elvaco CMe2100 LTE CM-Bus Metering Gateway For Mobile Network Instruction Manual

June 13, 2024
elvaco

elvaco CMe2100 LTE CM-Bus Metering Gateway For Mobile Network

elvaco CMe2100 LTE CM-Bus Metering Gateway For Mobile
Network

INTRODUCTION

CMe2100 LTE is a flexible and cost-effective DIN-mounted M-Bus Metering Gateway for Mobile Network. It is compatible with all meters following the M-Bus standard. For a complete description of the product, visit the Elvaco AB website, www.elvaco.com.

OVERVIEW

Overview

  1. Serial number
  2. Push button
  3. M-Bus connector
  4. Antenna SMA connector
  5. IR interface
  6. Status LED (green)
  7. Error LED (red)
  8. Network LED (yellow)
  9. Blue LED (not used)
  10. SIM card holder
  11. USB slave connector
  12. USB master connector
  13. Power supply L
  14. Power supply N

MOUNTING

The CMe2100 LTE should be mounted on a DIN-rail. The plastic clip on the bottom is used to mount and demount the unit from the DIN-rail. For safety reasons, a DIN-rail enclosure must cover the terminals.

SIM CARD

Install the SIM card into the SIM card holder (10). Remember the phone number for later use.

IMPORTANT

  • The SIM card shall not have any PIN code activated.
  • The SIM card must have 2G/3G/LTE internet access activated for full functionality.
  • If a prepaid SIM card is used, ensure that enough credits are available.

POWER SUPPLY

The installation should be performed by a qualified electrician or installer with required knowledge. The power supply should be connected via a clearly marked, easily accessible and close switch so the unit can be switched off during service work. The main supply should be connected to screw terminal (13) and (14). Main supply voltage should be in the range of 100-240 VAC, 50/60 Hz.

M-BUS 2-WIRE BUS

M-Bus is a multi-drop 2-wire bus with no polarity. Use a cable of area 0.25-1.5 mm2 , e.g. a standard telephone cable (EKKX 2x2x0.5). Connect the wiring to the connector (3). Do not exceed the maximum cable length of 1000 m.

IMPORTANT

The product handles up to 256 meters. Use an M-Bus extender for installations with more meters than the product limit. All connected M-Bus slaves must have unique primary or secondary M-Bus addresses depending on addressing mode.

ANTENNA

An external antenna is needed for CMe2100 LTE, this is ordered separately. Please visit www.elvaco.com to find a suitable antenna option.

The antenna should be connected to the SMA connector (4). If the unit is mounted in a metal cabinet, the external antenna should be mounted outside the metal cabinet.

IMPORTANT

  • CMe2100 LTE should be connected to the antenna when the antenna wiring is done. Otherwise the SMA connector can be damaged.
  • Do not mount the antenna close to the M-Bus 2-wire bus.
  • Do not mount the antenna inside a metallic cabinet.

INSTALLATION/SEND SMS COMMAND

CMe2100 LTE is configured with SMS commands. Send any command from the table below in a text message to the phone number of the product.

Function SMS command
New installation of meter install n [profile]
Change of meter install n [profile] clean
Add meter on the bus install n [profile] keep
Signal strength/is the terminal alive? status
Is mobile data working? timesync
Send momentary values via e-mail misreport
Send momentary values to a specific recipient misreport email.to=name@

domain.se
Receive meter values via sms| misreport 101 [secondary address]
Receive meter values as excel files| report 1day 1104 email. to=name@domain.se
Receive hourly values once every day as excel files| sch report1 1day 1104

n: the number of meters to be installed [profile]: customer specific profile with custom settings (contact Elvaco to order a profile). Default settings will be used if no customer specific profile is set.

[secondary address]: secondary address of the meter to be read. If only TECHNICAL SPECIFICATIONS one meter is connected, the secondary address can be omitted.An SMS from the product should be received within a minute with information that the installation has started. The product will also send an SMS with information about if the installation was successful or not. For a successful installation, the signal strength should be at least 3.

TROUBLESHOOTING

All LEDs are permanently off

There is a problem with the supply voltage. Please verify 100-240 VAC.
If the problem persists, the product may be malfunctioning. Please contact Elvaco support.

Red LED is permanently on

This indicates an error on the M-Bus 2-wire bus. Please verify no short circuit of the M-Bus bus. The voltage of the bus should be between 24
VDC and 30 VDC.
Red LED is flashing shortly or 50/50

This indicates an error on the networks or SIM card.

Please verify:

  • SIM card has no PIN code activated.
  • SIM card is activated.
  • SIM card contact areas are clean.
  • Antenna installation. Installation with bad network coverage sometimes requires an external antenna.

The product does not respond to SMS requests

Please verify:

  • Product is powered up.
  • LEDs are showing normal operation and network coverage.
  • Security access codes may be used; verify correct access code.
  • If a prepaid SIM card is used, balance may be zero.

Install command does not find any meters

Please verify your M-Bus slave configuration:

  • Voltage over M-Bus slave should be between 24 VDC and 30 VDC.
  • All M-Bus slaves must have unique primary or secondary M-Bus addresses depending on addressing mode.
  • M-Bus slave baud rates.

Timesync command does not work

This may be due to wrong APN is set. Set the correct APN with the command: qset net [APN][user][password]. Please contact your network provider for information about APN, APN username and APN password.

E-Mail reporting is configured but no e-mails are sent

This may be due to the following reasons, when customer specific profile is not used:

  • No or wrong SMTP server is auto detected. Please verify with command status. If the SMTP server is not set, please set the SMTP server manually by using command qset email [recipient] [SMTPserver] [SMTP-port].
  • No/no valid recipients are set. Set recipients with command qset email [recipient].
  • Report is not correctly activated, please configure e-mail reports with command sch (see table).

SAFETY

The warranty does not cover damage to the product caused by usage in any other way than described in this manual. Elvaco AB can not be liable for personal injury or property damage caused by usage in any other way than described in this manual.

TECHNICAL SPECIFICATIONS

Mechanics

Protection class| IP20
Mounting| Mounted on DIN rail (DIN 50022) 35 mm
SIM card| Push-push type
Electrical connections
Supply voltage| Screw terminal. Cable 0.5-2.5 mm², 0.5 Nm tightening torque
M-Bus master port| Screw terminal. Cable 0.2-1.5 mm²
Electrical characteristics
Nominal voltage| 100-240 VAC (+/- 10%)
Frequency| 50/60 Hz
Power consumption (max)| <6 W
Power consumption (nom)| <1 W
Installation category| CAT 3
User interface
Green LED| Power
Red LED| Error
Yellow LED| Network status
Push button| Factory reset
Configuration| SMS, HTTP, Telnet
Integrated M-Bus Master
M-Bus baud rate| 2400 and 9600 bit/s
Nominal voltage| 28 VDC
Maximum unit loads| 16T/24 mA
Maximum cable length| 1000 m (100 nF/km, maximum 90 Ù)
Approvals
EMC| EN 61000-6-2, EN 61000-6-3, EN 301489-

1, EN 301489-7

Safety| EN 61010-1, CAT 3

ORDERING INFORMATION

Product Item number Description
CMe2100 LTE 1100386 1 M-Bus meter
CMe2100 LTE 1100363 16 M-Bus meter (16T)
CMe2100 LTE 1100364 32 M-Bus meters (16T)
CMe2100 LTE 1100365 64 M-Bus meters (16T)
CMe2100 LTE 1100366 128 M-Bus meters (16T)
CMe2100 LTE 1100367 256 M-Bus meters (16T)

SIMPLIFIED DECLARATION OF CONFORMITY

Hereby, Elvaco declares that the product is in compliance with the following directives:

EU:

  • 2014/30/EU (EMC)
  • 2014/35/EU (LVD)
  • 2014/53/EU (RED)
  • 2011/65/EU + 2015/863 (RoHS)

UK:

  • 2017 No. 1206
  • 2016 No. 1091
  • 2016 No. 1101
  • 2012 No. 3032

The complete Declaration of Conformity can be found at www.elvaco. se/en > Search on product or article number.

CUSTOMERS SUPPORT

© 2022, Elvaco AB. All rights reserved. The documentation and product are provided on an “as is” basis only and may contain deficiencies or inadequacies. Elvaco AB takes no responsibility for damages, liabilities or other losses by using this product. No part of the contents of this manual may be transmitted or reproduced in any form by any means without the written permission of Elvaco AB. Printed in Sweden.

CONTACT INFORMATION

Symbol

Elvaco AB Technical support:
E-mail: support@elvaco.com
Online: www.elvaco.com

Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals