Hanyoung Nux MAS-025 Digital Indicator Instruction Manual
- June 10, 2024
- HANYOUNG NUX
Table of Contents
- Hanyoung Nux MAS-025 Digital Indicator
- Digital Indicator MAS Instruction Manual
- Usage Instructions
- Safety information
- Suffix code
- Specification
- Wire size and TIGHT TORQUE
- Dimensions and panel cutout
- Connection diagrams
- Assembly drawing
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Hanyoung Nux MAS-025 Digital Indicator
Digital Indicator MAS Instruction Manual
The Digital Indicator MAS is a product manufactured by Hanyoung Nux. The product has a rated capacity of 25A, 63A, or 125A and a rated insulation voltage Ui of 690V. It is equipped with a main switch and comes in two shape classifications – A for emergency use (Guard: YELLOW, HANDLE: RED) and B for normal use (Guard: WHITE,HANDLE: BLACK). The alerts declared in the safety manual are classified into Danger, Warning, and Caution according to their importance. The product dimensions are as follows:
- MAS-025: 66.3mm x 55.0mm x 38.8mm
- MAS-063: 88.0mm x 55.0mm x 48mm
- MAS-125: 88.0mm x 55.0mm x 68.4mm
Usage Instructions
Before using the Digital Indicator MAS, it is important to read the instruction manual carefully and follow the safety guidelines= provided. The product is suitable for use with motor loads according to UL/CSA standards.
To assemble the MAS-025, follow the assembly drawing provided in the manual. When connecting wires, refer to the wire size and tight torque specifications provided:
- MAS-025: Wire size (AWG No.) 14~7, Torque terminal screws – 0.8 Nm
- MAS-063: Wire size (AWG No.) 14~2, Torque terminal screws – 2.5 Nm
- MAS-125: Wire size (AWG No.) 8~1, Torque terminal screws – 2.5 Nm
It is important to use the product correctly and keep the instruction manual for future reference. If there are any issues or concerns, contact Hanyoung Nux for assistance.
Thank you for purchasing Hanyoung Nux products. Please read the instruction manual carefully before using this product, and use the product correctly. Also, please keep this instruction manual where you can see it any time.
Safety information
Please read the safety information carefully before use, and use the product
correctly.
The alerts declared in the manual are classified into Danger, Warning and
Caution according to their importance
DANGER
Indicates an imminently hazardous situation which, if not avoided,will result
in death or serious injury
WARNING
Indicates a potentially hazardous situation which, if not avoided,could result
in death or serious injury
CAUTION
Indicates a potentially hazardous situation which, if not avoided,may result
in minor injury or property damage
- Use within the product rating.
- Be sure to turn off the power when installing or disassembling the product.
Suffix code
Specification
▍ SpecificatiMoodnel
division
| MAS-025| MAS-063| MAS-125
---|---|---|---
Rated Insulation Voltage Ui| 690V| 690V| 690V
Rated through current Ith| 25A| 63A| 125A
Motor load according to UL/CSA| | |
3M-POHTAOSRE| 240V| 7.5HP| 15HP| 25HP
480V| 10HP| 30HP| 50HP
600V| 10HP| 30HP| 50HP
1M-POHTAOSRE| 120V| 1HP| 3HP| 6HP
240V| 2HP| 7.5HP| 15HP
Rated control output AC3| | |
MOTOR| 3X230V| 5.5kW| 15kW| 22kW
3X400V| 7.5kW| 22kW| 37kW
3X690V| 7.5kW| 22kW| 45kW
Rated control output AC23A| | |
MOTOR| 3X230V| 7.5kW| 18.5kW| 25kW
3X400V| 11kW| 30kW| 45kW
3X690V| 11kW| 30kW| 45kW
TERMINAL SCREW| M3.5| M6| M6
Wire size and TIGHT TORQUE
division Model | MAS-025 | MAS-063 | MAS-125 |
---|---|---|---|
Wire size (AWG No.) | 14~7 | 14~2 | 8~1 |
TORQUE TERMINAL SCREWS | 0.8 Nm | 2.5 Nm | 2.5 Nm |
Dimensions and panel cutout
Dimensions
MAS-025
MAS-063
MAS-125
Connection diagrams
Assembly drawing
HANYOUNGNUX CO.,LTD
28, Gilpa-ro 71beon-gil, Michuhol-gu, Incheon, Korea TEL : +82-32-876-4697
http://www.hanyoungnux.com
Read User Manual Online (PDF format)