TCW122B-WD
IP watchdog monitoring module
Revision 4.8 / December 2022
USER MANUAL
www.teracomsystems.com
Short description
TCW122B-WD is an IP watchdog monitoring module, based on TCW122 hardware. It
has 2 digital and 2 analog inputs. It supports up to two temperature/humidity
sensors on its 1-Wire interface.
The IP watchdog controller has also two relays with normally open and normally
closed contacts.
TCW122B-WD is dedicated to IP watchdog monitoring as a stand-alone device.
The controller supports also SNMP v1 as M2M protocol. It can also be used as a
part of small to medium SCADA systems for environmental monitoring of server
rooms.
Features
- Password protected, web-based configuration and control;
- 2 digital inputs with ” dry contact” and “logic level” modes;
- 2 analog inputs with 0 to 60VDC range;
- 2 relays with NO and NC contacts;
- 1-Wire interface for up to 2 temperature (TST1XX) or temperature/humidity (TSH2xx) sensors;
- SNMP v.1 support, SNMP trap alerts;
- SNMP traps for alert conditions;
- HTTP and SNMP port changing;
- VLAN, MAC address filtering;
- ICMP watchdog monitoring;
- Remote firmware update.
Specifications
-
Physical characteristics
Dimensions: 109 x 82 x 32 mm
Weight: 110 g -
Environmental limits
Operating тemperature range: -20 to 55°C
Storage temperature range: -25 to 60°C
Operating relative humidity range: 5 to 85% (non-condensing) -
Warranty
Warranty period: 3 years -
Power supply
Operating voltage range (including -15/+20% according to IEC 62368-1): 10 to 14 VDC
Current consumption (with both relays ON): 0.2 A @ 12 VDC -
Ethernet connectivity
10 Mbit/s transfer rate
Half-duplex mode only
Auto-negotiation not supported -
Digital inputs
Isolation: Non-isolated
Mode: Dry contact or Logic level
Maximum input voltage: +5.5VDC
Minimum input voltage for high logic level: +2.5VDC
Maximum input voltage for low logic level: +0.8VDC
Sampling rate: 10ms
Digital filtering time interval: 30ms -
Analog inputs
Isolation: Non-isolated
Type: Single-ended
Resolution: 10 bits
Mode: Voltage
Input Range: 0 to 60 VDC
Accuracy: ±1%
Sampling Rate: 37.6ms per channel (averaged value of 64 samples)
Input Impedance: 1 mega-ohm (min.) -
Relay outputs
Type: Form C (N.O. and N.C. contacts)
Contact current rating: 3 A @ 24 VDC/30 VAC (resistive load)
Initial insulation resistance: 100 mega-ohms (min.) @ 500 VDC
Mechanical endurance: 10 000 000 operations
Electrical endurance: 100 000 operations @ 3 A resistive load
Contact resistance: 50 milli-ohm max. (initial value)
Minimum pulse output: 1 Hz at rated load
CAUTION: The device does not contain any internal overcurrent protection facilities on the relays’ contact lines.
External fuses or short circuit current limiting circuit breakers, rated to 3 Amps, are to be used for overcurrent protection of the connecting lines. -
1-Wire interface
Output voltage (+VW): 5.3 ± 0.2 VDC
Maximum output current (+VW): 0.2 A -
Internal FLASH memory
Endurance: 100 000 cycles (Every relay status and settings change is a memory cycle.)
Connectors
Inputs and outputs locations are shown below:
Connector 1 – Power – 2.1×5.5mm connector, central positive
Connector 2, Pin1 – Digital input 1 (Din1)
Connector 2, Pin2 – Digital input 2 (Din2)
Connector 2, Pin3 – Ground
Connector 2, Pin4 – Analog input 1 (Ain1)
Connector 2, Pin5 – Analog input 2 (Ain2)
Connector 2, Pin6 – Ground
Connector 2, Pin7 – 1-Wire data
Connector 2, Pin8 – 1-Wire power supply
Connector 3 – Ethernet – RJ45
Connector 4, Pin1 – NC Relay1
Connector 4, Pin2 – COM Relay1
Connector 4, Pin3 – NO Relay1
Connector 5, Pin1 – NC Relay2
Connector 5, Pin1 – COM Relay2
Connector 5, Pin1 – NO Relay2
- Operating mode is selected by jumper DI1/DI2 – closed for “dry contact” and open for “logic level”. By default, jumpers are closed.
LED indicators
The following indicators show the status of the controller:
- Relay1/Relay2 (green) – these LEDs are illuminated whenever the corresponding relay is activated (the NO contact is closed and the NC contact is open);
- Sts (red) – flashes when the main program of the controller is executed;
- Log (yellow) – indicates that somebody is logged via the WEB interface;
- Net (green/red) – red when the device is linked, yellow when there is an activity.
Powering
TCW122B-WD is designed to be supplied by adapter SYS1421-0612-W2E or similar,
intended for use in the conditions of overvoltage category II, and priorly
assessed for compliance with safety requirements. The power supply equipment
shall be resistant to short circuit and overload in the secondary circuit.
When in use do not position the equipment so that it is difficult to
disconnect the device from the power supply.
Installation
This device must be installed by qualified personnel.
This device must not be installed directly outdoors.
The installation consists of mounting the device, connecting to an IP network,
connecting inputs and outputs, providing power and configuring via a web
browser.
TCW122B-WD can be wall or flat, not flammable surface mounted, in a clean and
dry location room. Ventilation is recommended for installations where the
ambient air temperature is expected to be high.
Mount the device to a wall by using two plastic dowels 8x60mm (example Würth
GmbH 0912 802 002) and two dowel screws 6x70mm (example Würth GmbH 0157 06
70). Attach the screws to the surface vertically. See Appendix-A, fig. 1 for
mechanical details.
Maintain spacing from adjacent equipment. Allow 50 mm of space on all sides,
as shown in fig.2 in Appendix A, this provides ventilation and electrical
isolation.
Configuration
Please follow the steps below for proper installation:
- Mount the controller in a dry and ventilated place.
- Connect the Ethernet port to a 10/100MB Ethernet network. For direct connection to a PC using a “crossover” cable.
- Connect the I/O pins of the controller according to the required application.
- Connect the power supply.
If the red LED (STS) blinks, the main program of the controller is executed.
By default TCW122BWD comes with the following network settings:
IP address: 192.168.1.2, Subnet Mask: 255.255.255.0, Default Gateway:
192.168.1.1
Communication with TCW122B-WD can be established by assigning a temporary IP
address to the computer. This address should be on the same network (for
example 192.168.1.3). To get access to the web interface, you should type
http://192.168.1.2 into the browser.
If the network settings are correct, the “Login” page will appear.
The web-based interface allows configuration, monitoring, and control.
8.1. Login page
After opening the Login page, authorization data must be entered (by default
username = admin, password = admin). It is recommended to change the username
and password to prevent unauthorized access to the controller.
The controller supports one active session – only one user can operate the device. If another user tries to log in, the message “Someone’s logged in” appears:
The active session will stay open until the “Monitoring” page is open. Inactivity on other pages or closing the browser without logoff will terminate the session automatically in 4 minutes.
8.2. Monitoring page
After successful authorization, the “Monitoring” page appears:
The “Monitoring” page provides information about the state of the relays and
digital inputs, values of analog voltages (applied on analog inputs),
temperature and humidity.
The state of the relay can be changed by appropriate “ON/OFF” button. To
change the state of the relay for a specified time, “Pulse” button should be
pressed. Duration of the pulse is specified in “Pulse Duration” field of “I/O
Setup” page.
Digital inputs can be used for monitoring the state of discrete devices –
motion sensor, door contact, relay contact, alarm output etc. All digital
inputs are not galvanic isolated. One side of the contact is connected to
“Digital In” and another side is connected to “GND” pins.
Digital inputs are sampled every 30ms. The change of input status is
considered valid if the same value is read in seven consecutive samples.
8.3. Network Setup page
The Network parameters are set on this page. The following parameters can be
changed:
- IP configuration – IP Address can be static or dynamic (DHCP server should be present in the network);
- IP address, Subnet mask, Default gateway – these fields are active if the IP address is static;
- Host Name – up to 16 symbols
- MAC – device MAC address.
The good practice is to change the default IP address of the controller
immediately after first power-on. This will avoid collisions if many devices
are used on the same network. It may be necessary to clear the arp cache, each
time you connect a new device to the network. This is done by typing “arp –d”
in the command prompt window of the computer.
VLAN and MAC address filtering are supported. Up to 3 MAC addresses (including
Default Gateway) can be active in MAC filtering.
Attention! If you are not familiar with VLAN and MAC filtering, leave these
sections by default.
Username and password for WEB access to TCW122B-WD can be changed in the Web Access section. Setting the authentication to “disabled” will provide access to monitoring page without entering username and password. The HTTP port can be changed also in this section.
8.4. SNMP Setup page
TCW122B-WD supports SNMP v.1. This enables the device to be part of large
monitoring and control networks. The possible settings for “SNMP” section are:
- SNMP Configuration – enable/disable SNMP;
- SNMP Port – allows standard port changing;
- Write/Read community – performs client authentication;
- SNMP Traps – enable/disable SNMP trap messages;
- IP address – IP address of the receiving host;
- Community string – performs client authentication;
- Trap Interval – time interval in seconds for SNMP trap messages;
- Max. Traps number – the maximum number of SNMP trap messages sent if trap condition is present.
SNMP traps are sent if:
- event occurs (status change) on Digital Input 1 or Digital Input 2;
- measured voltage on Analog Input 1 or Analog Input 2 goes outside the range;
- measured temperature goes outside the range;
- measured humidity goes outside the range;
- restart condition.
8.5. I/O setup page
I/O settings can be made here. For temperature, humidity and analog value MIN,
MAX, and HYSTERESIS values can be set. These values define the thresholds for
all monitored parameters.
When the measured value goes out of range SNMP trap (if enabled) will be sent. Leaving range is considered when the parameter goes lower than MIN values or higher than MAX. Coming back in the range is considered when the parameter goes higher than (MIN + HYSTERESIS) or lower than (MAX – HYSTERESIS).
For IP watchdog monitoring following parameters can be set:
- Mode – outgoing (echo request) or incoming (echo replay) mode can be chosen;
- IP address – IP address of ICMP corresponding host;
- Activation options – the relay activation options – Pulse OFF, Pulse ON, Permanent OFF, Permanent ON
- Outgoing ping interval – the time between two echo requests;
- Ping timeout for activation – timeout before activation of the relay;
- Maximum number of activations – the maximum number of activation of the relay (restarts) after the timeout has expired.
Ping timeout for activation should be longer than Outgoing ping interval.
Relays can be activated manually from the WEB interface or automatically in
function of the watchdog.
By default, relay state changes via the WEB interface are memorized in non-
volatile memory.
After the power on, the relay goes in its last state, before the power down.
If the “Save relay state after change via WEB” is No, after power on the relay
is always OFF.
The guaranteed write cycles (every change saving) are 100000.
When Web/SNMP activation is selected, “Pulse” and “ON/OFF” buttons on
“Monitoring” page are active. The duration of the pulse for relay activation
can be set from 1 to 253 seconds.
For every sensor, analog input, digital input and relay description with a
length of 11 characters can be set.
Temperature units can be changed between Fahrenheit and Celsius.
Automatic monitoring page refresh interval can be set from 1 to 253 second.
8.6. Update page
For details see chapter 12. Firmware update.
Application examples
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with any
particular installation, Teracom Ltd.
cannot assume responsibility or liability for actual use based on the examples
and diagrams.
9.1. Watchdog
TCW122B-WD is set to send a periodic ping to AP (Local network) and the remote
server (Internet). If there is no answer in “Ping timeout for restart”, the
corresponding relay is activated in order to reset particular network
equipment.
9.2. Dry contact monitoring
The monitored contacts are connected to digital inputs (Din1 and Din2) and
ground (GND).
Changes in the state of contacts can be monitored either by WEB or SNMP
interface. If SNMP traps are allowed and properly set, every change of state
will generate a trap to the server.
1-Wire Bus
1-Wire is a registered trademark of Maxim Integrated Products, Inc. It is
designed to connect several sensors over short wiring. The bus carries power
and a single data wire. It is not suitable for long distances or environments
with EMC interference.
We strongly recommend reading Maxim’s 1-Wire tips at
https://www.teracomsystems.com/wpcontent/uploads/1-wire/guidelines-for-
reliable-long-line-1-wire-networks.pdf.
The total wiring length should be up to 30m, although functionality has been
achieved in the longer distance. We cannot guarantee error-free operation over
mentioned wiring length.
We guarantee proper operation only with our 1-Wire sensors series TST1XX and
TSH2XX.
SNMP protocol
TCW122B-WD can be configured and monitored through SNMP (Simple Network
Management Protocol). This could be done using every SNMP v.1 compatible
program. Parameters that can be changed, are grouped according to their
functions in the tables below. To obtain a valid OID number it is necessary to
replace the “x” symbol with ”1.3.6.1.4.1.38783”.
To save the changes configurationSaved (OID x.3.13.0) should be set to “1”.
11.1 Product
OID | Name | Access | Description | Syntax |
---|---|---|---|---|
x.1.1.0 | name | read-only | Device name | String |
x.1.2.0 | version | read-only | Firmware version | String |
x.1.3.0 | date | read-only | Release date | String |
11.2 Setup - > network
OID | Name | Access | Description | Syntax |
---|---|---|---|---|
x.2.1.1.0 | deviceIPAddress | read-write | Device IP address | IpAddress |
x.2.1.2.0 | subnetMask | read-write | Subnet Mask | IpAddress |
x.2.1.3.0 | gateway | read-write | Gateway | IpAddress |
x.2.1.4.0 | deviceMACAddress | read-write | Device MAC Address | OCTET STRING |
(SIZE(6))
x.2.1.5.0| dhcpConfig| read-write| DHCP configuration ON/OFF| INTEGER {
off(0), on(1) }
x.2.1.6.0| dns| read-write| Domain Name Server address| IpAddress
x.2.1.7.0| hostName| read-write| Device Host name| String (SIZE (0..38))
11.3 Setup - > VLAN
OID | Name | Access | Description | Syntax |
---|---|---|---|---|
x.2.2.1.0 | vlanStatus | read-write | VLAN status ENABLED/DISABLED | INTEGER { |
disabled(0), enabled(1) }
x.2.2.2.0| vlanId| read-write| VLAN ID (0 – 4095)| INTEGER (0..4095)
11.4 Setup - > macFilter
OID | Name | Access | Description | Syntax |
---|---|---|---|---|
x.2.3.1.0 | filterMACAddress1 | read-only | MAC Filter 1 | OCTET STRING (SIZE(6)) |
x.2.3.2.0 | filterMACEnable1 | read-write | MAC Filter 1 ENABLED/DISABLED |
INTEGER { disabled(0), enabled(1) }
x.2.3.3.0| filterMACAddress2| read-write| MAC Filter 2| OCTET STRING (SIZE(6))
x.2.3.4.0| filterMACEnable2| read-write| MAC Filter 2 ENABLED/DISABLED|
INTEGER { disabled(0), enabled(1) }
x.2.3.5.0| filterMACAddress3| read-write| MAC Filter 3| OCTET STRING (SIZE(6))
x.2.3.6.0| filterMACEnable3| read-write| MAC Filter 3 ENABLED/DISABLED|
INTEGER { disabled(0), enabled(1) }
11.5 Setup - > SNMP
OID | Name | Access | Description | Syntax |
---|---|---|---|---|
x.2.4.1.0 | snmpConfiguration | read-write | SNMP Configuration | INTEGER { |
disabled(0), enabled(1) }
x.2.4.2.0| trapEnabled| read-write| TRAP messages ENABLED/DISABLED| INTEGER {
no(0), yes(1) }
x.2.4.3.0| trapReceiverIPAddress| read-write| TRAP receiver IP address|
IpAddress
x.2.4.4.0| trapCommunity| read-write| TRAP community| String (SIZE (0..13))
x.2.4.5.0| trapInterval| read-write| TRAP messages interval| INTEGER (1..253)
x.2.4.6.0| maxNumberOfTraps| read-write| Maximum number SNMP traps| INTEGER
(1..253)
11.6 Setup - > oneWireSensor1 -> temperature1
OID | Name | Access | Description | Syntax |
---|---|---|---|---|
x.2.5.1.1.0 | temperature1Min | read-write | Temperature1 range (min. value) |
INTEGER (-400..1250)
x.2.5.1.2.0| temperature1Max| read-write| Temperature1 range (max. value)|
INTEGER (-400..1250)
x.2.5.1.3.0| temperature1Hyst| read-write| Hysteresis| INTEGER (0..1250)
11.7 Setup - > oneWireSensor1 -> humidity1
OID | Name | Access | Description | Syntax |
---|---|---|---|---|
x.2.5.2.1.0 | humidity1Min | read-write | Humidity1 range (min. value) | INTEGER |
(0..1000)
x.2.5.2.2.0| humidity1Max| read-write| Humidity1 range (max. value)| INTEGER
(0..1000)
x.2.5.2.3.0| humidity1Hyst| read-write| Hysteresis| INTEGER (0..1000)
11.8 Setup - > oneWireSensor2 -> temperature2
OID | Name | Access | Description | Syntax |
---|---|---|---|---|
x.2.6.1.1.0 | temperature2Min | read-write | Temperature2 range (min. value) |
INTEGER (-400..1250)
x.2.6.1.2.0| temperature2Max| read-write| Temperature2 range (max. value)|
INTEGER (-400..1250)
x.2.6.1.3.0| temperature2Hyst| read-write| Hysteresis| INTEGER (0..1250)
11.9 Setup - > oneWireSensor2 -> humidity2
OID | Name | Access | Description | Syntax |
---|---|---|---|---|
x.2.6.2.1.0 | humidity2Min | read-write | Humidity2 range (min. value) | INTEGER |
(0..1000)
x.2.6.2.2.0| humidity2Max| read-write| Humidity2 range (max. value)| INTEGER
(0..1000)
x.2.6.2.3.0| humidity2Hyst| read-write| Hysteresis| INTEGER (0..1000)
11.10 Setup - > analogInput -> input1
OID | Name | Access | Description | Syntax |
---|---|---|---|---|
x.2.7.1.1.0 | voltage1Min | read-write | Voltage1 alarm range (min. value) |
INTEGER (0..1000)
x.2.7.1.2.0| voltage1Max| read-write| Voltage1 alarm range (max. value)|
INTEGER (0..1000)
x.2.7.1.3.0| voltage1Hyst| read-write| Voltage1 hysteresis| INTEGER (0..1000)
11.11 Setup - > analogInput -> input2
OID | Name | Access | Description | Syntax |
---|---|---|---|---|
x.2.7.2.1.0 | voltage2Min | read-write | Voltage2 alarm range (min. value) |
INTEGER (0..1000)
x.2.7.2.2.0| voltage2Max| read-write| Voltage2 alarm range (max. value)|
INTEGER (0..1000)
x.2.7.2.3.0| voltage2Hyst| read-write| Voltage2 hysteresis| INTEGER (0..1000)
11.12 Setup - > relay
OID | Name | Access | Description | Syntax |
---|---|---|---|---|
x.2.9.1.0 | relay1ControlledBy | read-write | Relay1 control item | INTEGER { |
manual(0), watchdog1(1),
watchdog2(2) }
x.2.9.2.0| relay2ControlledBy| read-write| Relay2 control item| NTEGER {
manual(0), watchdog1(1),
watchdog2(2) }
x.2.9.3.0| relayPulseWidth| read-write| Relay Pulse Width| INTEGER{ 1..253 }
11.13 Setup - > watchdog1
OID | Name | Access | Description | Syntax |
---|---|---|---|---|
x.2.10.1.0 | wdg1Mode | read-write | Watchdog 1 Mode – Incomming or | |
Outgoing Ping | INTEGER { disabled(0), |
incomingPing(1), outgoingPing(2) }
x. 2.10.2.0| wdg1OutgoingPingInterval| read-write| Watchdog 1 Outgoing Ping
Interval| INTEGER { 1..253 }
x. 2.10.3.0| wdg1PingTimeOutForRestart| read-write| Watchdog 1 Ping Time out
for restart| INTEGER {2..65000}
x. 2.10.4.0| wdg1PingIPAddress| read-write| Watchdog 1 Ping IP address|
IpAddress
x.2.10.5.0| wdg1NumberOfRestarts| read-write| Watchdog 1 Max Number of
restarts| INTEGER (1..253)
11.14 Setup - > watchdog2
OID | Name | Access | Description | Syntax |
---|---|---|---|---|
x.2.11.1.0 | wdg2Mode | read-write | Watchdog 2 Mode – Incomming or | |
Outgoing Ping | INTEGER { disabled(0), |
incomingPing(1), outgoingPing(2) }
x. 2.11.2.0| wdg2OutgoingPingInterval| read-write| Watchdog 2 Outgoing Ping
Interval| INTEGER { 1..253 }
x. 2.11.3.0| wdg2PingTimeOutForRestart| read-write| Watchdog 2 Ping Time out
for restart| INTEGER {2..65000}
x. 2.11.4.0| wdg2PingIPAddress| read-write| Watchdog 2 Ping IP address|
IpAddress
x.2.11.5.0| wdg2NumberOfRestarts| read-write| Watchdog 2 Max Number of
restarts| INTEGER (1..253)
11.15 Monitor and control
OID | Name | Access | Description | Syntax |
---|---|---|---|---|
x.3.1.0 | digitalInput1State | read-only | Digital Input1 state | INTEGER { |
closed(0), open(1) }
x.3.2.0| digitalInput2State| read-only| Digital Input2 state| INTEGER {
closed(0), open(1) }
x.3.3.0| relay1State| read-write| Relay1 state| INTEGER { off(0), on(1) }
x.3.4.0| relay1Pulse| read-write| Relay1 pulse| INTEGER { off(0), on(1) }
x.3.5.0| relay2State| read-write| Relay2 state| INTEGER { off(0), on(1) }
x.3.6.0| relay2Pulse| read-write| Relay2 pulse| INTEGER { off(0), on(1) }
x.3.7.0| voltage1x10Int| read-only| Voltage1 x10 in integer format| INTEGER{
0..1000 }
x.3.8.0| voltage2x10Int| read-only| Voltage2 x10 in integer format| INTEGER{
0..1000 }
x.3.9.0| temp1x10Int| read-only| Temperature1 x10 in integer format| INTEGER{
-400..1250 }
x.3.10.0| temp2x10Int| read-only| Temperature2 x10 in integer format| INTEGER{
-400..1250 }
x.3.11.0| humi1x10Int| read-only| Humidity1 x10 in integer format| INTEGER{
0..1000 }
x.3.12.0| humi2x10Int| read-only| Humidity2 x10 in integer format| INTEGER{
0..1000 }
x.3.13.0| configurationSaved| read-write| Configuration save status| INTEGER {
unsaved(0), saved(1) }
x.3.14.0| restartDevice| read-write| Restart device| INTEGER { cancel(0),
restart(1) }
x.3.15.0| temperatureUnits| read-write| Temperature Units| INTEGER {
celsius(0), fahrenheit(1) }
Firmware update
TCW122B-WD supports remote firmware update. To update the device follow the steps below:
-
Go to www.teracomsystems.com and download the latest firmware version file from
TCW122B-WD product page; -
Go to the device Login page, enter a username, and password and press the “Login” button;
-
Go to the “Update” menu, select the update .cod file and press “upload” button;
-
After the firmware update is completed, you will be forwarded to the device Login page.
Attention! Don’t turn off the power supply during the update. Turning off
the power supply will damage the device.
For some updates factory default settings procedure is mandatory.
Factory default settings
TCW122B-WD can be restored to its original factory default settings, following the steps below:
- Turn off the power supply;
- Press and hold the RESET button then turn on the power supply;
- After turning the power supply release the RESET button. The LED’s STS and LOG will flash 14 times after that only the STS LED will continue to blink. The controller is restored to its default settings.
The factory default settings are:
User Name (Admin) | admin |
---|---|
Password (Admin) | admin |
IP Address | 192.168.1.2 |
Subnet Mask | 255.255.255.0 |
Default Gateway | 192.168.1.1 |
SNMPConfiguration | disabled |
readCommunity | public |
writeCommunity | private |
Environment information
This equipment is intended for use in a Pollution Degree 2 environment, at altitudes up to 2000 meters. When the controller is a part of a system, the other elements of the system shall comply with the EMC requirements and shall be intended for use in the same ambient conditions.
Safety
This device must not be used for medical, life-saving purposes or for any
purpose where its failure could cause serious injury or the loss of life.
To reduce the risk of fire, only flexible stranded wire, with cross-section
0.5mm² or larger for wiring of digital and analog inputs and relay output of
the device should be used.
To avoid electric shock and fire hazard, do not expose this product to
liquids, rain, or moisture.
Objects filled with liquids, such as vases, should not be placed on this
device.
There is a risk of overheating (damage) of the controller if recommended free
spaces to adjacent devices are not ensured. A joint part with external
component shall have space for attachment/removal of the cable after
installation.
Teracom does not guarantee a successful operation of the product if the
product was used under conditions deviating from the product specifications.
To ensure that the device works correctly follow the steps below:
- ensure that the device is installed correctly, refer this user manual;
- log into the devices via a browser;
- make proper setup;
- set up the digital inputs to work in “dry contact” mode;
- short the “Din1” and “GND”;
- install sensor TSH1XX or TST1XX on the 1-Wire bus;
- go to “Monitoring page” of WEB interface – proper parameters value should be displayed at the same time flashing “STS” led should indicate the proper operation.
If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
In no event will Teracom Ltd. be responsible or liable for indirect or
consequential damages resulting from the use or application of this equipment.
Maintenance
Upon completion of any service or repairs to the device or once per year, a safety check must be performed to determine that this product is in proper operating condition. Clean the device only with a dry cloth. Do not use a liquid cleaner or an aerosol cleaner. Do not use a magnetic/static cleaning device (dust remover) or any kind of abrasive materials to clean the device.
Appendix A
Fig.1 Fig.2
TCW122B-WD_R4.8 – December 2022
Documents / Resources
|
TERACOM 924TCW122B-WD IP Watchdog Monitoring
Module
[pdf] User Manual
924TCW122B-WD IP Watchdog Monitoring Module, 924TCW122B-WD, IP Watchdog
Monitoring Module, Watchdog Monitoring Module, Monitoring Module
---|---
References
- Remote monitoring and control solution for your automation challenges
- Remote monitoring and control solution for your automation challenges
- Remote monitoring and control solution for your automation challenges
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>