ARADA BK545 Hamlet Solution 5 Inset (S4) stove Installation Guide
- June 13, 2024
- ARADA
Table of Contents
Dry stove installation guide
Suitable For Freestanding
and Inset Appliances
BK545 Hamlet Solution 5 Inset (S4) stove
Arada Dry Stove Installation Guide
Please carefully read through the entirety of this installation guide
before commencing installation. Should you have any questions about our stoves
that are not covered in this manual, please contact the Arada retailer in your
area, or call our technical support department on +44 (0)1297 632052.
Arada has a policy of continuous product development and therefore we reserve
the right to amend specifications without prior notice.
Please check with your retailer or dealer if you are unsure about any aspect
of your stove, its installation or correct use.
Warnings
It is a legal requirement that the installation of all new or replacement,
wood or solid fuel heating appliances obtain Building Control approval from
your local authority. This can be done by using a qualified heating engineer,
affiliated to a government approved Competent Persons Scheme such as those
listed on www.gov.uk/building-regulations-competent-personschemes You can also
consult your local buildings inspector / controller. All local regulations,
including those referring to National and European standards, need to be
complied with when installing the appliance. Refer to the current issue of BS
8303 code of practice for the installation of domestic heating appliances
burning solid mineral fuel. This stove should not be installed into a chimney
that serves any other heating appliance.
Any further warnings in this document will be marked out in a box such as this
one. Ignoring the warnings could lead to damage/injury to persons and/or
property.
Any manufacturer’s instructions must not be taken as overriding statutory
requirements. Arada Ltd will not be responsible for any consequential or
incidental loss or injury however caused.
Health and safety
Before any installation work is undertaken consideration must be given to the
Health and Safety at Work Act 1974. Safe working practices should be followed
at all times. Please consult health and safety guidelines for advice on
handling heavy and/or large items. During installation ensure that adequate
precautions are taken to avoid unnecessary risk to yourself or any
householder. The danger from the caustic nature of fire cement, should be
avoided by using these accepted methods: Wear gloves when handling fire
cement. Wear goggles when chiseling or looking up chimneys. This stove
contains no asbestos. If there is a possibility of disturbing any asbestos in
the course of the installation then please seek specialist guidance and use
appropriate protective equipment.
Hearths and Recesses
The stove should be installed on a surface with adequate load bearing
capacity. If the existing construction does not meet this prerequisite,
suitable measures (e.g. load distributing plate) should be taken to achieve
it. Please pay particular attention when examining existing building work for
suitability to meet the following requirements.
When installing an inset stove, hearths should have a sufficiently flat
surface to allow a good seal to the stove body to be created during its
installation. Stonework, uneven bricks etc., may need further work to ensure
that this can be achieved. Any voids behind an inset stove should be filled
with vermiculite or similar. The stove should be installed on a non-
combustible surface not less than 12mm thick (conforming to Building
Regulations unless otherwise specified) of suitable load bearing capacity and
heat resistance. Allowances should be made for the expansion and contraction
of any materials which are fitted up to and near the appliance.
If required, the dimensions of any constructional hearth for all stoves should
project at least 500mm forward of the front of the appliance and 150mm at the
sides. The surface of the hearth should be free of combustible materials. The
superimposed hearth for all installations should project at least 225mm
forward from the front of the appliance and 150mm either side of the edge of
the appliance. In most buildings with solid concrete or stone floors, the
requirement will be met by the floor itself, but mark the hearth to ensure
floor coverings are kept well away or use different levels to mark the hearth
perimeter. Please be aware that hot air can cause staining above the fire in a
similar fashion to walls above radiators. To help prevent this and cracking we
recommend that any plaster above the fire should be fitted with reinforcing
expanding mesh for at least 220mm above, and the full width of the fire. You
should also use a suitably heat resistant plaster which should be allowed
sufficient time to fully dry before using the stove or cracking is likely to
occur
Combustible Materials
Please view the product sheet which accompanied your stove for specific
minimum distances to combustible measurements. Ideally, adjacent walls should
be of suitable noncombustible construction, preferably brickwork. In large
fireplaces take care that any supporting beam is protected by a 13mm sheet of
heat resistant fire board spaced 12mm off the surface with strips of
noncombustible material. Make sure that there is a gap between an un-insulated
flue system and any combustible material. This gap must be at least 3X the
outside diameter of the flue pipe, or 1.5X the flue diameter to non-
combustible surfaces. Please consult the flue manufacturers specification for
insulated flues.
Air for combustion
All stoves require ventilation to burn safely and correctly. There are a
number of requirements that need to be met when installing a stove, for
example, allowing for the permeability of the house (air permeability is the
general seepage of air into the house via air vents, doors and windows etc.)
There must always be a permanent means of providing air for combustion into
the room in which the stove is installed. Air starvation will result in poor
flue draw and may cause smoke to leak into the room. For all installations it
is recommended that a permanent vent with a total free area of at least 550mm
2 for every kW above 5kW should be connected directly to the outside air.
Installations in properties built after 2008 should have their vent increased
by a further 330mm 2 for each of the first 5kW. Alternatively this air can be
supplied through an external wall of an adjacent room, which itself has to be
connected to the room the appliance is installed by a permanent vent of the
same size. Note: If the appliance is fitted with a draught stabilizer (or if
one is fitted to the flue pipe or chimney in the same room as the appliance)
then the permanent air entry opening (or openings) should be increased by
300mm 2 for each kW of rated output up to 5kW and 2 an additional 850mm for
each kW output over 5kW. If there is more than one appliance in the property
then each appliance must be supplied with adequate combustion air so that all
appliances can be lit simultaneously. The positioning of any air vent must be
so that it cannot be liable to blockage or obstruction. Ideally it should also
be positioned where it is unlikely to cause a cold draught. It should not be
positioned in the fireplace recess. For more detailed guidelines on required
ventilation sizes please refer to the Document J Building Regulations
(Combustion Appliances) at the
www.planningportal.gov.uk website. If you
plan to use an external air supply on a suitable stove, and have bought the
appropriate Arada External Air Supply Kit, please refer to the instructions
included with the kit on how to install it. The accompanying stove technical
product sheet states whether or not your appliance is compatible with a Direct
Air Supply Kit.
Flues and Chimneys
The stove must be connected to a suitable and efficient flue so that products
of combustion (fumes) from the stove are expelled to the outside air. Please
remember that chimney draught is dependent on four main factors :
- Flue gas temperature
- Flue height
- Flue size
- Flue terminal
To ensure a good up draught it is important that the flue gases are kept warm
and that the flue size suits the stove. The termination of the outlet at the
top of the flue also needs to comply with Building Regulations. The minimum
effective height of the flue must be at least 4.5 meters from the top of the
stove to the top of the flue outlet. When warm the flue draught should be
between 0.1 to 0.2mb. The draw of a chimney / flue can vary in different
weather conditions and the customer should be made aware of this. Failure to
correct an over-drawing flue will invalidate the warranty.
A chimney may comply with regulations but could still be subject to down
draught and similar problems. A chimney terminating above the ridge level is
generally less likely to suffer such problems. If a new chimney is being
provided it should fully comply with the relevant Building Regulations that
specify the requirements for solid fuel burning installations. Suitable types
of chimney include the following :
- Masonry Chimney: Built with clay or concrete liners, or a chimney block system meeting Building Regulations. These types of chimneys should be installed in accordance with the Building Regulations and BS EN 15287-1:2007.
- Factory Made Insulated Chimney: Complying with BS 4543:Part 2 (often called Class 1 prefabricated metal chimney). These types of chimneys should be installed in accordance with Building Regulations and BS EN 15287-1:2007.
Due to the gradual introduction of European Chimney Standards chimneys will be
specified according to their performance designation as defined in BS EN 1443
that covers the General Requirements for chimneys. The minimum performance
designation required for use with solid fuel burning stoves is T450N2 S D3.
The flue and chimney installation must be carefully checked by a competent
person before fitting the stove to ensure it is suitable and will work safely.
If the chimney is old (i.e.: built of brick or stone without a liner) or being
opened up for reuse additional checks and smoke testing as described in
Appendix E of the Approved Document J 2010 Edition should also be carried out
to ensure the flue and chimney are in good operating condition.
Check the existing flue is in good condition with suitable access for
collection and removal of debris. It is also important that suitable flue pipe
with (recommended at least 600mm in length) complying with the Building
Regulations is used to connect the stove to the flue in the chimney. Suitable
access should be provided into the flue for regular inspection and sweeping of
the flue ways.
The installer should comply with Building Regulations requirements in respect
of providing a Notice Plate giving details on the chimney, flue lining, hearth
and fireplace installation.
Chimneys should be as straight as possible. Horizontal runs should be avoided
except where the rear outlet of the appliance is used, in which case the
horizontal section should not exceed 150mm in length. If necessary a
combination of 45° and 90° bends can be used as long as the sum of their
angles is not greater than 180° in total. i.e. four 45° bends, or two 45° and
a 90° bend.
If the stove appears to be working hard but produces very little output to the
room it is likely that excess draw is present in the chimney, and that heat is
being sucked out of the appliance and up the chimney. If this is the case we
recommend the fitting of a draught stabilizer in preference to a flue damper,
in the interest of safety and efficiency.
Installing the stove
To make the stove easier to maneuver (and safer) we recommend you remove the
following parts which canteen be refitted when the stove is in its final
position:
- Grate Bars
- Liners
- Door (To help prevent the glass from breaking)
- Operating Tool
- Ash pan
- Throat Plate
Removing the door
Open the door so that it is perpendicular to the stove body and then carefully
lift the stove door upwards off its hinges. To replace the door reverse the
instructions above.
Removing the throat plate and liners
The throat plate rests on liners and (in some models) a tertiary air bar. With
the fire door removed or open, push up on the throat plate with the palm of
one hand. With the other, remove the side liners and then lower the throat
plate forward. It is easier to lower one side of the throat plate first to
help remove it from its position and to allow it to fit through the opening of
the stove. Once the throat plate has been removed you can also remove the rear
liner(s). To replace the liners/throat plate follow the steps above in
reverse.
Assembling the grate bars
In a multi fuel stove the grate comprises of a series of cast iron grate bars,
seated on a pair of combs. All bars in the grate are identical.
In stoves with a riddling grate system the bars should be seated with every
other bar rotated 180 degrees, so the ends marked ’H’ and ’L’ alternate on
each comb. When assembling the grate, fit bars to the low sections of the comb
first by seating the ends marked ’L’ onto the low part of the comb, whilst
the ends marked ’H’ should then be seated on the high sections.
In stoves with non-riddling grate systems the grate is assembled with the ends
of the bars marked ’H’ sitting on the front comb, and the ends marked ’L’
sitting on the rear comb.
Fitting the spigot outlet to the stove
The flue outlet spigot and hot plate (blanking plate) can be found packed
inside the appliance and must be fitted during installation.
(Only applicable to freestanding appliances).
Smear a very thin layer of fire cement or use the supplied self adhesive rope
seal on the mating faces of the flue outlet and the hot plate. Fit the outlet
to the appliance in the desired position.
Inset models have a single flue outlet and no blanking plate.
Connecting the spigot outlet to the flue system
The flue pipe must be fitted inside the outlet spigot as shown in Figure 2.
Failure to do so could result in the spillage of condensation running down the
flue.
Fire cement should be used to create an airtight seal between the flue and
spigot.
Sealing of terminals
If an add in boiler is not to be fitted, please ensure that any partially cut
circular terminals (located on the rear of the appliance) are sealed with fire
cement, thus preventing surplus air entering the firebox, resulting in lower
efficiency and poor fuel consumption.
Inset stove Specific Instructions
All inset stoves, are designed to be fitted in a ‘builders opening’ and not a
chair brick. A suitable ‘builders opening’ will be required to facilitate
installation, observing the relevant building standards in regulation,
especially paying attention to the location and positioning of the lintel.
Inset stove flue connection
We strongly advise the connection of the inset stove onto a flexible flue
liner (System Flue).
The reasoning for this, is to ensure the stove operates correctly and at
maximum efficiency, maintaining a sound air tight seal for the flue connection
and thus preventing products of combustion being emitted to the dwelling.
Please note the importance, for any voids surrounding an inset stove, must be
filled with fire cement, vermiculite granules or mineral wool when installed
for the interest of safety and heat efficiency .
Adjusting the self-levelling feet (Cam style)
If applicable, adjustment is as follows:
- Position the stove on the hearth into its final resting place.
- On the rear leg of the stove, loosen the pozi screw, and rotate the inner ‘cam’ shaped levelling foot until this touches the hearth.
- Re-tighten the poi screw. Check the stove is level with a spirit level.
- Repeat for the other rear leg.
Adjusting the self-levelling feet (Levelling screw style)
If your stove model is factory fitted with the screw style, self levelling
feet, then please follow the procedure below. Please note, an adjuster is
fitted at each corner to allow the stove to be independently adjusted.
- Position the stove on the hearth into its final resting place.
- Using a 8mm open spanner, unscrew the levelling foot until this touches the hearth.
- Repeat for the remaining other corners.
- Using a spirit level adjust until the stove canopy is horizontal side to side and front to back.
Firebox liner panels / ‘liners’
Most Arada stoves use firebox liner panels to the sides and back. Some
Villager wood burners also have firebox liners in the base of the stove. For
detailed fitting instructions for Villager stoves please refer to
www.aradastoves.com/support.
Stoves which are being fitted with an add-in boiler should have the rear liner
removed to create the space in which the boiler is fitted.
For the majority of Arada stoves, the throat plate sits on top of the side and
rear panels. These should come fitted to your stove, if however they are not,
proceed as follows to fit them:
- Remove the fuel retainer.
- Set the small liner(s) into the back of the firebox.
- Insert the side liner panels.
- Fit the throat plate with the single bend and two cut outs to the front facing up. The projecting lugs sit on top of the side liners. The long centre tab on the back edge rests on the rear liners.
- Replace the fuel retainer.
Commissioning the stove
Before handing over the installation to the customer it is a requirement under Document J (of the Building Regulations for England and Wales) that the appliance is lit and the functioning of the chimney system is checked for satisfactory operation.
- Be sure that the chimney is operating and all smoke and fumes are vented to the atmosphere through the chimney terminal.
- Check all joints and seals.
- Clean the outside of the cold appliance with a lint free cloth or shoe brush to prevent any stains becoming burnt on.
- Check the flue draught which should read 10 – 20pa, or 0.1 – 0.2 mbar.
- Consult a suitably qualified person who will have the knowledge and equipment to perform a test.
For a registered Competent Persons scheme (such as those referred to at
www.gov.uk/building-regulationscompetent-person-schemes ), please complete a
Certificate of Compliance, which is used for checking and reporting the
installation as imposed by the Government.
Otherwise please ensure the installation is approved by your local building
control officer.
- Ensure a Carbon Monoxide alarm is fitted. This must be between 1m to 3m from the appliance, and approximately 150mm below the ceiling level.
- A fireguard conforming to BS 8423:2010 +A1:2016 should be used in the presence of children or infirm people.
A notice plate should be provided containing information on the performance characteristics of the hearth, fireplace, flue or chimney.
Explain the following to the customer:
- How to operate the riddling mechanism and air control lever.
- The importance of an adequate air supply to the room.
- The importance of regularly having the chimney swept / inspected.
- That a protective glove should be used when operating the stove.
- How changes in the weather can affect the performance of the stove.
- Using the correct fuels
- If burning wood, ensure that is well seasoned or has a moisture content of less than 20%.
NOTES
Arada Ltd, The Fireworks, Reycraft Avenue,
Axminister, Devon. EX13 5HU United Kingdom
Tel: +44(0)1297 632052 www.aradastoves.com
Dry Stove Installation Guide — BK545 Rev 14
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>