EATON IL019140ZU Moeller Series xPole Home Switch
Product Information
The product is a circuit breaker or protective device used for electrical installations. It is designed to protect against overcurrents and short circuits in both single-phase and three-phase applications. The circuit breaker is available in different types and configurations, including 1-pole, 2-pole, 3-pole, 4-pole, and 3-pole with neutral (3p+N). It meets the standards of IEC/EN 60898-1 and UL 1077 for safety and performance.
Technical Specifications
- Tripping Current: 155% of rated current at 30°C
- Operating Voltage: 230/400V AC
- Frequency: 50-60Hz
- Short Circuit Capacity (Icn) : 6kA
- IP Rating: IP20
Usage Instructions
- Before installation, ensure that the power supply is turned off.
- Determine the appropriate type and configuration of the circuit breaker based on your electrical installation requirements.
- Connect the circuit breaker to the electrical panel or distribution board according to the wiring diagram provided in the user manual.
- Make sure to follow the correct polarity when connecting the line and neutral wires.
- Tighten the connection screws securely, using a torque wrench if specified (e.g., 2-2.4Nm).
- For extension or additional protection, refer to the specified back-up fuse ratings and connect accordingly.
- Once all connections are made, double-check the wiring to ensure correctness.
- Turn on the power supply and test the circuit breaker by operating the ON/OFF switch.
- Periodically inspect and maintain the circuit breaker according to the manufacturer’s recommendations (e.g., every 6 months).
- For disposal or recycling of the product, refer to the recycling information provided on the manufacturer’s website.
Note: It is recommended to consult a qualified electrician or professional for proper installation and usage of the circuit breaker.
Dimension
Extension for MCB’s:
Supplementary Protector USA/Canada Technical Data UL 1077
1 phase (series-fuse 100A):Tripping Current:
5 kA – 277 V ~ 60 Hz 155 % of rated current 3 phase (series-fuse 100 A): at 30oC
5 kA – 277/480 V ~ 60 Hz Cu 75oC, min. AWG 18,
max. AWG 4, Nm 2.4
Wiring
Technical specification
- HN-(xxx)
- Nominal voltage (U): 230/400 V
- Rated current (In): 1A-63A AC
- Nominal frequency (f) : 50-60Hz
- Rated short-circuit power Icn (EN60898-1) at 230: 6kA
- Standards: IEC/EN 60898-1
- Number of poles : 1p, 2p, 3p, 4p, 3p+N
- Overvoltage category: 3
- Protection level (IP): IP20
- Eaton Industries (Austria) GmbH, Eugenia 1, 3943 Schrems, Austria
- © 2019 by Eaton Industries (Austria) GmbH,www.eaton.eu/documentation
- MA-G9.qxd / 10.2019r / IL019140ZU / 180503264
- www.eaton.com/recycling All Rights Reserved / Printed in Austria