ACTIVSENSE NC-MC-0-R Intelligent Conventional Manual Call Point Instruction Manual
- June 13, 2024
- ACTIVSENSE
Table of Contents
ACTIVSENSE NC-MC-0-R Intelligent Conventional Manual Call Point
Description
The NC Series Intelligent Conventional Manual Call Point is designed for
indoor use with compatible conventional fire panels. Each unit includes a
built-in resistor (0, 100, 470, or 560Ω, depending on the model purchased).
All units are supplied with a resettable element – this can be replaced with a
breakable element, if required (order number N-MC-FE). See “Replacing the
resettable element”.
The series includes the following models.
Model | Description |
---|---|
NC-MC-0-R | Red intelligent conventional manual call point – 0Ω [1] |
NC-MC-100-R | Red intelligent conventional manual call point – 100Ω |
NC-MC-470-R | Red intelligent conventional manual call point – 470Ω |
NC-MC-560-R | Red intelligent conventional manual call point – 560Ω [2] |
NC-MC-IS-0-R | Red intelligent conventional intrinsically safe manual call |
point – 0Ω
[1] Also available in blue (NC-MC-0-U), green (NC-MC-0-G), orange (NC-MC-0-O),
white (NC-MC-0-W), and yellow (NC-MC-0-Y).
[2] Also available in blue (NC-MC-560-U).
Figures
Figure 1: Backbox and mounting holes
Figure 2: Front assembly terminal block
Figure 3: Unlocking the front cover
Figure 4: Removing the front cover
Figure 5: Removing the resettable element
Figure 6: Replacing the front cover
Installation
Caution : This product must be installed and maintained by qualified
personnel adhering to all local or national installation requirements and any
other applicable regulations.
The manual call point can be surface mounted or recess mounted.
For surface mounting, order one of the backboxes shown in the table below.
Model | Description | Colour |
---|---|---|
N-MC-BB-R | Red backbox | Red |
N-MC-BB-U | Blue backbox | Blue |
N-MC-BB-G | Green backbox | Green |
N-MC-BB-O | Orange backbox | Orange |
N-MC-BB-W | White backbox | White |
N-MC-BB-Y | Yellow backbox | Yellow |
For recess mounting, order one of the recess adaptors shown in the table below.
Model | Description |
---|---|
N-MC-AFM-R | Red recess adaptor |
N-MC-AFMG-R | Red recess adaptor with fork grips |
N-MC-AFM-G | Green recess adaptor |
Remember to remove the protective dust cover before installation.
Note : The dust cover may also be used to indicate when the unit is not
operational (for example, before commissioning, during maintenance, when
disabled, etc.)
To surface mount the manual call point:
-
Fix the backbox onto the wall using 4 × M4 screws (not supplied) and feed the zone cable through the selected cable knockouts or through the rear of the backbox.
See Figure 1 for the location of the mounting holes. -
Connect zone cable and relay cable (if required) to the supplied terminal block, and then plug the terminal block into the PCB connector on the back of the front assembly (see Figure 2).
Use the supplied cable link to test cable continuity during installation.
See “Wiring” below for terminal block connections and zone cable specifications. -
Unlock and remove the front cover, and then remove the resettable element.
To unlock the front cover, insert the key and turn it clockwise (two clicks), then pull the cover outwards from the bottom to remove it (see Figure 3 and Figure 4).
To remove the resettable element, push the element up, and then pull it out (see Figure 5). -
Fix the front assembly to the backbox using the 2 screws supplied with the unit (located in the backbox).
-
Replace the resettable element (or add the breakable element, if required), and then replace the front cover (see Figure 6).
Turn the key anticlockwise (two clicks) to lock the cover, and then remove the key.
Finally, test the manual call point (see “Testing”).
Wiring
For optimal system performance, use 0.129 to 3.31 mm² (26 to 12 AWG) twisted-
pair cable.
Wire the unit as described below. Observe the indicated polarity.
Terminal | Description |
---|---|
Zi+ | Zone in (+) |
Zo+ | Zone out (+) |
Zi– | Zone in (–) |
Zo– | Zone out (–) |
COM | Common |
NC | Normally closed |
NO | Normally open |
Status LED
Two steady red LEDs on the front of the unit indicate that the manual call
point has been activated and is in alarm.
Note : The 0Ω manual call point has no LED indications.
Maintenance and Testing
Maintenance
The unit should be maintained and tested according to local or national requirements and any other applicable regulations. Do not modify internal wiring or circuitry.
Testing
To activate an alarm, push the resettable element or turn the key clockwise
(one click). To reset the device, turn the key
anticlockwise (one click). Reset the control panel after testing.
Replacing the resettable element
Replace the resettable element (or add the breakable element) as follows:
- Unlock and remove the front cover as described in “Installation” on page 2.
- Push the element up, and then pull it out (see Figure 5).
- Replace the resettable element (or add the breakable element, if required).
- Replace the front cover.
Specifications
Electrical
Operating voltage | 20 to 24 VDC |
---|
Current consumption
Standby| 0 mA
Alarm|
0Ω MCP| 55 mA [1]
100Ω MCP| 45 mA
470Ω MCP| 30 mA
560Ω MCP| 25 mA
Contact rating| Max. 1 A at 24 V
[1] Limited by the control panel
Mechanical and environmental
IP rating | IP41 |
---|
Backbox cable knockouts
Back| 1 × Ø 20 mm
Top| 1 × Ø 25 mm
Bottom| 2 × Ø 20 mm
Wire size
Minimum| 0.129 mm² (26 AWG)
Maximum| 3.31 mm² (12 AWG)
Operating environment
Operating temperature| −10 to +55°C
Storage temperature| −25 to +70°C
Relative humidity| 10 to 95% (noncondensing)
Colour
Red| RAL3028
Blue| RAL5005
Green| RAL6024
Orange| RAL2008
White| RAL9003
Yellow| RAL1003
Weight
Without backbox| 101 g
With backbox [1]| 160 g
Dimensions
Without backbox| 87 × 87× 26 mm
With backbox [1]| 87 × 87× 57 mm
[1] Backbox not supplied
Regulatory Information
This section provides a summary on the declared performance according to the
Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and (EU) 574/2014.
For detailed information, see the product Declaration of Performance
(available at firesecurityproducts.com).
EU compliance|
---|---
Certification body| 0370
Manufacturer| Carrier Safety System (Hebei) Co. Ltd., 80 Changjiang East Road,
QETDZ, Qinhuangdao 066004, Hebei, China. Authorized EU manufacturing
representative: Carrier Fire & Security B.V., Kelvinstraat 7, 6003 DH Weert,
Netherlands.
Year of first CE marking| 2021
Declaration of Performance number [1]| 03-0211-360-1003
EN 54 [1]| EN 54-11 Type A (Indoor Use)
Product identification| NC-MC-0-R, NC-MC-100-R, NC-MC-470-R, NC-MC-560-R, NC-
MCS06-560-R, NC-MCS18-560-R
Intended use| See the product Declaration of Performance
Declared performance| See the product Declaration of Performance
| 2012/19/EU (WEEE Directive): Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the European Union. For proper
recycling, return this product to your local supplier upon the purchase of
equivalent new equipment, or dispose of it at designated collection points.
For more information see: recyclethis.info.
[1] The Declaration of Performance only covers the red manual call points
listed in Product identification. Only red manual call points are covered by
EN 54-11 (this standard does not cover intrinsically safe devices).
Contact Information And Product Documentation
For contact information or to download the latest product documentation, visit firesecurityproducts.com.
Product Warnings And Disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE TO AND INSTALLATION BY QUALIFIED
PROFESSIONALS.
CARRIER FIRE & SECURITY B.V. CANNOT PROVIDE ANY ASSURANCE THAT ANY PERSON OR
ENTITY BUYING ITS PRODUCTS, INCLUDING ANY “AUTHORIZED DEALER” OR “AUTHORIZED
RESELLER”, IS PROPERLY TRAINED OR EXPERIENCED TO CORRECTLY INSTALL FIRE AND
SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers and product safety information,
please check https://firesecurityproducts.com/policy/product-warning/ or
scan the QR code: