HANYOUNG nux VX Series LCD Digital Temperature Controller Instruction Manual

June 12, 2024
HANYOUNG NUX

VX Series LCD Digital Temperature Controller

Product Information: LCD Digital Temperature Controller VX

series

The LCD Digital Temperature Controller VX series is a product
manufactured by Hanyoung Nux. It is designed to accurately control
and monitor temperature in various applications. The temperature
controller features an LCD display for easy reading and
programming.

The product is manufactured by HANYOUNGNUX CO.,LTD, located at
28 Gilpa-ro 71beon-gil, Michuhol-gu, Incheon, Korea. For any
inquiries or support, you can contact them at TEL: +82-32-876-4697
or visit their website at http://www.hanyoungnux.com.

Product Usage Instructions:

Before using the LCD Digital Temperature Controller VX series,
please read the instruction manual carefully and follow the safety
guidelines provided.

Safety Information:

The safety information provided in the manual is classified into
three categories: Danger, Warning, and Caution. It is important to
understand and adhere to these warnings to avoid any accidents or
injuries.

Usage Guidelines:

  • Install double safety devices in applications where high-risk
    equipment is involved, such as ships, aircraft, vehicles, railways,
    combustion devices, safety devices, crime/disaster prevention
    equipment, etc., to prevent accidents.

  • When using electromagnetic switches, set the proportional cycle
    to at least 20 seconds. When using SSR (Solid State Relay), set the
    proportional cycle to at least 1 second.

  • Ensure the temperature controller is used within the specified
    ambient temperature and humidity ranges mentioned in the
    instruction manual.

  • Avoid using the temperature controller in locations with
    corrosive gases, vibrations, impacts, liquids, oils, chemicals,
    steam, dust, salt, iron, etc. (pollution degree 1 or 2).

  • Do not place the temperature controller in areas with large
    inductive interference, static electricity, magnetic noise, or
    radiant heat.

  • Use circuit breakers compliant with IEC60947-1 or
    IEC60947-3.

  • Ensure the power input and relay output wires have a minimum of
    75% heat resistance and use copper wires from 18 AWG to 24
    AWG.

  • Tighten the terminal screws with a torque of 0.5 to 0.7
    N.m.

  • If the temperature controller is used as a signal to an
    external interlock circuit, use a delay relay together.

  • Clean the product with neutral detergents and avoid using
    alcohol or benzene.

  • Ensure compatibility when using multiple temperature
    controllers of the same model, as different set parameters may
    result in different operation.

  • Use dedicated temperature compensation cable to minimize
    temperature deviation between the temperature controller’s PV value
    and the actual temperature. Calibrate the temperature deviation if
    necessary.

Following these usage instructions will help ensure optimal
performance and longevity of the LCD Digital Temperature Controller
VX series.

LCD Digital Temperature Controller
VX series
INSTRUCTION MANUAL
Thank you for purchasing Hanyoung Nux products. Please read the instruction manual carefully before using this product, and use the product correctly. Also, please keep this instruction manual where you can view it any time.

HANYOUNGNUX CO.,LTD 28, Gilpa-ro 71beon-gil, Michuhol-gu, Incheon, Korea TEL : +82-32-876-4697 http://www.hanyoungnux.com
MA0631KE230509

Safety information
Please read the safety information carefully before the use, and use the product correctly. The alerts declared in the manual are classified into Danger, Warning and Caution according to their importance
DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor injury or property damage

DANGER
· The input/output terminals are subject to electric shock risk. Never let the input/output terminals come in contact with your body or conductive substances.

WARNING
· If there is a possibility of a serious accident due to malfunction or abnormality of this product, install an appropriate protection circuit on the outside. · Since this product is not equipped with a power switch and fuse, install them separately on the outside (fuse rating: 250 V a.c., 0.5 A). · Please supply the rated power voltage, in order to prevent product breakdowns or malfunctions. (Overvoltage category II) · The power supply should be insulated and limited voltage/current or Class 2, SELV power supply device. · To prevent electric shocks and malfunctions, do not supply power until the wiring is completed. · The product does not have an explosion-proof structure, so avoid using it in places with flammable or explosive gases. · Never disassemble, modify, process, improve or repair this product, as it may cause abnormal operations, electric shocks or fires. · Please disassemble the product after turning OFF the power. Failure to do so may result in electric shocks, product abnormal
operations or malfunctions. · Any use of the product other than those specified by the manufacturer may result in personal injury or property damage. · Please use this product after installing it to a panel, because there is a risk of electric shock. · When used in equipment with a high risk of personal injury or property damage (examples: medical devices, nuclear control,
ships, aircrafts, vehicles, railways, combustion devices, safety devices, crime/disaster prevention equipment etc.) install double safety devices and prevent accidents. Failure to do so may result in fire, personnel accident or property damage.

CAUTION

· The contents of this manual may be changed without prior notification. · When replacing the sensor, be sure to turn off the power.

· Please make sure that the product specifications are the same as you ordered. · Use an extra relay when the frequency of operation

· Please make sure that there are no damages or product

(such as proportional operation, etc.) is high, because connecting

abnormalities occurred during shipment.

the load to the output relay rating without any room shortens the

· Use this product in the following environments:

service life. In this case, SSR drive output type is recommended.

– indoors.

  • When using electromagnetic switch: set the proportional cycle to at least 20 sec.

– use it in the ambient temperature and humidity ranges indicated * When using SSR: set the proportional cycle to at least 1 sec.

in the instruction manual.

· Do not wire anything to unused terminals.

– use it in locations where corrosive gases (especially harmful

· Please wire correctly, after checking the polarity of the terminals.

gases, ammonia, etc.) and flammable gases are not generated. · When you install this product to a panel, please use switches or

– use it in places where vibrations and impacts are not directly

circuit breakers compliant with IEC60947-1 or IEC60947-3.

applied to product body.

· Please install switches or circuit breakers at close distance for

– use it in places without liquids, oils, chemicals, steam, dust, salt, user convenience.

iron, etc. (pollution degree 1 or 2).

· Please specify on the panel that, since switches or circuit breakers

– avoid places where large inductive interference, static electricity, are installed, if the switches or circuit breakers are activated,

magnetic noise are generated.

the power will be cut off.

– avoid places with heat accumulation caused by direct sunlight, · We recommend regular maintenance for the continuous safe use of this product.

radiant heat, etc.

· Some components of this product may have a lifespan or deteriorate over time.

– use it in places with elevation below 2000 m.

· The warranty period of this product, is 1 year, including its

– Power input and relay output wires are at least 75 of heat accessories, under normal conditions of use.

resistance and, use copper wires from 18 AWG to 24 AWG.

· The preparation period of the contact output is required during

– Tighten the screw on the terminal is torque from 0.5 to 0.7 N . m power supply. If used as a signal to external interlock circuit, etc.

· Please do not wipe the product with organic solvents such as

please use a delay relay together.

alcohol, benzene, etc. (wipe it with neutral detergents).

· If the user changes the product in case of malfunctions, the

· When water enters, short circuit or fire may occur, so please

operation may be different due to set parameters differences even

inspect the product carefully.

if the model name is the same. So, please check the compatibility.

· For thermocouple input, use the predetermined compensating · Before using the temperature controller, there may be a

cable (temperature errors occur when using ordinary cable).

temperature deviation between the PV value of the temperature

· For RTD input, use a cable with small lead wire resistance and

controller and the actual temperature, so please use the product

without resistance difference among 3 wires (temperature errors after calibrating the temperature deviation.

occur if the resistance value among 3 wires is different).

· The write life of non-volatile memory (EEPROM) is one million

· Use the input signal line away from power line and load line to

times. When configuring the system, please make sure that

avoid the influence of inductive noise.

the number of times that data are written to non-volatile memory

· Input signal line and output signal line should be separated from each does not exceed one million times.

other. If separation is not possible, use shield wires for input signal line. · If you connect the USB loader to another device using a USB cable, additional

· Use a non-grounded sensor for thermocouple (using a grounded input errors may occur depending on the target device to which the cable is

sensor may cause malfunctions to the device due to short circuits). connected. (it is recommended not to use it for control/monitoring)

· When there is a lot of noise from the power, we recommend to

use insulation transformer and noise filter. Please install the noise filter

to a grounded panel or structure, etc. and make the wiring of

noise filter output and product power supply terminal as short as possible.

· Tightly twisting the power cables is effective against noise.

· If the alarm function is not set correctly, it will not be output in

case of abnormal operation, so please check it before operation.

Suffix code

Model

Code

VX

– –

2

3

Size

4

7

9

Sensor

U

M

OUT 1 (control output 1)

S

C

OUT 2

N

(control output 2)

M

Power

A

D

A1

Sub output

A2

A4

Communication

C

Retransmission output (RET)

T

Digital input (DI)

D2

Current detection input (CT)

H1

Remote input (REM)

R

Content LCD Digital Temperature Controller 48(W) × 96(H) × 62.5(D) mm 96(W) × 48(H) × 62.5(D) mm 48(W) × 48(H) × 63(D) mm 72(W) × 72(H) × 62.5(D) mm 96(W) × 96(H) × 62.5(D) mm Universal input Relay output Voltage pulse output (voltage pulse output for SSR drive) Current output (4-20 mA current output for SCR drive) None Relay output 100 – 240 V a.c. 50/60 Hz 24 V d.c., Class2 1 relay output (VX4 basic option) 2 relay outputs (VX2, VX7, VX9 basic option) 4 relay outputs ( *1) RS-485 communication Retransmission output (4 ~ 20 mA) 2 digital inputs (DI 1 ~ 2) Current detection input (CT) 1 contact 1 input, 4 ~ 20 mA (1 ~ 5 V)

    1. You can select from VX2, VX3, VX7, VX9 (VX4 is excluded) Please refer to our user’s manual, catalog or homepage for the model names of VX available for order.

Basic key description 1: Please refer to the description of the right menu key to move between operation and menu mode. 2: Move to group name or n.PID. Please refer to the parameter configuration below.

No. Key Control/Monitoring

Operation mode *1

Menu mode *1

SV change

Control output Manual control output Simple / Basic / Full Change parameters

Mode

Move to control output mode

Move to control/ Move to control/ monitoring mode monitoring mode

*2

Set

Move to SV change mode

Save SV value

Change Parameter / Move to next parameter Move within group after saving value

Shift Down
Up

Shift digit position

Shift digit position

Shift digit position

Decrease value Increase value

Decrease value Increase value

Move among parameters / Move group

Decrease/change value
Increase/change value

Specifications

Input

Classification
Thermocouple Reference junction compensation accuracy
RTD
Allowable line resistance
DC voltage / current
Sampling cycle

Relay output (OVC II, Resistive load)

Control output
Control Memory

AC voltage type voltage pulse output
DC voltage type voltage pulse output Current output
Control type
Output operation
Non-volatile memory life

VVXX22-A-ALLLL

VCXo2n-AnLeLcVtXiV4oX-nA4Ld-ALiaLgLrams

VX4-AVXL7L-AVLXL7-ALL

VX2

VX3

VX4

VX7

K, J, E, T, R, B, S, L, N, U, W, PLII

VX9

VX4

VX7

VXV7XV-9AX-A2LLL-ALLVLX9-ALL VX9V-AXL4L-ALL When using the input as DC current, it is recommended to connect 250 (0.1% or less high precision) resistor in parallel to the outside of the terminal The 250 (1%) resistor included with the product is not a precision resistor.

VX2, VX3

VX9

±1.5 (within -10~50 )

Input type parameters (INP), input sensor types and ranges E···(EVRMMPXRaae3Otcx)eME.hRdsaaauwsnctnweihilctodicatc3hclks4hiewlw1nidif~2nigei:tEr1gcw21VveE:h02hocP~d2weaRlcmt.50npaOcait1pa.sMmAgVhe5ca±etiil(±ictolntOO4VSSCSSC:iliyOcnit12UUUUUUoOOk~1ygd0:4NenBBBBTTV:0.E5.MM20dc23/123412OO2SSCSSCt:0d.OAV%iPUUUUUUAmOOp.wR.mc111F2BBBBaLTT561384927u(2MMeh.012eF:o4b121234.Ae4lcpvsO,0sfun.)0euFM,(111eP,FVt561384927asFr0121Vl0ISeastsSvtD1aitneheanoe1~t0.MJ±ic.eu8ceGnlSSRRcPavRRRR5.aVtS0og,a..SCaoLLcTSrnLLLLe15Vd,nleEYYtCERgYYYYR1lueSSRRRRRR53ti,2.tTsdAPe0a/oc/aSCLLPr0LLLL0iAl.0MgiYYosnRgYYYYR.3(gLr,mt~l/le0/,)o3:ioa,23333P2232323tuO0d1snVa,(9456057283261TpNl0iVdclD233332232323or1do(945605728361eeiEV0aOd.nraccE,0de.a.dFGPct0sm..Rr·aSiPr~,OesE·eMcoItmRDCDDCDsMTDMts5anaiOOiERDCDDCDis0gaIIIInolaxsgicTOOtErxMMf1234.txIIIIcnoameoTia3MM3412.seum:nnwnsV1pABlcmwutABic,im (((rnetm-se+((0ioci- tt+ie)):nlmohcll))~ssirmh.ioenw122211121211i1122211i21211sn6n72348n3506149gia723483506149hi0n0tt.gxTi0ccoT0mR6.CChupuAm0e6iArAoMlnsr0BBBB0dwV)eg)w”0neRbRrcOORSSCSSCtrSiRR)uSetREUUUUUU:e4:OOTCCCEmr4TCCCmM58s7BBBBVrTTDOgMTT8VMMeDOA5aTT5u123412AAM512n0maM12tr111a:V56e1384927012n3A)t,eA9Med0aS)Wne/ ueSSRRRRRRaSCLLLLLLlYYRYYYYR//OOSUUUBOOSTT2333322323233U21UU945605728361BTT612345321M123456aSRSSRneMSLCLueYYRRaaSRSSRRDCDDCD//lneSLCLOOEueRABIIIIYYRRRRT(aSMM(3412+E/-E/l4))MT8RABBRR5(S(((111111+E-E-+4345678))MT))85122211121211111111723483506149345678DCDDCDOOTIIIICMM3412ABBDCDDCD’OOIIIIRMMR3412SRECCC4TCCCmMO8VTTDORRTTAM512LLM12YY111789CCC201TOCTTRRSSCMUU12BABOLLYY’BBM12mR111789VT201ATDCSSCUUBABO’BBM12mRVTOOSADUUUBTT312

12OUTSSR1SCLYRR12// 3
3OUT2 RLY4
4 SUB1 5
5SUB2 6
6COSMee 7 Manual 8
9

A(+) S1C13R/ RBOS(U-4)T815SR1SL24YR/

CCCOTTDCM12OI MSSR1SCLYRR//

ORUETM2 R13L5Y 146

DI2 RLY
DI3

SUB1R1L57Y SRUEBT2RL6Y
18
COM 7

CROEMTRLY DI4
RLRYLY

See 8 Manual
9

RLY See Manual

19 C T 1RLY CO2M0

7 DSIU1B11A9(+) 8 CSOUMB22B0(-)

10 D I 1 11 COM

C

T212RLY

9

DI2 COM21

12 D I 2

22

D 10

IB3’22

13 DI3

CCC2222R3465OTTREM12LSSTYUU11BB2134TCDCOIBAM4222mR345VTADSU1111B45763TCDCOIBBM4′

27 COM RLY

26 SU1B84 A

27 COM

A(+) 10 RS48O5UT1 B(-) 11

1 2

ROSUO4T8U15SSRTSCL112YRR//12CCOTM1SSRSCLOYRRSSRU//SCLTYRR133//78

11295 22206

DCOISSRM1SCLDCYRRODCABI//OM((1I-+M1))AB33((117AB8-+34(())-+))11011134RDCSO4I8M15RSABR4((S8-+45))851134

12 OUT2 REM 13

3 4

3 OUOTU2TR24LY RSEUSMBU1B15

C 3 4 5

T

2

39

RLOYRULTY240

41 RLSYUB1

32217 42228 5 29

D I 2DDI 2I 2 3195

D IR3LY COMDDI

I3 3

16 40 17

COM41

1215 D I 2

15

1316 17

D CI 3T1 COCCMOTRM2EM

16 CT1 CO1M7

SU14B1 5 SUB2 6

RLY42 23 D IR4CLYOM 18 14

CT2

SUBR2LY 6 RRELTSYUB2 6 30

D I 4 42 18 D I 4

18

SU15B2 mA VC1O6M RTD TC
17
18

6 7B’
8B A9

COM 7 SUCBO3RML8Y SUmSBVU4AB39 CROSTMUDB140
See MaCnOuaM1l1
12

RLY43 24

7 8 9 10

RRRRLLLLCSSCYYYYUURROOBBLLMMYY34444467451897022233337654231

See

1M1 anual 481135

See

RERTDLYI 4 SUB3 RET SUBR4LY C O MRLY
See

19 4230 4241 4252
4263
4274

15

TC111876BB2221T’2019CRRTRACEEBBTmMTV’DBA’RmTRVDEAmMVA22212019

A23

B

23 RTD

12 Manual 1236Manual 48 24 A

24

ROSU4T815

1 OUT1 2

12SSRSCLYRRSSR//SCLYRR//33RAB78(S(+-4))851134DCOI M1DCOABIM1((-+))

3

OUT2 CT1

4OSUUBT32

SUCBO1M 5

3RLYRLY 4

39 40REM 41

DI2 15 D I 2
DI3 16COMD I 3

CT2 SUB2 6 COM 7

5 RLY 42

17D I 4COM

RLY

RET

6 See 43 18

DI4

Manual

RET

SUB3 8

44

REM

RLY

SUB4 9

45

TC

B’ B

COmMA V
RTD

10 11

A

12

RLY See Manual

46 47 48

13

7 SUB1

RLYRS485

14

8 SUB2

15 RLY 9 COM

16

10 CTB’1

17 18

CT1 COM CT2

11TCCCOTBM2mVA RTD

19

12 A

20
REM 21

22 B’ TC
23 B
24 A

mA V RTD

Display part
(HW) mm
USB Loader

Display method PV character SV character MV character
Communication method
Protocol
Communication distance Sub output

Digital input

Option Power

Retransmission output

Remote input

Current detection input

Communic. method

Max. connections

Communic.sequence

RS-485

Communic.distance Communic. speed

bit

Protocol

Response time

AC Power Supply Voltage

DC Power Supply Voltage

Voltage fluctuation rate

Insulation resistance

Dielectric strength
AC voltage type power consumption
DC voltage type power consumption
Ambient temperature & humidity
Storage temperature

Wide viewing angle LCD

20.5 x 6.9

19.7 x 7.2

15.2 x 6.8

19.8 x 9.3

29.0 x 13.6

12.8 x 5.9

10.7 x 4.7

7.4 x 3.9

10.2 x 4.9

15.0 x 7.2

9.3 x 4.4

7.3 x 3.5

7.4 x 3.9

7.5 x 3.3

11.0 x 4.8

USB 2.0

· Protocol : PC-LINK · Data bit : 8 bit

· Baudrate : 38400 bps · Parity bit : None

· Start bit : 1 bit · Stop bit : 1 bit

Within 5 m

Relay 1 ~ 4 outputs, rated switching capacity: 5A 240 V a.c., 5 A 30 V d.c. 2 points or 4 point
Contact input ON : 1 K max., OFF: 100 K min., Non-contact input ON : 1.5 V max., OFF: 0.1 mA max. Current Flow : approx. 2 mA per contact, Voltage at open : Approx. 5 V d.c.
1 output, 4 ~ 20 mA ± 0.2% of FS ± 1 digit, load resistance: max. 600

1 input, 4 ~ 20 mA (1 ~ 5 V)

1 input or 2 inputs, 0.0 – 50.0 A, CT-70 current transformer (sold separately)

EIA RS485 standard, 2-wire half-duplex

31 (address setting 1~99 available)

No sequence

Within 1.2

4800, 9600, 14400, 19200, 38400, 57600 BPS

Start bit : 1 bit, Data bit : 7 or 8 bit, Parity bit : NONE / EVEN / ODD, Stop bit : 1 or 2 bit

PC-LINK STD, PC-LINK WITH SUM, MODBUS-ASCII, MODBUS-RTU

Actual response time = processing time + (response time X 50 )

100 – 240 V a.c., 50/60 Hz

24 V d.c., Class2

±10 % of power voltage

Min. 20 , 500 V d.c.

3,000 V a.c., 50/60 Hz for 1 minute (between 1st and 2nd terminal)

Max. 8.5 VA

Max. 8.5 VA

Max. 8.2 VA

Max. 8.5 VA

Max. 9.0 VA

Max. 2.7 W

Max. 2.7 W

Max. 2 W

Max. 2.8 W

Max. 3.2 W

-10 ~ 50 , 35 ~ 85 % RH (without condensation) -25 ~ 65

Approval
Weight (g) Basic components

· Electrostatic discharge (ESD) : KN61000-4-2 · EFT(RS) : KN61000-4-3

· Conductive RF (CS) : KN61000-4-6

· SURGE : KN61000-4-5

IP65 (front panel) IP65 (front panel) IP66 (front panel) IP65 (front panel) IP65 (front panel)

202

202

120

194

290

Main body, Bracket, 250 resistor (1%) , Rubber packing, Instruction manual

Thermocouple and RTD

Classifi cation Type
K
J E T R

Parameter set value

Screen display Communication

K0

1

K1

2

J0

3

J1

4

E1

5

T1

6

R0

7

Temperature range

-200 ~ 1370 -100.0 ~ 500.0
-200 ~ 1200

-328 ~ 2498 -148 ~ 932 -328 ~ 2192

-199.9 ~ 900.0 -199.9 ~ 900.0 -199.9 ~ 400.0

-328 ~ 1652 -328 ~ 1652 -328 ~ 752

0 ~ 1700

32 ~ 3092

Thermo couple

B

B0

8

100 ~ 1800 212 ~ 3272

S L N U W PLII
JPt100 RTD
Pt100

S0 L1
N0 U1 W0 PL0 JPt0 JPt1 Pt0 Pt1

9

0 ~ 1700

32 ~ 3092

10

-199.9 ~ 900.0 -328 ~ 1652

11

-200 ~ 1300 -328 ~ 2372

12

-199.9 ~ 400.0 -328 ~ 752

13

0 ~ 2300

32 ~ 4172

14

0 ~ 1300

32 ~ 2372

20

-200 ~ 500

-328 ~ 932

21

-199.9 ~ 500.0 -328 ~ 932

22

-200 ~ 640

-328 ~ 1184

23

-199.9 ~ 640.0 -328 ~ 1184

Tolerance
±0.2 % of FS ± 1 digit ±0.2 % of FS ± 1 digit
100~200 : ±2.0 % of FS ± 1 digit ±0.2 % of FS ± 1 digit
±0.2 % of FS ± 1 digit

Direct current and voltage

Classifi cation

Type

Parameter set value Screen display Communication

Range

Tolerance

Direct current 4 ~ 20 mA ()

1-5 V

30

(Current Input) 0 ~ 20 mA ()

5 V

31

1 ~ 5 V

1-5 V

30

0 ~ 5 V

5 V

31

Direct voltage (V d.c. / d.c.)

0 ~ 10 V

10 V

32

0 ~ 50 mV

0.05 V

33

-1999 ~ 9999

±0.2 % of FS ± 1 digit

0 ~ 100 mV

0.1 V

34

When direct current is used, it is recommended to connect 250 (0.1% or less, high precision) resistor in parallel to the outside of the terminal. Please note that the 250 (1%) resistor included with the product is not a precision resistor.

Remote input

Part names and functions

Operation indicator
RUN: RUN or STOP status (Turns on during control)
OUT1: Control output 1 status (Control output 1 blinks proportionally to 0 ~ 100%)
OUT2: Control output 2 status (Control output 2 blinks proportionally to 0 ~ 100%)
SUB1: Sub output 1 status (Turns on when sub output 1 is ON)
SUB2: Sub output 2 status (Turns on when sub output 2 is ON)
SUB3: Sub output 3 status (Turns on when sub output 3 is ON)
SUB4:Sub output 4 status (Turns on when sub output 4 is ON)
COM: Communication status (Turns on for 0.5 sec. during communication)
REM: Remote input activation (Turns on when remote input is set)
MANU: Manual output status (Turns on when manual output is set)

TUNING (Blinks during Auto-Tuning (AT))
UNIT (Displays , , %, no unit depending on unit set value)

PRESENT VALUE

T

(Displays PV value in operating mode,

displays parameter name in menu mode)

SET VALUE OR OUTPUT VALUE (Displays SV or control output value in operating mode, displays parameter set value in menu mode)

MODE

RUN/STOP SET SHIFT DOWN UP
OUTPUT VALUE (Control output value in operating mode)

Input Direct current Direct voltage

Type 4 ~ 20 mA ()
1 ~ 5 V d.c.

Range Same as input setting range

Tolerance ±0.2 % of FS ± 1 digit

When direct current is used, it is recommended to connect 250 (0.1% or less, high precision) resistor in parallel to the outside of the terminal. Please note that the 250 (1%) resistor included with the product is not a precision resistor.

Dimensions and panel cutout

Dimensions WW

LL D1 D1 D D

T T

HH

HH

Current transformer (CT-70, sold separately)
Available with HBA option (current ratio: 1000 : 1, current detection range: 0.0 – 50.0 A)
Make sure the CTs used are UL Listed or Recognized component (Reinforced insulation) in USA/Canada

U

Terminals use the following geometries. Wires must be connected using UL listed lugs.

[Unit: mm]

3.2

5.5

Ring terminal

3.2

5.8

USB Loader Cable (NMC-UM210, sold separately)
USB2.0 Mini 5PIN Cable

U-shaped terminal

Protective cover ( sold separately)

VX2, VX3 TC2A-COV

VX4 TC4A-COV

VX7 TC7A-COV

VX9 TC9A-COV

Alarm type (An.TY) and alarm operation description

Grey part: An.DB, : SV set value, : AL-n set value, the number indicated in parenthesis () has standby sequence n indicates alarm numbers 1 ~ 4

Alarm type set value

0

Alarm off

Alarm type

Alarm operation –

Absolute alarm Deviation alarm

1

High absolute

(7) High absolute with standby sequence

PV

Alarm section

O

PV

2

Low absolute

Alarm section

O

(8) Low absolute with standby sequence

3

High deviatioWn 1 W1

PV

Alarm section

O

(9) High deviation with standby sequence

PV

4

Low deviation

Alarm section

O

H1 H1 (10) Low deviation with standby sequence

5

High-Low deviation

PV

PV

Alarm

Alarm

O

(11) High-Low deviation with standby sequence

section

section

6

High-Low range

B PV

B

Alarm section

O

(12) High-Low range with standby sequence

TUNE: Auto-tuning status (Blinks for 1 sec. during Auto-Tuning)
LOCK: Lock setting status (Turns on when lock is set)

VX2

VX7, VX9

Panel cutout

[Unit: mm]

13 Sensor error

Classification Type VX2 VX3 VX4 VX7 VX9 ERROR message display

Burn-out

O

VX4 (top view)
VX3 W

L

D1

D

W1 H1

W

H

Product dimensions

D

D1

L

48.0 96.0 48.0 72.0 96.0 96.0 48.0 48.0 72.0 96.0 62.5 62.5 63.0 62.5 62.5 5.5 5.5 5.0 5.5 5.5 78.4 78.4 78.4 78.4 78.4

No Screen display Content

Cause and Action

1

SYS.E

System Data System data setting error (please contact us)

2

OPT.E

A A Option Data Option data setting error (please contact us)

3

E2P.E

EEPROM EEPROM error (please contact us)

T

H

H

W1 1) 45.0 90.5 45.0 67.5 92.0

4

ADC.E

AD Converter AD Converter error (please contact us)

B

Panel H1 1) 90.5 45.0 45.0 67.5 92.0

cutout

A

70.0 122.0 60.0 83.0 117.0 5

CAL.E

Calibration Calibration value setting error (please contact us)

B 2) 122.0 70.0 60.0 100.0 117.0 6

RJC.E

RJC

Reference contact compensation error (please contact us)

USB loader

VX7 is different from VX9 only in size.

Function key description(Used in operation mode) Menu key description (Used in operation mode)

No.

Combination

Description

No. Combination

Description

Press and hold

1

for 3 sec.

Lock / unlock

Press and hold

Simple menu

1

(set alarm value, PID value, HYS value, etc.)

Press and hold

for 1 sec. but go to operating mode from menu mode

2

Manual / automatic output mode

for 3 sec.

Press and hold

3

for 3 sec.

Auto tuning (AT) on / off

Press and hold

2

for 1 sec.

Full menu (set all parameters divided into groups)

Press and hold

4

for 1 sec.

5 Press

or

Switch RUN / STOP Release during alarm latch

Press and hold

3

for 1 sec.

Basic menu (Set input type, control method, control
cycle, alarm type, communication, lock, etc.)

A

Protective cover dimensions

W2

D2

H2

W2

Protective cover

H2

D2

48.4 94.4 48.0 71.8 94.4 48.4 48.1 71.8 26.9 26.9 24.0 26.9

    1. +0.5 mm tolerance applied * 2) 100.0 mm applied when using USB Loader cable in VX4

96.0 96.0 26.9

Bracket assembly drawing

VX4

VX2 VX3 VX7 VX9

Auto-tuning maximum elapsed time (24h) exceeded

– Check if the connected sensor and the set sensor are different

– If the output is not output from the output terminal when the control output is 100%

7

AT.E

Auto tuning

(please contact us) – If the control output is generated from the instrument but PV does not change

(check the wiring status)

– If the control output is 0%, enter the P, I, D values manually without running

AT for systems where temperature is not likely to drop

8

B.OUT

Burn out

Check sensor wiring status (check for disconnection) Check the sensor settings (check input type parameters (INP)) If the input is exceeded by more than ± OVER

9

OVR

+Over Check the sensor settings (if the input is exceeded within +5% of sensor input range)

10

-OVR

-Over

Check the sensor settings (if the input is exceeded within -5% of sensor input range)

Error messages are displayed on PV display window.

For further information, please visit our homepage(www.hanyoungnux.com) and refer to the user’s manual in the archive.

Parameter configuration

How to read parameters (example)
Parameter name

<0100>

Set value (SV) number [1,1 ~ 4]

Communication address

Initial value, description and display range

How to change parameter set values
Move to parameter change mode
Parameter change mode
Parameter set value change:
Save parameter set values and move to next parameter

Operation mode Model name &

System

Control/monitoring

FW version display & option display operation mode

Power on

SV change mode
Control output operation mode

Press and hold for 1 sec.

Press and hold for 1 sec. [2]

Press and hold for 1 sec. [2]

Press and hold for 1 sec.

Press and hold for 1 sec. [2]

Press and hold for 1 sec.

SV group

<0100> <0101> <0102> <0103> <0104> <0105> <0106>

3 Set value (SV) number [1,1 ~ 4] Set value (SV) high limit [1370, refer to input range] Set value (SV) low limit [-200, refer to input range] Set value 1 (SV 1) [-200, refer to input range] Set value 2 (SV 2) [-200, refer to input range] Set value 3 (SV 3) [-200, refer to input range] Set value 4 (SV 4) [-200, refer to input range]

3 <a+0> <a+1> <a+2> <a+3> <a+4> <a+5> <a+6> <a+8>

n. proportional band (heating) [ EUS 5.0%,1] n. integral time (heating) [ 240,OFF or 1 ~ 6000] n. derivative time (heating) [ 60,OFF or 1 ~ 6000] n. manual reset [ 50.0,-5.0 ~ 105.0] n.proportional band (cooling) [ EUS 5.0%,1] n.integral time (cooling) [ 240,OFF or 1 ~ 6000] n.derivative time (cooling) [ 60,OFF or 1 ~ 6000] n. heating/cooling deadband [ 3.0,-100.0 ~ 50.0]

CONTROL group

Full Menu: press and hold

ALARM group

for 1 sec.

TRANS group

SUB group

<0200> <0207> <0208> <0209> <0246> <0247> <0248> <0249> <0250>

3 Auto-tuning mode [STND,STND or LOW] Auto-tuning(AT) [OFF,OFF or ON] Anti- reset wind-up (ARW) [Auto, Auto or 50.0 ~ 200.0] Alpha [ 50, 0 ~ 100] 1.PID group
2.PID group
3.PID group
4.PID group
Ramp-up [ OFF, refer to input range] Ramp-up time [ 01.00,00.01 ~ 99.59] Ramp- down [ OFF, refer to input range] Ramp-down time [ 01.00,00.01 ~ 99.59] MV Bumpless [ ON,OFF or ON]

<0300+(n-1)x4> <0301+(n-1)x4> <0302+(n-1)x4> <0303+(n-1)x4>

<0316> <0317> <0318> <0319> <0320> <0321> <0015> <0322> <0323> <0016> <0324>

3 Alarm n type [1,0 ~ 13]

<0400>

Alarm n value [1]

<0401>

Alarm n deadband [1,1] Alarm n output hold status [RST,RST or SET]

<0402> <0403>

Loop break alarm time [480,0 ~ 7200]

<0404>

Loop break alarm set value [2,EUS 0.0 ~ 5.0%] Loop break alarm deadband [2,EUS 0.0 ~ 5.0%]

<0405> <0406>

Loop break alarm output hold status [RST,RST or SET]

<0407>

Heater break alarm 1 set value [OFF,1.0 ~ 50.0]

<0408>

Heater break alarm 1 deadband [0.5,0.1 ~ 50.0]

<0409>

Current detection 1 monitoring [0.0,0.0 ~ 55.0] Heater break alarm 2 set value [OFF,1.0 ~ 50.0]

<0410> <0411>

Heater break alarm 2 deadband [0.5,0.1 ~ 50.0]

Current detection 2 monitoring [0.0,0.0 ~ 55.0] Heater break alarm output hold status [RST,RST or SET]

3 Retransmission output type [PV,PV/SV/MV] Retransmission output high limit [1370,1] Retransmission output low limit [-200,1] Retransm. output high adjust. value [0,1]

<0500> <0501> <0502> <0503>

Retransm. output low adjust. value <0504+n-1)x4> [0,1]

Enable remote input [OFF,OFF or ON]

<0505+n-1)x4>

Remote input high limit [5.000,1.000 ~ 5.000]

<0506+n-1)x4>

Remote input low limit [1.000,1.000 ~ 5.000]

<0507+n-1)x4>

Remote input high scale value [1370,1] Remote input low scale value [-200,1]

<0520> <0521>

Remote input high adjust. value [0,1] Remote input low adjust. value [0,1]

<0522> <0523> <0524> <0525> <0526> <0527> <0528>

3 Sub 1 output type [ALM1,1] Sub 2 output type [ALM2,1] Sub 3 output type [ALM3,1] Sub 4 output type [ALM4,1] Alarm n ON delay time [0,0 ~ 999] Alarm n OFF delay time [0,0 ~ 999] Alarm n contact type [N.O,N.O or N.C] Alarm n output hold [OFF,OFF or ON] Loop break alarm ON delay time [0,0 ~ 999] Loop break alarm OFF delay time [0,0 ~ 999] Loop break alarm contact type [N.O,N.O or N.C ] Loop break alarm output hold [OFF,OFF or ON] Enable heater break alarm 2 [OFF,OFF or ON] Heater break alarm ON delay time [0,0 ~ 999] Heater break alarm OFF delay time [0,0 ~ 999] Heater break alarm contact type [N.O,N.O or N,C] Heater break alarm output hold [OFF,OFF or ON]

INPUT group

<0900> <0901> <0904> <0905> <0906> <0907> <0908> <0909>

3 Input type [K0,1] Unit [,1] Decimal point position [1,1] Scale high limit [100.0,-1999 ~ 9999] Scale low limit [0.0,-1999 ~ 9999] Reference junction compensation [ON,OFF or ON] Input filter [OFF,OFF or 1 ~ 120] Input bias [0,1]

OUTPUT group

<0800> <0801> <0802> <0803> <0804> <0805> <0806> <0807> <0808> <0809> <0810>

3 OUT1 control mode [PID,ONOFF or PID] OUT2 control mode [PID,NONE/ON OFF/PID] Control direction [REV,REV or DIR] Control cycle (OUT1) [1] Control cycle (OUT2) [1] ON/OFF control hysteresis (OUT1) [1,1] ON/OFF control hysteresis (OUT2) [1,1] Emergency output (OUT1) [0.0,1] Emergency output (OUT2) [0.0,1] Control output high limit [100,1] Control output low limit [0.0,1]

SET group

<0700> <0701> <0702> <0703> <0704> <0706> <0041> <0042> <0045>

3 Digital input mode [OFF,OFF or ON] Operation mode after power on [RUN,STOP or RUN] Parameter initialization [OFF,OFF or ON] Parameter set value lock [0,0 ~ 2] EEPROM lock during operation [OFF,OFF or ON] Indicator/controller selection [ON,OFF or ON] System data [0000~FFFF] Option data [0000~FFFF] Firmware version [V0.00~Vx.xx]

COMM group

<0600> <0601> <0602> <0603> <0604> <0605> <0606>

3 Communication protocol [PCK,1] Baud rate [9.6K,1] Parity bit [NONE,1] Stop bit [1,1 or 2] Data length [8,7 or 8] Address [1,1 ~ 99] Response delay time [0,0 ~ 10]

Basic Menu:

press and hold

for 1 sec.

<0900> <0909> <0800> <0801> <0802> <0803> <0804> <0805> <0806> <0300> <0301> <0302> <0304> <0305> <0306> <0308> <0309> <0310> <0312> <0313> <0314>

Input type [K0,1] Input bias [0,1] OUT1 control mode [PID,ONOF or PID] OUT2 control mode [PID,NONE/ONOF/PID] Control direction [REV,REV or DIR] Control cycle (OUT1) [1] Control cycle (OUT2) [1] ON/OFF control hysteresis (OUT1) [1,1] ON/OFF control hysteresis (OUT2) [1,1] Alarm 1 type [3, 0 ~ 13] Alarm 1 value [1570,1] Alarm 1 deadband [1,1] Alarm 2 type [10,0 ~ 13] Alarm 2 value [1570,1] Alarm 2 deadband [1,1] Alarm 3 type [1,0 ~ 13] Alarm 3 value [1370,1] Alarm 3 deadband [1,1] Alarm 4 type [2,0 ~ 13] Alarm 4 value [-200,1] Alarm 4 deadband [1,1]

<0600>

Communication protocol [PCK,1]

<0601> <0602> <0603> <0604> <0605> <0606> <0701> <0703>

Communication speed [96k,1] Parity bit [NONE,1] Stop bit [1,1 ~ 99] Data length [8,7 or 8] Address [1,1 ~ 99] Response delay time [0,0 ~ 10] Operation mode after power on [ RUN, STOP or RUN ] Parameter set value lock [ 0, 0 ~ 2 ]

Simple menu: press and hold

for 1 sec.

<0201> <0301> <0305> <0309> <0313>

Auto-tuning [OFF,OFF or ON] Alarm 1 setting [1570,1] Alarm 2 setting [1570,1] Alarm 3 setting [1370,1] Alarm 4 setting [-200,1]

PID No.1

PID No.2

PID No.3

<0805> <0806>

PID No.4
ON/OFF control hysteresis (OUT1) [1,1] ON/OFF control hysteresis (OUT2) [1,1]

3 <a+0> <a+1> <a+2> <a+3> <a+4> <a+5> <a+6> <a+8>

n. proportional band (heating) [ EUS 5.0%,1] n. integral time (heating) [ 240,OFF or 1 ~ 6000] n. derivative time (heating) [ 60, OFF or 1 ~ 6000 ] n. manual reset [ 50.0, -5.0 ~ 105.0 ] n. proportional band (cooling) [ EUS 5.0%, 1 ] n. integral time (cooling) [ 240, OFF or 1 ~ 6000 ] n. derivative time (cooling) [ 60, OFF or 1 ~ 6000 ] n. heating/cooling deadband [ 3.0, -100.0 ~ 50.0 ]

1 : Refer to the User’s Manual
Please visit our homepage (www.hanyoungnux.com) and refer to the user manual in the archive.
2 : Key to move to operation mode screen Press and hold in the parameter setting screen for 1 sec. to move to operation mode screen
3 : Move to group name display Press during parameter display to move to group name (but during parameter display in n.PID, it moves to n.PID.
The parameter display differs depending on suffix code options and parameter settings.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

HANYOUNG NUX User Manuals

Related Manuals