TERACOM TCW122B-CM Remote IO Module User Manual

June 13, 2024
TERACOM

TCW122B-CM Remote I/O module
Revision 4.8 / December 2022
USER MANUAL

Short description

TCW122B-CM is a remote IO module for monitoring and control. It has 2 digital and 2 analog inputs. The supported 1-Wire interface can handle up to 2 temperature or 2 humidity-temperature sensors.
The controller has 2 relays with normally open and normally closed contacts. Every relay can be activated either remotely (WEB, SNMP etc.) or locally – from the status of the monitored parameter (temperature, humidity, analog voltage and dry contact). Only one parameter can manage the relay at the same time, but for every parameter can be sent e-mail/SNMP trap for alert conditions.
TCW122B-CM is suitable for environmental monitoring and local control of heater/coolers, home and industrial and automation, data acquisition systems, general remote control, and monitoring.

Features

  • Password protected, web-based configuration and control;
  • 2 digital inputs with ” dry contact” and “logic level” modes;
  • 2 analog inputs with 0 to 60VDC range;
  • 2 relays with NO and NC contacts;
  • 1-Wire interface for up to 2 temperature (TST1XX) or humidity-temperature (TSH2xx) sensors;
  • SNMP v.1 support;
  • SNMP traps and/or e-mail sending for alert conditions;
  • SMTP with authentication (SSL/TLS is not supported);
  • HTTP and SNMP port changing;
  • HTTP and XML API commands;
  • Remote firmware update.

Specifications

  • Physical characteristics
    Dimensions: 109 x 82 x 32 mm
    Weight: 110 g

  • Environmental limits
    Operating тemperature range: -20 to 55°C
    Storage temperature range: -25 to 60°C
    Operating relative humidity range: 5 to 85% (non-condensing)

  • Warranty
    Warranty period: 3 years

  • Power supply
    Operating voltage range (including -15/+20% according to IEC 62368-1): 10 to 14 VDC
    Current consumption (with both relays ON): 0.2 A @ 12 VDC

  • Ethernet connectivity
    10 Mbit/s transfer rate
    Half-duplex mode only
    Auto-negotiation not supported

  • Digital inputs
    Isolation: Non-isolated
    Mode: Dry contact or Logic level
    Maximum input voltage: +5.5VDC
    Minimum input voltage for high logic level: +2.5VDC
    Maximum input voltage for low logic level: +0.8VDC
    Sampling rate: 10ms
    Digital filtering time interval: 30ms

  • Analog inputs
    Isolation: Non-isolated
    Type: Single-ended
    Resolution: 10 bits
    Mode: Voltage
    Input Range: 0 to 60 VDC
    Accuracy: ±1%
    Sampling Rate: 37.6ms per channel (averaged value of 64 samples)
    Input Impedance: 1 mega-ohm (min.)

  • Relay outputs
    Type: Form C (N.O. and N.C. contacts)
    Contact current rating: 3 A @ 24 VDC/30 VAC (resistive load)
    Initial insulation resistance: 100 mega-ohms (min.) @ 500 VDC
    Mechanical endurance: 10 000 000 operations
    Electrical endurance: 100 000 operations @ 3 A resistive load
    Contact resistance: 50 milli-ohm max. (initial value)
    Minimum pulse output: 1 Hz at rated load
    CAUTION: The device does not contain any internal overcurrent protection facilities on the relays’ contact lines.
    External fuses or short circuit current limiting circuit breakers, rated to 3 Amps, are to be used for overcurrent protection of the connecting lines.

  • 1-Wire interface
    Output voltage (+VW): 5.3 ± 0.2 VDC
    Maximum output current (+VW): 0.2 A

  • Internal FLASH memory
    Endurance: 100 000 cycles (Every relay status and settings change is a memory cycle.)

Powering

TCW122B-CM is designed to be supplied by adapter SYS1421-0612-W2E or similar, intended for use in the conditions of overvoltage category II, and priorly assessed for compliance with safety requirements. The power supply equipment shall be resistant to short circuit and overload in the secondary circuit.
When in use do not position the equipment so that it is difficult to disconnect the device from the power supply.

LED indicators

The following indicators show the status of the controller:

  • Relay1/Relay2 (green) – these LEDs are illuminated whenever the corresponding relay is activated (the NO contact is closed and the NC contact is open);
  • Sts (red) – flashes when the main program of the controller is executed;
  • Log (yellow) – indicates that somebody is logged via the WEB interface;
  • Net (green/red) – red when the device is linked, yellow when there is an activity.

Connectors

Inputs and outputs locations are shown below: Connector 1 – Power – 2.1×5.5mm connector, central positive
Connector 2, Pin1 – Digital input 1 (Din1)
Connector 2, Pin2 – Digital input 2 (Din2)

Connector 2, Pin3 – Ground
Connector 2, Pin4 – Analog input 1 (Ain1)
Connector 2, Pin5 – Analog input 2 (Ain2)
Connector 2, Pin6 – Ground
Connector 2, Pin7 – 1-Wire data
Connector 2, Pin8 – 1-Wire power supply
Connector 3 – Ethernet – RJ45
Connector 4, Pin1 – NC Relay1
Connector 4, Pin2 – COM Relay1
Connector 4, Pin3 – NO Relay1
Connector 5, Pin1 – NC Relay2
Connector 5, Pin1 – COM Relay2
Connector 5, Pin1 – NO Relay2

  • Operating mode is selected by jumper DI1/DI2 – closed for “dry contact” and open for “logic level”. By default, jumpers are closed.

Installation

This device must be installed by qualified personnel.
This device must not be installed directly outdoors.
The installation consists of mounting the device, connecting to an IP network, connecting inputs and outputs, providing power and configuring via a web browser.
TCW122B-CM can be wall or flat, not flammable surface mounted, in a clean and dry location room. Ventilation is recommended for installations where the ambient air temperature is expected to be high.
Mount the device to a wall by using two plastic dowels 8x60mm (example Würth GmbH 0912 802 002) and two dowel screws 6x70mm (example Würth GmbH 0157 06 70). Attach the screws to the surface vertically. See Appendix-A, fig. 1 for mechanical details.
Maintain spacing from adjacent equipment. Allow 50 mm of space on all sides, as shown in fig.2 in Appendix A, this provides ventilation and electrical isolation.

Configuration

Please follow the steps below for proper installation:

  1. Mount the controller in a dry and ventilated place.
  2. Connect the Ethernet port to a 10/100MB Ethernet network. For direct connection to a PC using a “crossover” cable.
  3. Connect the I/O pins of the controller according to the required application.
  4. Connect the power supply.

If the red LED (STS) blinks, the main program of the controller is executed. By default TCW122B-CM comes with the following network settings:
IP address: 192.168.1.2, Subnet Mask: 255.255.255.0, Default Gateway: 192.168.1.1
Communication with TCW122B-CM can be established by assigning a temporary IP address to the computer. This address should be on the same network (for example 192.168.1.3). To get access to the web interface, you should type http://192.168.1.2 into the browser.

If the network settings are correct, the “Login” page will appear.
The web-based interface allows configuration, monitoring, and control.
8.1. Login page
After opening the Login page, authorization data must be entered (by default username=admin, password=admin). It is recommended to change the username and password to prevent unauthorized access to the controller. The controller supports one active session – only one user can operate the device over the WEB interface. If another user tries to log in, the message “Someone is logged in” appears: The active session will stay open until the “Monitoring” page is open. Inactivity on other pages or closing the browser without logoff will terminate the session automatically in 4 minutes.
8.2. Monitoring page
After successful authorization, the “Monitoring” page appears: The “Monitoring” page provides information about the state of the relays and digital inputs, values of analog voltages (applied on analog inputs), temperature and humidity.
The state of the relay can be changed by appropriate “ON/OFF” button. To change the state of the relay for a specified time, the “Pulse” button should be pressed. Duration of the pulse is specified in “Pulse Duration” field of “I/O Setup” page.
Digital inputs can be used for monitoring the state of discrete devices – motion sensor, door contact, relay contact, alarm output etc. All digital inputs are not galvanic isolated. One side of the contact is connected to “Digital In” and another side is connected to “GND” pins. Digital inputs are sampled every 30ms. The change of input status is considered valid if the same value is read in seven consecutive samples.
8.3. Network Setup page
The Network parameters are set on this page. The following parameters can be changed:

  • IP configuration – IP Address can be static or dynamic (DHCP server should be present in the network);
  • IP address, Subnet mask, Default gateway – these fields are active if the IP address is static;
  • DNS – this field is mandatory if domain names are used instead of IP addresses. By default DNS has the same IP address as Default gateway;
  • Time Server and Time Zone – these fields are not mandatory, they are used when email must be sent;
  • Host Name – up to 16 symbols, it appears as a “Subject” in sent e-mails;
  • MAC – device MAC address.

The good practice is to change the default IP address of the controller immediately after first power-on. This will avoid collisions if many devices are used in the same network. It may be necessary to clear the arp cache, each time you connect a new device to the network. This is done by typing arp -d in the command prompt window of the computer. To use e-mail alerts following fields should be completed:

  • Mail server type – either “custom” or “tcwgateway”.
    “Custom” – public or private mail server without SSL should be used.
    Important! TCW122B-CM does not support Secure Socket Layer (SSL);
    “Tcwgateway” – dedicated mail server is used.
    Important! The service is free and not guaranteed.

  • Mail server [IP:port] – domain or IP address and port of SMTP mail server;

  • Sender E-mail – sender e-mail;

  • Username and Password – authentication details for mail server;

  • Recipient e-mail.

Username and password for WEB access to TCW122B-CM can be changed in the Web Access section. Setting the authentication to “disabled” will provide access to monitoring page without entering username and password. The HTTP port can be changed also in this section. XML/HTTP API section controls the access to XML file and HTTP commands. Detailed information can be found in the chapter “XML and HTTP API commands”. 8.4. SNMP Setup page
TCW122B-CM supports SNMP v.1. This enables the device to be part of large monitoring and control networks. The possible settings for “SNMP” section are:

  • SNMP Configuration – enable/disable SNMP;
  • SNMP Port – allows standard port changing;
  • Write/Read community – performs client authentication;
  • SNMP Traps – enable/disable SNMP trap messages;
  • IP address – IP address of the receiving host;
  • Community string – performs client authentication;
  • Trap Interval – time interval in seconds for SNMP trap messages;
  • Max. Traps number – the maximum number of SNMP trap messages sent if trap condition is present.

SNMP traps are sent if:

  • event occurs (status change) on Digital Input 1 or Digital Input 2;
  • measured voltage on Analog Input 1 or Analog Input 2 goes outside the range;
  • measured temperature goes outside the range;
  • measured humidity goes outside the range;
  • restart condition.

8.5. I/O setup page
I/O settings can be made here. For temperature, humidity and analog value MIN, MAX, and HYSTERESIS values can be set. These values define the thresholds for all monitored parameters. When the measured value goes out of range SNMP trap or e-mail (if enabled) will be sent.
Leaving range is considered when the parameter goes lower than MIN values or higher than MAX. Coming back in the range is considered when the parameter goes higher than (MIN + HYSTERESIS) or lower than (MAX – HYSTERESIS). Example:
TCW122B-CM, TST100, and appropriate heater are used to control the room temperature. The wanted minimum temperature is 19°C. The initial temperature is 17°C.
TST100 is assigned to the first position for 1-Wire sensors.
For Relay1 local activation from Sensor1 is set. Following parameters are set for Sensor1: Min=19, Max=100 and Hys=0.5.
When the controller is switched on, Relay1 is immediately activated because the monitored temperature is out of range. This switches the heater on. The temperature is going higher.
When temperature reaches 19.5°C (19.0 + 0.5) it goes in range (trigger condition) and Relay1 is deactivated. The heater is switched off.
The temperature falls and when it reached 19°C it goes out of range (trigger and alert conditions). The relay is activated (heater is switched on) and e-mail is sent. For digital inputs, conditional email sending can be arranged by following part of the page: Relays can be activated automatically depends on the value of the monitored parameter (humidity, temperature, analog voltage and changes on digital inputs) or manually. Only one parameter can be assigned for relay activation, at the same time: When manual activation is selected, “Pulse” and “ON/OFF” buttons on “Monitoring” page are active. The duration of the pulse for relay activation can be set from 1 to 253 seconds.
By default, relay state changes via the WEB interface are memorized in non- volatile memory.
After the power on, the relay goes in its last state, before the power down.
If the “Save relay state after change via WEB” is No, after power on the relay is always OFF.
By default, relay state changes via the HTTP API aren’t saved and after power on the relay is always OFF.
The guaranteed write cycles (every change saving doesn’t matter via HTTP API or WEB) are 100000.
For every sensor, analog input, digital input and relay description with a length of 11 characters can be set. Temperature units can be changed between Fahrenheit and Celsius. Automatic monitoring page refresh interval can be set from 1 to 253 second. 8.6. Update page
For details see chapter 13. Firmware update.

Application examples

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Teracom Ltd.
cannot assume responsibility or liability for actual use based on the examples and diagrams.
9.1. Temperature and humidity control
TCW122B-CM supports 1-Wire temperature and humidity sensors, which makes it suitable for use in heating and cooling systems.

9.2. Remote control
The controlled device is connected in series with the relay contacts. Users can operate TCW122B-CM using a web browser or SNMP application. Both relays are managed independently.

9.3. Remote monitoring
A relay contact of the monitored device is connected to the digital input. When an event occurs – the controller can send an e-mail and/or SNMP trap.

9.4. Data acquisition
The TCW122B-CM can be used in Data Acquisition Systems (DAQ). The device uses SNMP v.1 protocol for communication with monitoring and management software applications.

10. 1-Wire Bus
1-Wire is a registered trademark of Maxim Integrated Products, Inc. It is designed to connect several sensors over a short wiring. The bus carries power and a single data wire. It is not suitable for long distances or environments with EMC interference.
We strongly recommend reading Maxim’s 1-Wire tips at https://www.teracomsystems.com/wpcontent/uploads/1-wire/guidelines-for- reliable-long-line-1-wire-networks.pdf.
The total wiring length should be up to 30m, although functionality has been achieved in the longer distance. We cannot guarantee error-free operation over mentioned wiring length.
We guarantee proper operation only with our 1-Wire sensors series TST1XX and TSH2XX.

Control and monitoring using SNMP

TCW122B-CM can be configured and monitored through SNMP (Simple Network Management Protocol). This could be done using every SNMP v.1 compatible program. Parameters that can be changed, are grouped according to their functions in the tables below. To obtain a valid OID number it is necessary to replace the “x” symbol with ”1.3.6.1.4.1.38783”. To save the changes configurationSaved (OID x.3.13.0) should be set to “1”.

11.1. Product

OID Name Access Description Syntax
x.1.1.0 name read-only Device name String
x.1.2.0 version read-only Firmware version String
x.1.3.0 date read-only Release date String

11.2. Setup - > network

OID Name Access Description Syntax
x.2.1.1.0 deviceIPAddress read-write Device IP address IpAddress
x.2.1.2.0 subnetMask read-write Subnet Mask IpAddress
x.2.1.3.0 gateway read-write Gateway IpAddress
x.2.1.4.0 deviceMACAddress read-write Device MAC Address OCTET STRING

(SIZE(6))
x.2.1.5.0| dhcpConfig| read-write| DHCP configuration ON/OFF| INTEGER { off(0), on(1) }
x.2.1.6.0| dns| read-write| Domain Name Server address| IpAddress
x.2.1.7.0| Hostname| read-write| Device hostname| String (SIZE (0..38))

11.3. SetupsnmpSetup

OID Name Access Description Syntax
x.2.4.1.0 snmpConfiguration read-write SNMP Configuration INTEGER

{disabled(0), enabled(1)}
x.2.4.2.0| trapEnabled| read-write| TRAP messages ENABLED/DISABLED| INTEGER {no(0), yes(1)}
x.2.4.3.0| trapReceiverIPAddress| read-write| TRAP receiver IP address| IpAddress
x.2.4.4.0| trapCommunity| read-write| TRAP community| String (SIZE (0..13))
x.2.4.5.0| trapInterval| read-write| TRAP messages interval| INTEGER (1..253)
x.2.4.6.0| maxNumberOfTraps| read-write| Maximum number SNMP traps| INTEGER (1..253)

11.4. Setup - > oneWireSensor1 -> temperature1

OID Name Access Description Syntax
x.2.5.1.1.0 temperature1Min read-write Temperature1 range (min. value)

INTEGER (-400..1250)
x.2.5.1.2.0| temperature1Max| read-write| Temperature1 range (max. value)| INTEGER (-400..1250)
x.2.5.1.3.0| temperature1Hyst| read-write| Hysteresis| INTEGER (0..1250)
x.2.5.1.4.0| temperature1Action| read-write| Temperature1 action| INTEGER { noAction(0), sendMail(1) }

11.5. Setup - > oneWireSensor1 -> humidity1

OID Name Access Description Syntax
x.2.5.2.1.0 humidity1Min read-write Humidity1 range (min. value) INTEGER

(0..1000)
x.2.5.2.2.0| humidity1Max| read-write| Humidity1 range (max. value)| INTEGER (0..1000)
x.2.5.2.3.0| humidity1Hyst| read-write| Hysteresis| INTEGER (0..1000)
x.2.5.2.4.0| humidity1Action| read-write| Temperature1 action| INTEGER { noAction(0), sendMail(1) }

11.6. Setup - > oneWireSensor2 -> temperature2

OID Name Access Description Syntax
x.2.6.1.1.0 temperature2Min read-write Temperature2 range (min. value)

INTEGER (-400..1250)
x.2.6.1.2.0| temperature2Max| read-write| Temperature2 range (max. value)| INTEGER (-400..1250)
x.2.6.1.3.0| temperature2Hyst| read-write| Hysteresis| INTEGER (0..1250)
x.2.6.1.4.0| temperature2Action| read-write| Temperature2 action| INTEGER { noAction(0), sendMail(1) }

11.7. Setup - > oneWireSensor2 -> humidity2

OID Name Access Description Syntax
x.2.6.2.1.0 humidity2Min read-write Humidity2 range (min. value) INTEGER

(0..1000)
x.2.6.2.2.0| humidity2Max| read-write| Humidity2 range (max. value)| INTEGER (0..1000)
x.2.6.2.3.0| humidity2Hyst| read-write| Hysteresis| INTEGER (0..1000)
x.2.6.2.4.0| humidity2Action| read-write| Temperature2 action| INTEGER { noAction(0), sendMail(1) }

11.8. Setup - > analogInput -> input1

OID Name Access Description Syntax
x.2.7.1.1.0 voltage1Min read-write Voltage1 alarm range (min. value)

INTEGER (0..1000)
x.2.7.1.2.0| voltage1Max| read-write| Voltage1 alarm range (max. value)| INTEGER (0..1000)
x.2.7.1.3.0| voltage1Hyst| read-write| Voltage1 hysteresis| INTEGER (0..1000)
x.2.7.1.4.0| voltage1Action| read-write| Voltage1 action| INTEGER { noAction(0), sendMail(1) }
x.2.7.1.5.0| voltage1Description| read-write| Voltage 1 description| DisplayString (SIZE (0..11))

11.9. Setup - > analogInput -> input2

OID Name Access Description Syntax
x.2.7.2.1.0 voltage2Min read-write Voltage2 alarm range (min. value)

INTEGER (0..1000)
x.2.7.2.2.0| voltage2Max| read-write| Voltage2 alarm range (max. value)| INTEGER (0..1000)
x.2.7.2.3.0| voltage2Hyst| read-write| Voltage2 hysteresis| INTEGER (0..1000)
x.2.7.2.4.0| voltage2Action| read-write| Voltage2 action| INTEGER { noAction(0), sendMail(1) }
x.2.7.2.5.0| voltage2Description| read-write| Voltage 2 description| DisplayString (SIZE (0..11))

11.10. Setup - > digitalinput

OID Name Access Description Syntax
x.2.8.1.0 digitalinput1Action read-write Digital Input1 action INTEGER

{noAction(0), mailIfOpenToClosed(1),
mailIf Closed To Open(2) }
x.2.8.2.0| digitalinput2Action| read-write| Digital Input2 action| INTEGER {no Action(0), mailIf Open To Closed (1), mailIf Closed To Open (2)}
x.2.8.3.0| digitalInput1Description| read-write| Digital Input 1 description| DisplayString (SIZE (0..11))
x.2.8.4.0| digitalInput2Description| read-write| Digital Input 2 description| DisplayString (SIZE (0..11))

11.11. Setup - > relay

OID Name Access Description Syntax
x.2.9.1.0 relay1ControlledBy read-write Relay1 control item INTEGER {

manual(0), temperature1(1), humidity1(2), analogInput1(3), digitalInput1(4), temperature2(5), humidity(6), analogInput2(7), digitalInput2(8) }
x.2.9.2.0| relay2ControlledBy| read-write| Relay2 control item| INTEGER { manual(0), temperature1(1), humidity1(2), analogInput1(3), digitalInput1(4), temperature2(5), humidity(6), analogInput2(7), digitalInput2(8) }
x.2.9.3.0| relayPulseWidth| read-write| Digital Inputs mail recipient| INTEGER{ 1..253 }
x.2.9.4.0| relay1Description| read-write| Relay 1 description| DisplayString (SIZE (0..11))
x.2.9.4.0| relay2Description| read-write| Relay 2 description| DisplayString (SIZE (0..11))

11.12. Setup - > recipients

OID Name Access Description Syntax
x.2.10.1.0 recipient1EmailAddress read-write Recipient1 e-mail String

(SIZE (0..38))

11.13. Monitor &control

OID Name Access Description Syntax
x.3.1.0 digitalInput1State read-only Digital Input1 state INTEGER {closed

(0), open(1)}
x.3.2.0| digitalInput2State| read-only| Digital Input2 state| INTEGER {closed (0), open(1)}
x.3.3.0| relay1State| read-write| Relay1 state| INTEGER {off (0), on(1)}
x.3.4.0| relay1Pulse| read-write| Relay1 pulse| INTEGER {off (0), on(1)}
x.3.5.0| relay2State| read-write| Relay2 state| INTEGER {off (0), on(1)}
x.3.6.0| relay2Pulse| read-write| Relay2 pulse| INTEGER {off (0), on(1)}
x.3.7.0| voltage1x10Int| read-only| Voltage1 x10 in integer format| INTEGER {0..1000}
x.3.8.0| voltage2x10Int| read-only| Voltage2 x10 in integer format| INTEGER {0..1000 }
x.3.9.0| temp1x10Int| read-only| Temperature1 x10 in integer format| INTEGER{-400..1250}
x.3.10.0| temp2x10Int| read-only| Temperature2 x10 in integer format| INTEGER {-400..1250}
x.3.11.0| humi1x10Int| read-only| Humidity1 x10 in integer format| INTEGER {0..1000}
x.3.12.0| humi2x10Int| read-only| Humidity2 x10 in integer format| INTEGER {0..1000}
x.3.13.0| configurationSaved| read-write| Configuration save status| INTEGER {unsaved(0), saved(1)}
x.3.14.0| restartDevice| read-write| Restart device| INTEGER {cancel(0), restart(1)}

XML and HTTP API commands

XML is often preferred choice when it comes to M2M communication and system integration. The monitored values are transmitted in status.xml file that can be easily processed by software applications.
The structure of the status.xml file is:

TCW122B-CM 5C:32:C5:AA:00:05 TCW122B-CM 3.10 Digital 1 CLOSED 0 Digital 2 CLOSED 0 Analog 1 12.2V 0 Analog 2 23.8V 0 Sensor 1 22.4°C 0 41.8%RH 0 Sensor 2 0 0 Relay 1 OFF Relay 2 OFF 5 If XML/HTTP API authentication is enabled, basic access authentication is required to access the status.xml file. The format of the command is shown in the table below:
XML/HTTP API authentication Format
enabled [http://device.ip.address/status.xml _?a= uuuu :

pppp_](http://device.ip.address/status.xml?a=uuuu:pppp)
disabled| http://device.ip.address/status.xml

Where uuuu is username and pppp is password. Both parameters are unencrypted.
The following HTTP commands are supported:

Command Description
http://device.ip.address/status.xml?r1=1 Turn Relay 1 ON
http://device.ip.address/status.xml?r1=0 Turn Relay 1 OFF
http://device.ip.address/status.xml?r2=1 Turn Relay 2 ON
http://device.ip.address/status.xml?r2=0 Turn Relay 2 OFF
http://device.ip.address/status.xml?tg1=1 Toggle Relay 1 state
http://device.ip.address/status.xml?pl1=1 Pulse Relay 1
http://device.ip.address/status.xml?r1=1&r2=1

Turn both relays ON
http://device.ip.address/status.xml?r1=0&r2=0| Turn both relays OFF

If XML/HTTP API authentication is enabled, basic access authentication is required to send HTTP commands. The format of the commands is shown in the table below (user name=admin, pass=admin):

XML/HTTP API authentication Format
enabled

http://device.ip.address/status.xml?a=admin:admin&r1=1
disabled| http://device.ip.address/status.xml?r1=1

Firmware update

TCW122B-CM supports remote firmware update. To update the device follow the steps below:

  • Go to www.teracomsystems.com and download the latest firmware version from TCW122B-CM product page;
  • Go to the login page, enter a username, and password and press the “Login” button;
  • Go to the “Update” menu, select the update .cod file and press “upload” button;
  • After the firmware update is completed, you will be forwarded to the device Login page.

Attention! Don’t turn off the power supply during the update. Turning off the power supply will damage the device.
For some updates factory default settings procedure is mandatory.

Factory default settings

TCW122B-CM can be restored to its original factory default settings, following the steps below:

  • Turn off the power supply;
  • Press and hold the RESET button then turn on the power supply;
  • After turning the power supply release the RESET button. The LED’s STS and LOG will flash 14 times after that only the STS LED will continue to blink. The controller is restored to its default settings.

The factory default settings are:

User Name (Admin) admin
Password (Admin) admin
IP Address 192.168.1.2
Subnet Mask 255.255.255.0
Default Gateway 192.168.1.1
SNMPConfiguration disabled
readCommunity public
writeCommunity private

Environment information

This equipment is intended for use in a Pollution Degree 2 environment, at altitudes up to 2000 meters. When the controller is a part of a system, the other elements of the system shall comply with the EMC requirements and shall be intended for use in the same ambient conditions.

Safety

This device must not be used for medical, life-saving purposes or for any purpose where its failure could cause serious injury or the loss of life.
To reduce the risk of fire, only flexible stranded wire, with cross-section 0.5mm² or larger for wiring of digital and analog inputs and relay output of the device should be used.
To avoid electric shock and fire hazard, do not expose this product to liquids, rain, or moisture.
Objects filled with liquids, such as vases, should not be placed on this device.
There is a risk of overheating (damage) of the controller if recommended free spaces to adjacent devices are not ensured. A joint part with external component shall have space for attachment/removal of the cable after installation.
Teracom does not guarantee a successful operation of the product if the product was used under conditions deviating from the product specifications.
To ensure that the device works correctly follow the steps below:

  • ensure that the device is installed correctly, refer this user manual;
  • log into the devices via a browser;
  • make proper setup;
  • set up the digital inputs to work in “dry contact” mode;
  • short the “Din1” and “GND”;
  • install sensor TSH1XX or TST1XX on the 1-Wire bus;
  • go to “Monitoring page” of WEB interface – proper parameters value should be displayed at the same time flashing “STS” led should indicate the proper operation.

If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Teracom Ltd. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

Maintenance

Upon completion of any service or repairs to the device or once per year, a safety check must be performed to determine that this product is in proper operating condition. Clean the device only with a dry cloth. Do not use a liquid cleaner or an aerosol cleaner. Do not use a magnetic/static cleaning device (dust remover) or any kind of abrasive materials to clean the device.

Appendix A

TCW122B-CM_R4.8 – December 2022

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

TERACOM User Manuals

Related Manuals