 ㎐ for one minute)
Vibration resistance| 10 – 55 ㎐, double amplitude: 1.5 ㎜, Each X· Y· Z axis
for 2 hours
Stock resistance e
orange temperature
| 1000 ㎨ (about 100 G), Each X· Y· Z axis for 3 times
-30 ~ 90 ℃
Ambient temperature & humidity| -20 ~ 80 ℃, 45 ~ 85 % R.H.
|
Approval| | –
Weight (g)| 150
■ AC input type (high voltage)
Classification| HSR-2A104Z| HSR-2A204Z| HSR-2A304Z| HSR-2A404Z| HSR-2A504Z|
HSR-2A704Z
---|---|---|---|---|---|---
HSR-2A104R| HSR-2A204R| HSR-2A304R| HSR-2A404R| HSR-2A504R| HSR-2A704R
Input
| Power voltage| 100 – 240 VAC
Operating voltage range| 90 – 264 VAC
Impedance| Max. 4 ㏀
Operating voltage| Min. 80 VAC| Min. 80 VAC| Min. 80 VAC| Min. 80 VAC| Min. 75
VAC| Min. 75 VAC
Reset voltage| Max. 40 VAC
Input current| 240 VAC / 9 ㎃(±4)
Output
| Rated load voltage| 100 – 440 VAC
Load voltage range| 90 – 480 VAC
Peak voltage
(non-repetition)| 800 V| 1200 V| 1200 V| 1200 V| 1200 V| 1200 V
Rated load current| 10 A| 20 A| 30 A| 40 A| 50 A| 70 A
Frequency
Surge current| 170 A 250 A 350 A 50/60 ㎐ 370 A
580 A 580 A
| | | | | |
Leakage current| Max. 20 ㎃| Max. 20 ㎃| Max. 20 ㎃| Max. 20 ㎃| Max. 20 ㎃| Max.
20 ㎃
ON state voltage drop| 1.3 V| 1.6 V| 1.8 V| 1.8 V| 1.8 V| 1.8 V
Min. operating current| 1 A| 1 A| 1 A| 1 A| 0.5 A| 0.5 A
Ressppeoendse| Zero cross switching| 1/2 cycle + 1 ㎳ max.
Random switching| Max. 1 ms
Insulation resistance| 500 VDC, 100 ㏁ (input/output and among cases)
Dielectric strength| 2500 VAC (60 ㎐ for one minute)
Vibration resistance| 10 – 55 ㎐, double amplitude: 1.5 ㎜, Each X· Y· Z axis
for 2 hours
Shock resistance| 1000 ㎨ (about 100 G), Each X· Y· Z axis for 3 times
Storage temperature| -30 ~ 90 ℃
Ambient temperature & humidity| -20 ~ 80 ℃, 45 ~ 85 % R.H.
Approval| |
Weight (g)| 150
Dimensions
HEAT SINK
■ Model name: HSP series
Model | Applicable Model | Capacity(A) | Weight |
---|---|---|---|
HSP-10 | HSR-2E110EID | 10 A | 208 g |
Model | Applicable Model | Capacity(A) | A | B | C | Weight |
---|---|---|---|---|---|---|
HSP-20 | HSR-2120❑❑ | 20 A | 85.0 | 60. | 85.0 | 404 g |
HSP-40 | HSR-20300❑ | 30 A | 114.0 | 60. | 114.0 | 570 g |
HSR-2❑40❑40 | A |
Model name: HSM series
Model | Applicable Model | Capacity(A) | A | BCD | E | Weight | ||
---|---|---|---|---|---|---|---|---|
HSM-70 | HSR-2010❑❑ | 10 A | 70.0 | 35.0 | 49. | – | – | 364 g |
I-ISM 110 | HSR-2 M 20E10 | 20A | 110.0 | 55.0 | 49. | – | – | 568g |
HSR-2❑30❑❑ | 30 A | |||||||
HSM-150 | HSR-274000 | 40A | 150.0 | 75.0 | 49. | 97.0 | 32.0 | 768g |
Model name: HSN80-F series
■ Model name: HSN120-F series
Model | Applicable Model | Capacity(A) | Weight |
---|---|---|---|
HSN80-F | HSR-2050❑❑ | 50A | 1,474g |
HSN120-F | HSR-2770❑❑ | 70A | 2,052g |
The above contents are subject to change without prior notice for performance improvement.
Application circuits
AC input type (10 A ~ 40 A) Equivalent circuits
Load Current Characteristics
■ Input Voltage / Current Characteristics
■ Load Current Characteristics
■ Surge Current Characteristics
■ Precautions while using the heat sinks
- Using standard heat sink and heat-dissipation grease is mandatory for this product.
- Even the standard heat sink is used, HSR damage may occur if the environment temperature rises or if the ventilation does not work well (environment temperature : over 40 °C)
- The normal HSR element is damaged at the maximum temperature of 125 °C or more. When the temperature of heat sink is 85 ° C or higher, or more, the temperature of the element reaches around 125 °C. Therefore, during operation, measure the temperature of heat sink.
- When you connect HSR to the heat sink, heat-transmitting grease is needed for smooth heat transmission.
- To prevent separation by vibration, tighten up with bolts.
- Before installation, be sure to apply heat-dissipation grease to the contact surface i using the standard heat sink, as shown in the above picture. Do not use on insulation boards (wood, plastic, rubber)
For further information, please visit our homepage (www.hanyoungnux.com) and refer to the user’s manual in the archive.
HANYOUNGNUX CO.,LTD
28, Gilpa-ro 71beon-gil, Michuhol-gu,
Incheon, Korea TEL : +82-32-876-4697
http://www.hanyoungnux.com
MC1001KE220701
Documents / Resources
|
HANYOUNG NUX HSR-2D-2A Single Phase Solid State
Relay
[pdf] Instruction Manual
HSR-2D-2A, HSR-2D-2A Single Phase Solid State Relay, Single Phase Solid State
Relay, Phase Solid State Relay, Solid State Relay, State Relay, Relay
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>