WATLOW FMHA 0600-0096-0000 High Density Input/Output Modules User Guide

June 13, 2024
WATLOW

WATLOW FMHA 0600-0096-0000 High Density Input/Output Modules

WATLOW-FMHA-0600-0096-0000-High-Density-Input-Output-Modules-PRODUCT-IMG

Safety Information

  • We use caution symbols where needed within this document to draw your attention to important operational and safety information.
  • A “CAUTION” safety alert appears with information that is important for protecting your equipment and performance. Be especially careful to read and follow all cautions that apply to your application.
  • A “WARNING” safety alert appears with information that is important for protecting you, others and equipment from damage. Pay very close attention to all warnings that apply to your application.
  • The electrical hazard symbol, (a lightning bolt in a triangle) precedes an electric shock hazard CAUTION or WARNING safety statement. Further explanations follow:
Symbol Explanation

| CAUTION – Warning or Hazard that needs fur- ther explanation than label on unit can provide. Consult QSG for further information.

Available F4T/D4T Literature and Resources

All of the user documents listed below can be found on the Watlow website: http://www.watlow.com. The Watlow Support Tools DVD can be acquired by contacting Watlow customer service (507-494-5300).

Document Title and Part Number Description

F4T Installation and Troubleshooting User Guide, part number: 0600-0092-

0000

| Provides detailed specifications and information regarding mounting the base, flex module wiring and troubleshooting.

F4T Setup and Operations User Guide, part number: 0600-0093-0000

| Explains how to configure and operate the device for an application using Composer software as well as the user interface (touch screen). Includes detailed descriptions of all device features and parameter settings.
D4T Installation and Troubleshooting User Guide, part number: 0600-0107-

0000

| Provides detailed specifications and information regarding mounting the base, flex module wiring and troubleshooting.

D4T Setup and Operations User Guide, part number: 0600-106-0000

| Explains how to configure the datalogger for an application using the user interface and Composer software. Includes detailed descriptions of all data logger features and parameter settings.

Installation and Wiring

To install the flex module:

  1. Note the part number to determine the number and type of inputs oroutputs available to be connected in step 7.
  2. Turn off device power.
  3. Select a compatible base slot for the module. See the Flex Module-Slot Dependencies table below. If replacing a module, remove the oldmodule.
  4. Affix corresponding slot number labels (provided) to the module and tothe removable screw terminal block.
  5. With the component side of the module facing right (viewing the F4T/D4Tfrom the rear) insert the module into the slot until it latches.
  6. Remove the screw terminal block from the module.
  7. Wire field devices to the appropriate terminals. Wiring details for each input and output are provided in the following sections.
  8. Reconnect the wired screw terminal block to the module. Be sure to reconnect the terminal block to the correct module.
  9. Restore power to the F4T/D4T.

WATLOW-FMHA-0600-0096-0000-High-Density-Input-Output-Modules-
FIG-4

Note
If the flex module is a replacement with the same part number and slot position, the F4T/D4T uses it immediately when powered up. Otherwise, use Composer software to configure the F4T/D4T to expect and use the module.

Module Characteristics Description and Identification

Many of the modules appear to look alike at first glance, therefore, it is always recommended that the module part number be verified prior to plugging it into any of the available slots in a base. Each module is identified with a part number located on the back side of the assembly next to the screw terminal block, as displayed in the graphic to the right.

Wiring
Prior to wiring any of the I/O modules described in this document, it is recommended that the warnings and notes listed below be reviewed.
CAUTION
To prevent damage to the F4T/D4T, do not connect wires to unused terminals.

Note
Maintain electrical isolation between the analog input, digital input-outputs, switched dc/open collector outputs and process outputs to prevent ground loops.
Note
Modules IP10 when properly installed in base enclosure with slot caps in empty slots.
CAUTION:   Quencharc Note:
Switching pilot duty inductive loads (relay coils, solenoids, etc.) with the mechanical relay, solid-state relay or open collector output options requires use of an R.C. suppressor for AC load or a diode for a DC load.

Note
Wire size and torque for screw terminations:

  • 0.0507 to 3.30 mm2 (30 to 12 AWG) single-wire termination or two 1.31 mm2 (16 AWG)
  • 0.57 Nm (5.0 lb.-in.) torque

Input Connections

Thermocouple

FMHA – [R] A A A – A _

  • Grounded or ungrounded sensors, greater than 20MΩ input impedance, 2kΩ source resistance max
  • 3μA open-sensor detection
  • Thermocouples are polarity sensitive. The negative lead (usually red) must be connected to S terminal
  • To reduce errors, the extension wire for thermocouples must be of the same alloy as the thermocouple

RTD

FMHA – [R] A A A – A _

  • Platinum, 100 and 1kΩ @ 32°F (0°C) calibration to DIN curve (0.00385 Ω/Ω/°C)
  • RTD excitation current of 0.09mA typical. Each ohm of lead resistance may affect the reading by 2.55°C for a 100Ω platinum sensor or 0.25°C for a 1kΩ sensor (see table to right)
AWG Ohms/ 1000ft
14 2.575
16 4.094
18 6.510
20 10.35
22 16.46
24 26.17
26 41.62
28 66.17

Process

FMHA – [R] A A A – A

  • 0 to 20mA @ 100Ω input impedance
  • 0 to 10V (dc) @ 20kΩ input impedance
  • 0 to 50mV (dc) @ 20MΩ input impedance
  • Scalable

Potentiometer

FM [M, L] A – [C, L, Y, R] A – A

  • Potentiometer: 0 to 1.2kΩ

Thermistor

FMHA – [P] A A A – A _

  • 20MΩ input impedance

  • 0 to 40kΩ, 0 to 20kΩ, 0 to 10kΩ, 0 to 5kΩ
  • 2.252kΩ and 10kΩ base at 77°F (25°C)
  • User-selectable curves for Alpha Technics, Beta THERM and YSI
  • User-scaling support for Steinhart-Hart coefficients

Thermistor Curve Setting| Base R @ 25 ºC| Alpha Technics| Beta Therm| YSI
---|---|---|---|---
Curve A| 2.252k| Curve A| 2.2k3A| 004
Curve B| 10k| Curve A| 10k3A| 016
Curve C| 10k| Curve C| 10k4A| 006

Custom

| Use Steinhart-Hart equation coefficients (A, B and

C) from thermistor manufacturer corresponding to the terms of the Steinhart- Hart equation:

1 / T = A + B ln (R) + C (ln(R))3

Six Digital Inputs

  • Voltage
    • Max. input 36V at 3mA
    • Input inactive when ≤ 2V
    • Input active when ≥ 3V at 0.25mA
  • Dry Contact
    • Input inactive when ≥ 500Ω
    • Input active when ≤ 100Ω
    • Max. short circuit 13mA

FMHA – [C] A A A – A _

WATLOW-FMHA-0600-0096-0000-High-Density-Input-Output-Modules-
FIG-13

Six Digital Outputs

Open Collector

  • Maximum switched open collector voltage is 32V (dc)
  • 400mA, maximum open circuit voltage of 25V (dc), typical 8V (dc) at 80mA
  • Maximum output sink current per output is 1.5A (external class 2 or SELV* supply required)
  • Total sink current for all outputs not to exceed 8A
  • Do not connect outputs in parallel
  • Safety Extra Low Voltage

FMHA – [C] A A A – A _

Open Collector Outputs

Switched DC

  • User selectable voltage, 5V (dc) at 130mA or 19 to 22V (dc) at 80mA

Switched DC Outputs

Tri-Process/Retransmit Outputs

  • 0 to 20mA into 400Ω maximum load
  • 0 to 10V (dc) into 4 kΩ minimum load
  • Outputs are scalable
  • Output supplies power
  • Each output can be independently set for voltage or current
  • Output may be used as retransmit or control

FMHA – [F] A A A – A _

WATLOW-FMHA-0600-0096-0000-High-Density-Input-Output-Modules-
FIG-18

Four Mechanical Relays, Form A

  • 5A at 240VÅ (ac) or 30V (dc) maximum resistive load
  • 20mA at 24V minimum load
  • 125 VA pilot duty @ 120/240VÅ (ac), 25 VA at 24VÅ (ac)
  • 100,000 cycles at rated load
  • Output does not supply power.
  • For use with ac or dc
  • See Quencharc note (page 4)

Note
Not 60730 compliant.

WATLOW-FMHA-0600-0096-0000-High-Density-Input-Output-Modules-
FIG-20

Dual 10A Solid-State Relays, Form A

  • 10A at 20 to 264VÅ (ac) maximum resistive load
  • 10A per output at 240VÅ (ac), max. 20A per card at 122°F (50°C), max. 12A per card at 149°F (65°C)
  • Opto-isolated, without contact suppression
  • Maximum off state leakage of 105μA
  • Output does not supply power
  • Do not use on dc loads.
  • Requires two slots

FMHA – [K] A A A – A _

WATLOW-FMHA-0600-0096-0000-High-Density-Input-Output-Modules-
FIG-22

Note
This module requires 2 slots, therefore it cannot be placed in slot 3 or 6.

Note
Not 60730 compliant.

Four 2A Solid-State Relays, Form A

  • 2A at 20 to 264VÅ (ac) maximum resistive load
  • 50 VA 120/240VÅ (ac) pilot duty
  • Optical isolation, without contact suppression
  • Maximum off state leakage of 105μA
  • Output does not supply power.
  • Do not use on dc loads.
  • N.O., COM, N.O wiring (shared common) between each set of outputs.
  • See derating curve below for maximum current output.

FMHA – [L] A A A – A _

WATLOW-FMHA-0600-0096-0000-High-Density-Input-Output-Modules-
FIG-25

3 Mechanical Relays, 2 Form C, 1 Form A

  • 5A at 24 to 240VÅ (ac) or 30V (dc) maximum resistive load
  • 125 VA pilot duty 120/240VÅ (ac) 25 VA at 24VÅ (ac)
  • Output does not supply power
  • Form A relay shares common with one Form C relay.
  • See Quencharc note

FMHA – [B] A A A – A _

WATLOW-FMHA-0600-0096-0000-High-Density-Input-Output-Modules-
FIG-27

Warranty

F4T/D4T Flex modules are manufactured by ISO 9001 registered processes and are backed by a three-year warranty to the first purchaser for use, providing that the modules have not been misapplied.

Technical Assistance

To get assistance from Watlow:

This F4T/D4T Quick Start Guide (QSG) is copyrighted by Watlow Electric Manufacturing Company, © November 2016 with all rights reserved.

Symbol Explanation

Unit is compliant with European Union directives. See Declaration of Conformity for further details on directives and standards used for compliance.

| Unit has been reviewed and approved by CSA Inter- national for use as Temperature Indicating-Regulating Equipment per CSA C22.2 No. 24. See: www .csa-inter- national.org
| Recognized component UL Files E185611 Process Control Equipment and E43684 Automatic Temperature Sensing Control Integrated Equipment, see conditions of acceptability.

Specifications

Input Type

| Max Error @ 25 Deg C| Accuracy Range| Operating Range|

Units

---|---|---|---|---
Low| High| Low| High
J| ±1.75| 0| 750| -210| 1200| Deg| C
K| ±2.45| -200| 1250| -270| 1371| Deg| C
*T (-200 to

| ±1.55| -200| 350| -270| 400| Deg| C
N| ±2.25| 0| 1250| -270| 1300| Deg| C
*E| ±2.10| -200| 900| -270| 1000| Deg| C
R| ±3.9| 0| 1450| -50| 1767| Deg| C
S| ±3.9| 0| 1450| -50| 1767| Deg| C
B| ±2.66| 870| 1700| -50| 1816| Deg| C
C| ±3.32| 0| 2315| 0| 2315| Deg| C
D| ±3.32| 0| 2315| 0| 2315| Deg| C
F (PTII)| ±2.34| 0| 1343| 0| 1343| Deg| C


Input Type

| Max Error @ 25 Deg C| Accuracy Range| Operating Range|


Units

---|---|---|---|---
Low| High| Low| High
*RTD, 100Ω| ±2.00| -200| 800| -200| 800| Deg C


RTD, 1kΩ

| ****

±2.00

| ****

-200

| ****

800

| ****

-200

| ****

800

| ****

Deg C

mV| ±0.05| 0| 50| –| –| –| –| –| –| mV
Volts| ±0.01| 0| 10| –| –| –| –| –| –| Volts
mAdc| ±0.02| 2| 20| –| –| –| –| –| –| mA DC
mAac| ±5| -50| 50| –| –| –| –| –| –| mA AC
Potenti- ometer 1k range| ****

±1

| ****

0

| ****

1000

| ****

| ****

| ****

| ****

| ****

| ****

| ****

Ohms

  • NSF approved inputs

Thermistor Input

Input Type| Max Error @ 25 Deg C| Accuracy Range| Units
Low| High
Thermistor, 5k range| ±5| 0| 5000| Ohms
Thermistor, 10k range| ±10| 0| 10000| Ohms
Thermistor, 20k range| ±20| 0| 20000| Ohms
Thermistor, 40k range| ±40| 0| 40000| Ohms

Declaration of Conformity

  • WATLOW Electric Manufacturing Company ISO 9001since 1996.
  • 1241 Bundy Blvd. Winona, MN 55987 USA
  • Designation:Series EZ-ZONE®Flex ModulesModel Numbers:FMLA-(LAJ, LCJ, LEJ, MAJ, MCJ, MEJ, YEB1)A1-A1(A1,F1,B1,G1)X1X1FMMA-X1(A1,C1,E,F1,K)(A1,C1,H,J,K)A1-A1(A1,F1,B1,G1)X1X1FMHA-(R1,P1,C1,F1,B1,J,K,L1)A1A1A1-A1(A1,F1,B1,G1)X1X11FMCA-XAAA-A(A,F,B,G)XX;
  • Note: X1= Any letter or numberClassification:FMLA, FMMA and FMHA are Process Controlmodules, FMCAare Communication modules; Modules are Integrated Controlsin either EZ-ZONE®CC,F4Tor D4TBases;Modules are IP10when properly installed.Rated Voltage and
  • Frequency:Relay, SSR or No-Arc Control outputs 24 to240 V~ (ac)50/60 Hz, Switched DC, Processand communications;low voltage SELVRated Power Consumption:See manual for de-ratingat increase dtemperatures.No-arc relays 15A1.C, Dual SSR module 1.C 10A each output,
  • Mechanical relay 5A125 VA,25 VA at 24 V~ (ac)1.B,Discreet SSR 1/2A1.C 20VA, Quad SSR 1.C 1.5A50 VA, Hex I/O ELV 1.5A, all others SELV limited energy.Flex Modules are considered components and have no function in and of themselves, it is only when installed inaWatlowEZ-
  • ZONE®CC, Series F4Tor Series D4TBase enclosure that they have useful function. Modules were tested as parts of these systems for compliance with the following directives.

2014/30/EUElectromagnetic Compatibility DirectiveEN 61326-1:2013Electrical equipment for measurement, control and laboratory use –EMC requirements (Industrial Immunity, Class B Emissions).

2014/35/EULow-Voltage Directive

  • EN 61010-1:2010All options compliantSafety Requirements of electrical equipment for measurement, control and laboratory use. Part 1: General requirements
  • EN 60730-1:2011EN 60730-2-9:20101Food Service Compliant options.Automatic electrical controls for household and similar
  • use –Particular requirements for temperature sensing controls.Only certain output options comply with 60730 spacing and dielectric requirements, see order information for compatible models.

Compliant with 2011/65/EURoHS2Directive

  • Per 2012/19/EU W.E.E.E Directive,  Please Recycle Properly.
  • See the Declarations of Conformity forWatlowEZ-ZONE®CC,SeriesF4T and Series D4Tmodelsfor further details on standards used for compliance.

WATLOW-FMHA-0600-0096-0000-High-Density-Input-Output-Modules-
FIG-32

How to Reach Us

Corporate Headquarters

Latin America

  • Watlow de México S.A. de C.V.
  • Av. Fundición No. 5
  • Col. Parques Industriales
  • Querétaro, Qro. CP-76130
  • Mexico
  • Tel: +52 442 217-6235
  • Fax: +52 442 217-6403

Europe

  • Watlow France
  • Tour d’Asnières.
  • 4 Avenue Laurent Cély
  • 92600 Asnières sur Seine

France

Watlow GmbH

  • Postfach 11 65, Lauchwasenstr. 1
  • D-76709 Kronau
  • Germany
  • Tel: +49 (0) 7253 9400-0
  • Fax: +49 (0) 7253 9400-900
  • Email: info@watlow.de
  • Website: www.watlow.de

Watlow Italy S.r.l.

Watlow Ibérica, S.L.U.

  • C/Marte 12, Posterior, Local 9
  • E-28850 Torrejón de Ardoz
  • Madrid – Spain
  • T. +34 91 675 12 92
  • F. +34 91 648 73 80
  • Email: info@watlow.es
  • Website: www.watlow.es

Watlow UK Ltd.

  • Linby Industrial Estate
  • Linby, Nottingham, NG15 8AA
  • United Kingdom
  • Telephone: (0) 115 964 0777
  • Fax: (0) 115 964 0071
  • Email: info@watlow.co.uk
  • Website: www.watlow.co.uk
  • From outside The United Kingdom:
  • Tel: +44 115 964 0777
  • Fax: +44 115 964 0071

Asia and Pacific

  • Watlow Singapore Pte Ltd.
  • 20 Kian Tech Lane 4th Floor
  • Singapore – 627854
  • Tel: +65 6773 9488 Fax: +65 6778 0323
  • Email: info@watlow.com.sg Website: www.watlow.com.sg
  • Watlow Australia Pty., Ltd.
  • 4/57 Sharps Road
  • Tullamarine, VIC 3043
  • Australia
  • Tel: +61 3 9335 6449
  • Fax: +61 3 9330 3566
  • Website: www.watlow.com

Watlow Electric Manufacturing (Shanghai) Company

  • 1118 Fangyuan Road, Anting Industrial Park, Jiading, Shanghai,
  • PRC 201203
  • People’s Republic of China
  • Tel: +86 21 39509510
  • Fax: +86 21 5080-0906
  • Email: info@watlow.cn
  • Website: www.watlow.cn

Watlow Korea Co., Ltd.

  • 2208, Hyundia KIC Building B, 70 Doosan-ro

  • Geumcheon-gu, Seoul
  • Republic of Korea
  • Tel: +82 (2) 2169-2600
  • Fax: +82 (2) 2169-2601
  • Website: www.watlow.co.kr

Watlow Malaysia Sdn Bhd

  • No. 14-3 Jalan 2/114
  • Kuchai Business Centre
  • Jalan Kuchai Lama
  • 58200 Kuala Lumpur
  • Malavsia
  • Tel: +60 3 7980 7741 Fax: +60 3 7980 7739

1241 Bundy Boulevard., Winona, Minnesota USA 55987 Phone: +1 507-454-5300, Fax: +1 507-452-4507 http://www.watlow.com

Read User Manual Online (PDF format)