CMa30 USB M-Bus Master
Specifications:
- Product Name: CMa30 USB M-Bus master
- Designed for mobile use
- Supports up to 30 M-Bus slaves
- M-Bus 2-wire bus with no polarity
Product Usage Instructions:
Installation:
-
Download drivers for CMa30 from
here. -
Install the drivers on the computer.
-
Connect CMa30 to the USB port on the computer.
-
Check the COM port number assigned to the device in the device
manager.
LED Indications:
-
Green PWR LED: Indicates mains supply
status. -
Red ERR LED: Indicates M-Bus 2-wire bus
status. -
Yellow RX LED: Indicates communication from
M-Bus slave to computer. -
Yellow TX LED: Indicates communication from
computer to M-Bus slaves.
Troubleshooting:
-
If Green PWR LED is permanently off, ensure CMa30 is connected
to an active USB port. -
If Green PWR LED is on but CMa30 is not working, check if
drivers are correctly installed: -
Click on Start.
-
Right-click on Computer and select Properties.
-
Click on Device Manager.
-
Expand the Ports (COM & LPT) tab.
-
Check for a port called Silicon Labs CP210X USB to UART Bridge
to find the COM port assigned to the device. -
If not found, download drivers from here.
Frequently Asked Questions (FAQ):
Q: How many M-Bus slaves can CMa30 handle?
A: CMa30 can handle up to 30 M-Bus slaves.
Q: Where can I download drivers for CMa30?
A: Drivers for CMa30 can be downloaded from the Elvaco Knowledge
Base at https://support.elvaco.com/hc/en-us.
CMa30
USB M-Bus master
INTRODUCTION
CMa30 is a USB M-Bus master specifically designed for mobile use. In
combination with a laptop, it is suitable for installation and troubleshooting
of M-Bus slaves. CMa30 is also suitable for fast and easy reading of small
M-Bus systems. Drivers for CMa30 and more information about M-Bus can be
downloaded from the Elvaco Knowledge Base, https://support.elvaco.com/ hc/en-
us.
OVERVIEW
1. USB port 2. PWR LED green 3. ERR LED red 4. RX LED yellow 5. TX LED yellow
6. M-Bus connection
M-BUS 2-WIRE BUS
M-Bus is a multi-drop 2-wire bus with no polarity. Connect the wiring to
terminal (6). CMa30 handles up to 30 slaves. Overloading the bus will turn on
the ERR LED and turn off the M-Bus bus. All connected M-Bus slave devices must
have unique primary or secondary addresses depending on addressing mode.
LED INDICATIONS
Green PWR LED PWR LED indicates mains supply.
Mode
Description
Visual
Permanently on
Mains power connected
Permanently off
No mains power connected
Red ERR LED ERR LED indicates M-Bus 2-wire bus status.
Mode
Description
Visual
Permanently on
Short circuit of the M-Bus 2-wire bus
Permanently off Normal mode, Idle
INSTALLATION
Drivers for CMa30 have to be installed on the computer before using CMa30.
Drivers are available for download at https://support.elvaco.com/hc/en-us/
articles/17439477128221-Installing-drivers.
Start the installation guide and follow the instructions. Connect the CMa30 to
the USB port in the computer and check which COM port number the device
received in the device manager. See the Troubleshooting section for more
information.
Short flash every No M-Bus slaves
second
connected
Flashing for 1 second
M-Bus slave collision
Yellow RX LED RX LED indicates communication from M-Bus slave to computer.
Mode
Description
Visual
On/Flashing
M-Bus slave is transmitting data
Off
M-Bus slave is not
transmitting data
Yellow TX LED TX LED indicates communication from computer to M-Bus slaves.
Mode
Description
Visual
On/Flashing
Computer is transmitting data
Off
Computer is not
transmitting data
TROUBLESHOOTING
Green PWR LED is permanently off Make sure that CMa30 is connected to an
active USB port.
Green PWR LED is on but CMa30 is not working Make sure that the drivers for
CMa30 are correctly installed (Windows).
1. Click on “Start”
2. Right click on “Computer” and properties.
3. Click on “Device manager”
4. Expand the tab under Ports (COM & LPT)
5. Check if there is a port called “Silicon Labs CP210X USB to UART Bridge”.
The line ends with the COM port the device has been assigned.
6. To ensure which port is used, the USB cable should be plugged out. The
port will then disappear from the list. When reconnecting the USB cable the
port appears in the list again.
7. If the device is not found in the list, the drivers for the device need to
be installed/reinstalled. Download the drivers on http://www.
elvaco.com/en/download/31160
NOTE! The steps 1-3 may look different depending on which version of Windows
you are using. The keyboard shortcut Windows key + R with the command
devmgmt.msc can also be used to start the device manager. (Press the Windows
key and R simultaneously and type devmgmt.msc in the box that appears.)
CMa30 is working but no slaves are found
1. Make sure that the yellow TX LED is flashing when the scan is started from
the M-Bus software. This is a confirmation that the correct COM port is
selected.
2. Check if the red ERR LED is flashing. This indicates error on the bus.
3. Check if the red ERR LED is permanently on. This indicates short circuit
or overload of the bus (more than 30 M-Bus loads).
4. Make sure that scanning/reading is made with the correct baud rate.
SAFETY
The warranty does not cover damage to the product caused by usage in any other
way than described in this manual. Elvaco AB can not be liable for personal
injury or property damage caused by usage in any other way than described in
this manual.
ORDERING INFORMATION
Product CMa30
Part number 1050103
Description USB M-Bus master
CONTACT INFORMATION
Elvaco AB Technical support:
E-mail: support @elvaco.com Online: www.elvaco.com
TECHNICAL SPECIFICATIONS
Mechanics Protection class Dimensions Weight Connection M-Bus
Mounting Cable Electrical Power supply Power consumption at 1 T Environmental
Operating temperature range Storage temperature range Pollution Operating
altitude M-Bus M-Bus standard M-Bus baud rate Maximum connected M-Bus loads
Maximum cable length Maximum load capacitance Nominal voltage IR interface
Pass through Compatibility Approvals EMC
IP41 98x57x26 mm 95 g Pluggable screw terminal 0.25-2.5 mm² Desktop USB type
A-B 0.6 m
USB type B 5 V 500 mA 160 mA
-20 °C to +55 °C
-40 °C to +85 °C Degree 2 0-2000 m
EN 13757 300, 2400 Bit/s 30 (one load is 1.5 mA)
1000 m 1.5 uF 28 VDC No No All standard M-Bus slaves
EN 61000-6-2, EN 61000-6-3
Elvaco AB, Kabelgatan 2T, S-43437 Kungsbacka, Sweden
© 2016, Elvaco AB. All rights reserved. The documentation and product are provided on an “as is” basis only and may contain deficiencies or inadequacies. Elvaco AB takes no responsibility for damages, liabilities or other losses by using this product. No part of the contents of this manual may be transmitted or reproduced in any form by any means without the written permission of Elvaco AB. Printed in Sweden.
CMa30 Quick manual A4 English Document id: 1090071 Version: 3.1
References
Read User Manual Online (PDF format)