ACTIVSENSE DM3110R Addressable Point Detector Intelligent Addressable Manual Call Point Installation Guide
- June 13, 2024
- ACTIVSENSE
Table of Contents
ACTIVSENSE DM3110R Addressable Point Detector Intelligent Addressable
Manual Call Point Installation Guide
Installation Sheet
Description
The DM3000 Series Intelligent Addressable Manual Call Point is designed for
indoor use and supports the Aritech 2000 protocol.
All units are supplied with a resettable element – this can be replaced with a breakable element, if required (order number
N-MC-FE). See “Replacing the resettable element” on page 3. The series includes the following models.
Model | Description |
---|---|
DM3010R [1] | Red intelligent addressable manual call point |
DM3110R [1] | Red intelligent addressable manual call point with integrated |
short circuit isolator
[1] Also available in blue, green, orange, white, and yellow.
Figures
Figure 1: Mounting holes and dimensions
Figure 2: Front assembly terminal block and DIP switch
Figure 3: Unlocking the front cover
Figure 4: Removing the front cover
Figure 5: Removing the resettable element
Figure 6: Replacing the front cover
Installation
Caution: This product must be installed and maintained by qualified personnel adhering to all local or national installation requirements and any other applicable regulations.
Addressing
Set the device address before installation using the DIP switch on the back of
the front assembly (see Figure 2).
The address range is 001-128. See the table on the last page of this publication for DIP switch positions for each address.
Note: If you change the device address after installation, you must disconnect the device from the loop power for at least one second and then reconnect it for the new address to be recognised.
Installation
The manual call point can be surface mounted or recess mounted.
For surface mounting, order one of the backboxes shown in the table below.
Model | Description |
---|---|
N-MC-BB-R | Red backbox |
N-MC-BB-U | Blue backbox |
N-MC-BB-G | Green backbox |
N-MC-BB-O | Orange backbox |
N-MC-BB-W | White backbox |
N-MC-BB-Y | Yellow backbox |
For recess mounting, order one of the recess adaptors and (if required) trim skirts shown in the table below.
Model | Description |
---|---|
N-MC-AFM-R | Red recess adaptor |
N-MC-AFMG-R | Red recess adaptor with fork grips |
N-MC-S-R | Red trim skirt |
N-MC-AFM-G | Green recess adaptor |
N-MC-S-G | Green trim skirt |
Remember to remove the protective dust cover after commissioning.
Note: The dust cover may also be used to indicate when the unit is not operational (for example, before commissioning, during maintenance, when disabled, etc.)
To surface mount the manual call point:
-
Fix the backbox onto the wall using 4 × M4 screws (not supplied) and feed the loop cable through the selected cable knockouts. Depending on your installation requirements, the backbox can be installed with two cable knockouts at the top and one at the bottom or with one cable knockout at the top and two at the bottom. See Figure 1 for the location of the mounting holes.
-
Connect loop cable to the supplied terminal block, and then plug the terminal block into the PCB connector on the back of the front assembly (see Figure 2). Use the supplied cable link to test cable continuity before the terminal block is plugged into the PCB connector on the back of the front assembly. See “Wiring” on page 3 for terminal block connections and loop cable specifications.
-
Unlock and remove the front cover, and then remove the resettable element. To unlock the front cover, insert the key and turn it clockwise (two clicks), then pull the cover outwards from the bottom to remove it (see Figure 3 and Figure 4). To remove the resettable element, push the element up, and then pull it out (see Figure 5).
-
Fix the front assembly to the backbox using the 2 screws supplied with the unit (located in the backbox).
-
Replace the resettable element (or add the breakable element, if required), and then replace the front cover (see Figure 6).
Turn the key anticlockwise (two clicks) to lock the cover, and then remove the key.
Finally, test the manual call point (see “Testing” on page 3).
Wiring
For optimal system performance, use 0.13 to 3.31 mm² (0.40 to 2.05 mm) twisted-pair cable with a maximum length of 2 km.
Wire the unit as described below. Observe the indicated polarity.
Terminal | Description |
---|---|
A+ | Positive line (+) |
B+ | Positive line (+) |
A– | Negative line (–) |
B– | Negative line (–) |
Device status
The device status is indicated by two colour changing LEDs on the front of the unit, as shown in the table below.
State | Indication |
---|---|
Alarm | Steady red LEDs [1] |
Isolation active | Steady yellow LEDs [2] |
Fault | Flashing yellow LEDs |
Communicating | Flashing green LEDs |
- This may also indicate an active Locate Device command from the control panel.
- DM3110 models only.
Maintenance and testing
Maintenance
The unit should be maintained and tested according to local or national
requirements and any other applicable regulations. Do not modify internal
wiring or circuitry.
Testing
To activate an alarm, push the resettable element or turn the key clockwise (one click). To reset the device, turn the key anticlockwise (one click). Reset the control panel after testing.
Replacing the resettable element
Replace the resettable element (or add the breakable element) as follows:
- Unlock and remove the front cover as described in “Installation” on page 2.
- Push the element up, and then pull it out (see Figure 5).
- Replace the resettable element (or add the breakable element, if required).
- Replace the front cover.
Analogue values
Analogue values for diagnosing and troubleshooting device status are shown in
the table below.
Value | Device Status |
---|---|
32 | Normal |
128 | Alarm |
Specifications
Electrical
Operating voltage | 17 to 38 VDC |
---|---|
Current consumption StandbyDM3010 DM3110AlarmDM3010 DM3110 | 180 µA200 µA **** |
2.8 mA2.8 mA
Isolation
The following isolation specifications apply to DM3110 models with an
integrated short circuit isolator.
Current consumption (isolation ACTIVE ) | 1.5 mA |
---|---|
Isolation voltage Minimum Maximum | **** 14 VDC15.5 VDC |
Reconnect voltage Minimum Maximum | **** 14 VDC15.5 VDC |
Rated current Continuous (switch closed) Switching (short circuit) | **** 1 A1 |
A
Leakage current| 1 mA max.
Series impedance| 0.06 Ω max.
Number of isolators per loop| 128 max.
Number of devices between isolators| 32 max.
Mechanical and environmental
IP rating | IP41 |
---|---|
Backbox cable knockouts BackTop/bottom [1] | **** 1 × Ø 20 mm1 × Ø 25 mm2 × Ø |
20 mm
Wire sizeMinimum Maximum| 0.13 mm² (0.40 mm)3.31 mm² (2.05 mm)
Operating environment Operating temperature Storage temperature Relative
humidity| −25 to +72°C−25 to +72°C10 to 95% (noncondensing)
ColourRed Blue Green Orange White Yellow| RAL3028 RAL5005 RAL6024
RAL2008 RAL9003 RAL1003
MaterialBody Contacts| ABS, PC, PMMA, POMN sickle plated H59, tin plated
QSn6.5-0.1, tin plated H65
Weight Without backbox With backbox [2]| **** 110 g165 g
- Top/bottom location subject to installation orientation.
- Backbox not supplied.
Regulatory information
This section provides a summary on the declared performance according to the
Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and
(EU) 574/2014.
For detailed information, see the product Declaration of Performance (available at firesecurityproducts.com)
Conformity
Notified/Approved body | 0370 |
---|---|
Manufacturer | Carrier Safety System (Hebei) Co. Ltd., 80 Changjiang East Road, |
QETDZ, Qinhuangdao 066004, Hebei, China.Authorized EU manufacturing
representative:Carrier Fire & Security B.V., Kelvinstraat 7, 6003 DH Weert,
Netherlands.
Year of first CE marking| 2022
Declaration of Performance number [1]DM3010 DM3110|
03-0210-360-108303-0210-360-1093
EN 54 [1]| EN 54-11 Type A (Indoor Use) EN 54-17:2005
Product identification [1]| DM3010R, DM3110R, DM3010RS06, DM3110RS06,
DM3010RS18, DM3110RS18, DM3010RS27, DM3110RS27, DM3010RSCH, DM3110RSCH,
DM3010RSCL, DM3110RSCL
Intended use| See the product Declaration of Performance
Declared performance| See the product Declaration of Performance
| 2012/19/EU (WEEE Directive): Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the European Union. For proper
recycling, return this product to your local supplier upon the purchase of
equivalent new equipment, or dispose of it at designated collection points.
For more information see: recyclethis.info.
The Declaration of Performance only covers red manual call points. Only red manual call points are covered by EN 54-11 and EN 54-17.
Contact information and product documentation
For contact information or to download the latest product documentation, visit firesecurityproducts.com.
Product warnings and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE TO AND INSTALLATION BY QUALIFIED PROFESSIONALS. CARRIER FIRE & SECURITY B.V. CANNOT PROVIDE ANY ASSURANCE THAT ANY PERSON OR ENTITY BUYING ITS PRODUCTS, INCLUDING ANY “AUTHORIZED DEALER” OR “AUTHORIZED RESELLER”, IS PROPERLY TRAINED OR EXPERIENCED TO CORRECTLY INSTALL FIRE AND SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers and product safety information, please check https://firesecurityproducts.com/policy/product warning/ or scan the QR code: