IRay Technology AT30 Online Dual Spectrum Thermal Camera User Manual

June 13, 2024
Iray Technology

IRay Technology AT30 Online Dual Spectrum Thermal Camera

Product Information

The AT30 Online Dual-spectrum Thermal Camera is a product developed by IRay Technology Co., Ltd. It is a compact-sized thermal camera that supports accurate temperature measurement. The camera features bi-spectral display, multi-protocol access to industrial or IoT systems, and a multi-functional web client. It also supports Power over Ethernet (PoE) for convenient installation.

Main Features:

  • Accurate temperature measurement
  • Supports PoE
  • Bi-spectral display
  • Supports multi-protocol access to industrial or IoT systems
  • Multi-functional web client
  • Wi-Fi hotspot
  • Compact size

Typical Applications:

  • Monitoring power distribution cabinet
  • Monitoring warehouse
  • Monitoring production line

Product Usage Instructions

Calibration:

It is recommended to perform annual calibration to ensure the accuracy of temperature measurement. Calibration can be done through IRay Technology or third-party organizations.

Accuracy:

For accurate measurement, it is recommended to use the thermal camera after it has been stable for 30 minutes.

Video Teaching:

You can search for mount and use videos from the IRay Technology website for additional guidance on using the thermal camera.

Documentation Update:

The user manuals are updated several times per year. To access the latest manuals and notifications of changes, please visit the IRay Technology website.

Mechanical Installation:

The thermal camera comes with mounting interfaces on the front and back. To install, punch holes using the auxiliary stickers provided in the package and use screws to secure the camera. There are two optional forms of front and back installation available.

WARNING: Do not use screws that are too long to avoid damaging the thermal camera. The maximum hole depth for the front shell is 10mm, and for the rear shell is 4mm. During operation, the thermal camera may generate heat. To dissipate the heat effectively, it is suggested to fix the back shell of the thermal camera on a metal object to minimize temperature drift of the infrared detector.

IRay Technology Co., Ltd.
www.infiray.com

Introduction to IRay Technology

IRay Technology concentrates on developing infrared thermal imaging technologies and manufacturing relevant products, with completely independent intellectual property rights. IRay is committed to providing global customers with professional and competitive infrared thermal imaging products and solutions. The main products include IRFPA detectors, thermal imaging modules, and terminal thermal cameras and imagers. With R&D personnel accounts for 48% of all employees, 787 intellectual property projects in terms of IRay have been authorized and accepted: 629 patented technologies authorized and accepted in China (including those for integrated circuit chips, MEMS sensors design and manufacture, Matrix III image algorithms and intelligent precise temperature measurement algorithms, etc.); 18 patented technologies authorized and accepted overseas; 101 software copyrights; and 39 integrated circuit layout designs.(The statistic data is up to August, 2021) IRay products have been applied in various fields, including epidemic prevention and control, industrial thermography, security and fire control, night vision observation, automatic driving, Internet of Things, AI, and machine vision.

Legal Disclaimer

Legal Disclaimer
The thermal cameras manufactured by IRAY TECHNOLOGY are warranted for a period of two-year and the accessories are warranted for a period of three-month form the delivery date of the original purchase, provided such products have been under normal storage, use and maintenance. This warranty extends only to the original purchaser and is not transferable. It is not applicable to any product that has be subjected to misuse, neglect, accident or abnormal conditions of operation.
In the case of a defect in a product covered by this warranty, the product must not be further used or maintained in order to prevent additional damage. The purchaser shall promptly report any defect to IRAY TECHNOLOGY or this warranty will not apply.
IRAY TECHNOLOGY will, at its option, repair or replace any such defective product free of charge if, upon inspection, the product or accessories prove to be defective, the user can contact with after-sales service department of IRAY TECHNOLOGY within the said warranty period.

Copyright
©IRay Technology Co., Ltd. 2022. All right reserved worldwide. All contents in this manual, including words, pictures, images, etc., belong to IRAY TECHNOLOGY CO., LTD. (Hereinafter referred to as “THE COMPANY” or “IRAY TECHNOLOGY”). No part of the manual, in whole or in parts, may be copied, photocopied, translated, or transmitted without the prior written permission of IRAY TECHNOLOGY. This manual is used as a guide. The photos, graphics, diagrams and illustrations provided in the manual are only used to explain, which may be different from the specific product. Please refer to the real object. We try our best to make sure the contents in this manual are accurate. We do not provide any representations or warranties in this manual.
IRAY TECHNOLOGY reserve the right to update the manual. If you need the latest version of this manual, please contact us. It is recommended that you use this manual with the guidance of professionals.

Quality Assurance
The Quality Management System under which these products are developed and manufactured has been certified in accordance with the ISO 9001 standard.
We reserve the right to make changes and improvements on any of the products without prior notice.

Safety Information

WARNING

  1. Before using the cleanser, make sure you read all applicable material safety data sheets (MSDS) and warning labels on cleanser containers.
  2. Do not use too long screws when installing the front/rear mounting bracket, which may damage the thermal camera.
  3. It is prohibited to place the product in a high temperature above 70°C or in a low temperature below-45 °C.
  4. It is forbidden to disassemble or refit the thermal camera at will.

CAUTION

  1. No matter there is a lens cover or not, do not point the thermal camera towards strong light or equipment with laser radiation. This will affect the accuracy of the thermal camera and even damage the detector in the thermal camera.
  2. Do not use the product under conditions that doesn’t match the environmental requirements. For specific use environment requirements, see the product parameter table..
  3. Do not apply solvents or equivalent liquids to the camera, the cables, or other items.
  4. Be careful when you clean the infrared lenses. The lens has an anti-reflective coating which is easily damaged. Damage to the infrared lens can occur with too much force or cleaning with rough objects such as tissues.

Notice to user

Calibration
Annual calibration to the thermal camera is recommended to ensure the accuracy of temperature measurement, either through IRAY TECHNOLOGY or third-party organizations.

Accuracy
For accurate measurement, it’s recommended that you use the thermal camera after it is stable for 30 minutes.

Video Teaching
You can search for mount and use videos from our website.

Documentation Update
Our manuals are updated several times per year, and we also issue product- critical notifications of changes on a regular basis. Please visit our website to access the latest manuals and notifications.

Product Introduction

IIRay Technology AT30 Online Dual Spectrum Thermal Camera-FIG2Ray Technology
AT30 Online Dual Spectrum Thermal Camera-FIG2








Main Features

| Accurate temperature measurement
---|---
Support PoE
Bi-spectral display
Support multi-protocol access to industrial or IoT systems
Multi-functional web client
Wi-Fi hotspot
Compact size




Typical Applications

| Monitoring power distribution cabinet
---|---
Monitoring warehouse
Monitoring production line

Quick Start Guide

Please follow the steps:

1. After installing the thermal camera in the desired position, use the cable to connect the thermal camera and the computer correctly. There are two power supply methods for AT30. Connect the device to the PoE port of the power supply through the M12 8-pin adapter cable or connect to the DC power supply through the M12 12-pin adapter cable. Connect AT30 to the network, and wait for 2 minutes after powering on. The power indicator light is steady blue and the network indicator

light flashes green, indicating that the network connection is normal.

2.  Modify the computer network segment to be the same with that of thermal camera.

The specific path is “Control Panel”-“Network and Internet”-“Network and Sharing Center”-“Change Adapter Options”-“Ethernet”-“Properties”-“Internet Protocol Version 4 (TCP/IPv4)” – “Use the following IP address”-set the IP address to 192.168.1.xxx.

Product and Accessories List

Product and Accessories

AT30 online dual-spectrum thermal camera
M12 8-pin adapter cable
Fixing accessories (screws, mounting stickers)
Optional Accessories

M12 12-pin adapter cable &alarm input/output cable
front/rear mounting bracket

Mechanical Installation

The front and back of the thermal camera are equipped with mounting interfaces, which can be installed with screws after the holes are punched with the auxiliary stickers in the package. In addition, we also provide two optional forms of front and back installation.

WARNING
Do not use too long screws in case of damaging the thermal camera.
The maximum hole depth of the front shell is 10mm, and the maximum hole depth of the rear shell is 4mm.

It’s normal that the thermal camera will generate heat during operation. In order to sufficiently dissipate the heat, it is suggested that the back shell of the thermal camera should be fixed on a metal object to minimize the temperature drift of the infrared detector in thermal camera.

Installing Shells with Screws
As shown in Figure 7.1, please paste the sticker to the position to be installed, and then punch 4 Φ2.5 mounting holes according to the label on the sticker, and use 4 M2 screws to install the front shell.

IRay Technology AT30 Online Dual Spectrum Thermal Camera-
FIG3

Front Mounting
There are four M4 threaded holes on the front mounting bracket for fixing.

Step 1 Install the front mounting bracket
As shown in Figure 7.2, connect the front mounting bracket and the thermal camera with ST2.2*8 self-tapping screws. The installation effect is shown in Figure 7.3.

Step 2 Punch holes
As shown in Figure 7.4, please paste the sticker to the position to be installed, and then punch four Φ4.5 mounting holes according to the label on the sticker.

Step 3 Install the thermal camera
As shown in Figure 7.4, use M4 screws to install the thermal camera to the designated location.

IRay Technology AT30 Online Dual Spectrum Thermal Camera-FIG4IRay Technology
AT30 Online Dual Spectrum Thermal Camera-FIG4

Rear Mounting

There are four M4 threaded holes on the rear mounting bracket for fixing.

Step 1 Install the rear mounting bracket
As shown in Figure 7.5, connect the rear mounting bracket and the thermal camera with M2*6 screws. The effect installation is shown in Figure 7.6

Step 2 Punch holes
As shown in Figure 7.7, please paste the sticker to the position to be installed, and then punch four Φ4.5 mounting holes according to the label on the sticker.

Step 3 Install the thermal camera
As shown in Figure7.7, use M4 screws to install the thermal camera to the designated location.

IRay Technology AT30 IRay Technology AT30 Online Dual Spectrum Thermal
Camera-FIG5Online Dual Spectrum Thermal Camera-FIG5

Alarm Input and Output

Alarm Input
Support 1-ch active alarm input (switch value, photoelectric isolation).

Alarm Output
Support 2-ch alarm outputs (switch value, photoelectric isolation), 3~25VDC, maximum 85mA.

Technical Data

Imaging and Optical Data







Infrared

| Resolution| 384×288
NETD| 40mK
Frequency| 25Hz
Lens| 3.8mm
FOV| 68.0°×51.8°
Focus| Focus free




Visible Light

| Visible Light Pixels| 2 MP
FOV| 81°×61°
Supplement Light| LED
Detector Data

Detector Type| VOx, Uncooled FPA detector
Spectral Range| 8~14μm
Pixel| 12μm
Temperature Measurement

Object Temperature Range| -20~650℃
Accuracy| ±2℃ or ±2%, the larger value shall prevail
Spot/Line/Area| maximum 8 spots/8 lines/8 areas
Palette| 20




Environment Variable Correction

| ****

distance, atmospheric temperature, emissivity, reflection temperature, atmospheric transmittance

---|---
Alarm






Alarm Function

| ****

The highest temperature, lowest temperature and average temperature in all temperature measurement points, temperature measurement areas and lines can be configured with separate alarm outputs.






Alarm Input/Output

| ****



1-ch alarm input; 2-ch alarm out


Other alarms: save image/video, sending file (FTP), email (SMTP), and flash alarm.

Alarm






Alarm Function

| ****

The highest temperature, lowest temperature and average temperature in all temperature measurement points, temperature measurement areas and lines can be configured with separate alarm outputs.






Alarm Input/Output

| ****



1-ch alarm input; 2-ch alarm out


Other alarms: save image/video, sending file (FTP), email (SMTP), and flash alarm.

Ethernet

Ethernet Functions| control, imaging and power supply
Ethernet Connector Type| RJ45/ Wi-Fi/ Hotspot
Ethernet Power Supply| Support PoE
Network Protocol| TCP,UDP,RTSP,HTTP,SMTP
Interface Protocol| ONVIF,GB28181,Modbus TCP,MQTT
Image transmission







Image Stream

| Image Stream Format| H.264/H.265



Resolution

| visible light 1600×1200;

infrared 384×288, support super resolution up to Max. 1024×768



Image Mode

| thermal image, visual image, fusion, DDE, and parallel display of visual

images are supported.

Frame Rate Adjustment| supported



Data Stream

| ****


Data Stream Transmission

| Visible and thermal images, temperature stream, adjustable

frame rate





Image Storage

| Storage Medium| built-in 32GB storage


Storage Mode

| store thermal images and visible


images simultaneously.

File Format| JPG, MP4


Storage Form

| local storage, connected to


monitoring systems, such as NVR.

Typical Power Supply

External Power| 12~30V DC
PoE| IEEE 802.3af
Power Consumption| ≤2W


Environmental Data



Encapsulation

| ****

IP67


Operating Temperature Range

| ****

-10~50℃


Storage Temperature Range

| ****

-40~70℃


Humidity

| ****

≤95% (no condensation)




EMC

| ****

IEC 61000-4-2(anti-interference)



IEC 61000-4-3(anti-radiation)


Shock

| ****

25G,IEC68-2-29


Vibration

| ****

2G, IEC68-2-6

Physical Data

Dimension| 109×58×31mm
Weight| 191g


Housing Material

| Front shell is plastic and rear shell is


aluminum alloy.

Others

Certification| CE/FCC/RoHS


SDK

| Cross-platform SDK for secondary


development.





External Interface

| M12, Type A ,8-pin, including 10M / 100M adaptive Ethernet port and PoE power supply;

M12, Type A, 12-pin, including DC power


supply, alarm input and output;

Pin Configuration for Interfaces

Ethernet Pin Configuration (8pin

Pin Configuration Pin Configuration

1

| ****

TX+

| ****

5

| ****

PD+


2

| ****

TX-

| ****

6

| ****

PD+


3

| ****

RX+

| ****

7

| ****

PD-


4

| ****

RX-

| ****

8

| ****

PD-

Power Pin Configuration (12pin

Pin Configuration Pin Configuration
1 Power + 7 ALARM POWER2
2 Power + 8 ALARM OUT2
3 Power Ground 9 ALARM IN+
4 Power Ground 10 ALARM IN-
5 ALARM_POWER1 11 GND
6 ALARM_OUT1 12 Video

Mechanical Drawings

IRay Technology AT30 IRay Technology AT30 Online Dual Spectrum Thermal
Camera-FIG9Online Dual Spectrum Thermal Camera-FIG9

Common Troubleshooting

Troubles Possible Cause Solutions




Camera cannot be started.

| The supply voltage exceeds the normal working supply voltage

range.

| ****

Check whether the power supply voltage is between 12 and 30V

The power connector is loose.| Check whether the power cable is connected


Web cannot be logged in.

| ****


IP setting is wrong.

| Manually configure the

computer address to the 192.168.1.XX


Image is stuck.

| Network cable connection is loose.| After checking the network cable connection, restart the web.

Cleaning Thermal Camera

Cleaning Camera Housing, Cables and Other Items

Camera Housing, Cables and Other Items




Liquids

| ****

One of the following liquids can be used. 1.Warm water

2. Neutral detergent solution

Cleaning Tools| A soft cloth




Cleaning Procedures

| Please follow this procedure: 1.Soak a soft cloth in the liquid.

2. Twist the cloth to remove excess liquid.


3. Clean the camera parts with the cloth.

Cleaning Infrared Lens

Cleaning Infrared Lens



Liquids

| One of the following liquids can be used.

1.Commercial lens cleaning liquid with more than 30% is opropyl alcohol.

2.96% ethyl alcohol(C2H5OH).

Cleaning Tools| Dustless cloth, cotton wool




Cleaning Procedure

| ****

Please follow this procedure (Take dustless cloth as an example).

1.Soak the dustless cloth in the liquid. 2.Gently wipe the lens with the dustless cloth

CAUTION
The dustless cloth or cotton wool should be used one time only.

Appendix A Emissivity of Common Materials

Material Temperature (℃) Emissivity
Water 0~100 0.95~0.98
Soil(dry) 20 0.92
Soil(wet) 20 0.95
Woods 17 0.962
Sand 20 0.9
Sandstone 19 0.909~0.935
PVC plastic 70 0.93
Asphalt 20 0.967
Paint 70 0.92~0.94
Wallpaper 20 0.85~0.90
Cloth 20 0.98
Concrete 20 0.92
Pavement surface 5 0.974
Smooth porcelain 20 0.92
Ceramic tile 17 0.94
Gypsum 17 0.86
Bricks 35 0.94
Hard rubber 0~100 0.89
Charcoal 20~400 0.95~0.97
Granite(rough) 20 0.879
Cold rolled steel 70 0.09
Oxidized steel 50 0.88
Copper 20 0.07
Oxidized copper 50 0.6~0.7