WATLOW Fluent In Line Air Heater User Guide

June 4, 2024
WATLOW

FLUENT® QUICK START GUIDE

FLUENT ® INSTALLATION

Mounting Orientation

  • FLUENT® heater orientation must be vertical for liquids.
  • Flow direction must always start at the inlet (lead exit) and flow to the outlet. When mounted vertically, the inlet side should be on the bottom.

Application Orientation

Electrical Connection

  • Do not apply more than the recommended voltage marked on the FLUENT heater.
  • Grounding to any of the exterior metal components is recommended.
  • A heater with multiple heating circuits should have the circuits connected in parallel and must be powered simultaneously.

2-Circuit Wiring Diagram

Temperature Control

  • The FLUENT heater should not be powered unless fluid flow is present.
  • The integrated Type K thermocouple is mounted on the heating element and should only be used as a high-limit sensor with a latching limit control.
  • The maximum limit temperature setting is 350°C. A lower setting may be applicable and provide improved product protection.
  • Fluid temperature sensing must be accomplished by a downstream sensor.

Minimum High Limit Circuit Requirements

Other Specifications

  • Maximum pressure rating: 150 PSI (10.3 bar)
  • This is intended to be used as a quick start guide. Full documentation on these and other topics can be found in the product guide at http://fluent.watlow.com/

Contact us atwww.watlow.com