WATLOW F4T FMMA Mixed I-O Flex Module User Guide
- June 9, 2024
- WATLOW
Table of Contents
- F4T/D4T Flex Module
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
F4T/D4T Flex Module
Quick Start Guide
Mixed Input / Output Modules
Control, Limit, Auxiliary and CT
FM [M or L] A- A-A
0600-0097-0000 Rev. D Made in the U.S.A.
November 2016
Safety Information
We use caution symbols where needed within this document to draw your
attention to important operational and safety information.
A “CAUTION” safety alert appears with information that is important for
protecting your equipment and performance. Be especially careful to read and
follow all cautions that apply to your application.
A “WARNING” safety alert appears with information that is important for
protecting you, others and equipment from damage. Pay very close attention to
all warnings that apply to your application.
The electrical hazard symbol, (a lightning bolt in a triangle) precedes an
electric shock hazard CAUTION or WARNING safety statement. Further
explanations follow:
Symbol | Explanation |
---|
CAUTION WARNING
or
Electrical Shock Hazard| CAUTION – Warning or Hazard that needs further explanation than label on unit can provide. Consult QSG for further information.
Document Overview
The purpose of this Quick Start Guide (QSG) is to acquaint the user with the F4T Flex Modules and associated wiring.
Product Overview
Flex modules add functionality, inputs and outputs to an F4T system. The flex modules described in this document offer various input and output options as well as a safety over/under temperature limit. Each module can include one analog input and up to two outputs. All of these modules can be placed in any available slot.
Available F4T/D4T Literature and Resources
Document Title and Part Number | Description |
---|---|
F4T Installation and Troubleshooting User Guide, part number: 0600-0092-0000 |
Provides detailed specifications and information regarding mounting the base,
flex module wiring and troubleshooting.
F4T Setup and Operations User Guide, part number: 0600-0093-0000| Explains how
to configure and operate the device for an application using Composer software
as well as the user interface (touch screen). Includes detailed descriptions
of all device features and parameter settings.
D4T Installation and Troubleshooting User Guide, part number: 0600-0107-0000|
Provides detailed specifications and information regarding mounting the base,
flex module wiring and troubleshooting.
D4T Setup and Operations User Guide, part number: 0600-106-0000| Explains how
to configure the datalogger for an application using the user interface and
Composer software. Includes detailed descriptions of all data logger features
and parameter settings.
Installation and Wiring
To install the flex module:
- Note the part number to determine the types of inputs and outputs available to be connected in step 7.
- Turn off power to the controller.
- Select a slot for the module. If replacing a module, remove the old module.
- Affix corresponding slot number labels (provided) to the module and to the removable screw terminal block.
- With the component side of the module facing right (viewing the controller from the rear) insert the module in to the slot until it latches.
- Remove the screw terminal block from the module.
- Wire field devices to the appropriate terminals. Wiring details for each input and output are provided in the following sections.
- Reconnect the wired screw terminal block to the module. Be sure to reconnect the terminal block to the correct module.
- Restore power to the controller.
Note:
If the flex module is a replacement with the same part number and slot
position, the controller uses it immediately when powered up. Otherwise, use
Composer software to configure the F4T/D4T to expect and use the module.
Module Characteristics
Description and Identification
Many of the modules appear to look alike at first glance, therefore, it is always recommended that the module part number be verified prior to plugging it into any of the available slots in a base. Each module is identified with a part number located on the back side of the assembly next to the screw terminal block, as displayed in the graphic above.
FM[ M, L ]A – A – A
Wiring
Prior to wiring any of the I/O modules described in this document it is
recommended that the warnings and notes listed below be reviewed.
CAUTION:
To prevent damage to the controller, do not connect wires to unused terminals.
Note:
Maintain electrical isolation between the analog input, digital input-outputs,
switched dc/open collector outputs and process outputs to prevent ground
loops.
Note:
Modules IP10 when properly installed in base enclosure with slot caps in empty
slots.
CAUTION:
Switching pilot duty inductive loads (relay coils, solenoids, etc.) with the
mechanical relay, solid-state relay or open collector output options requires
use of an R.C. suppressor for AC load or a diode for a DC load.
Note:
Wire size and torque for screw terminations:
-
0.0507 to 3.30 mm² (30 to 12 AWG) single-wire termination or two 1.31 mm² (16 AWG)
-
0.57 Nm (5.0 lb.-in.) torque
-
-
Input Connections
Thermocouple
FM [ M, L ] A – [ L, U, Y ] A – A _
-
Grounded or ungrounded sensors, greater than 20MΩ input impedance, 2kΩ source resistance max.
-
3µA open-sensor detection
-
Thermocouples are polarity sensitive. The negative lead (usually red) must be connected to S terminal
-
To reduce errors, the extension wire for thermocouples must be of the same alloy as the thermocouple.
-
-
Process
Milliamps Volts
FM [ M, L ] A – [ L, U ] A – A _
-
0 to 20mA @ 100Ω input impedance
-
0 to 10VÎ (dc) @ 20kΩ input impedance
-
0 to 50mVÎ (dc) @ 20MΩ input impedance
-
Scalable
-
-
Potentiometer
FM [M, L] A – [L, U] A – A _
-
Potentiometer: 0 to 1.2kΩ
-
-
Thermistor
FM [M, L] A – [M, T] A – A _
-
20MΩ input impedance
- 0 to 40kΩ, 0 to 20kΩ, 0 to 10kΩ, 0 to 5kΩ
- 2.252kΩ and 10kΩ base at 77°F (25°C)
- User-selectable curves for Alpha Technics, Beta THERM and YSI
- User-scaling support for Steinhart-Hart coefficients
Thermistor Curve Setting| Base R @ 25 ºC| Alpha Technics|
Beta Therm| YSI
---|---|---|---|---
Curve A| 2.252k| Curve A| 2.2k3A| 004
Curve B | 10k| Curve A| 10k3A| 016
Curve C| 10k| Curve C| 10k4A| 006
Custom| Use Steinhart-Hart equation coefficients (A, B and C) from thermistor
manufacturer corresponding to the terms of the Steinhart-Hart equation: 1 / T
= A + Bln(R) + C (ln(R))³
RTD
2-wire RTD 3-wire RTD
Note:
Use of 2-wire RTDs adds error to the measurement based on wire lead length
(see table). 3-wire auto compensates for wire resistance.
FM [ M, L ] A – [ **L, U, Y ***] A – A _
- 2- or 3-wire platinum, 100 and 1kΩ @ 32°F (0°C) calibration to DIN curve (0.00385 Ω/Ω/°C)
- RTD excitation current of 0.09 mA typical. Each ohm of lead resistance may affect the reading by 2.55°C for a 100Ω platinum sensor or 0.25°C for a 1kΩ sensor.
- For 3-wire RTDs, the S1 lead (usually white) must be connected to R1.
***** This option does not support 3-wire RTDs
Lead Wire Resistance Each Wire for 2-Wire RTDs
AWG| Ohms/1000ft
14| 2.575
16| 4.094
18| 6.510
20| 10.35
22| 16.46
24| 26.17
26| 41.62
28| 66.17
Current Transformer
FMMA – C A – A _
-
Input range is 0 to 50mA (ac).
-
Current transformer part number: 16-0246
-
100Ω input impedance
-
Response time: 1 second maximum
-
Accuracy +/-1mA typical
-
-
Digital Input
FMLA – Y E B A – A _
-
Update rate 10Hz
-
Dry Contact
– Input inactive when ≥ 500Ω
– Input active when ≤ 100Ω
– Max. short circuit 13mA -
Voltage
– Max. input 36V at 3mA
– Input inactive when ≤ 2V
– Input active when ≥ 3V at 0.25mA
Dry Contact
Voltage Input
Output Connections
Mechanical Relay, Form C
FM [ **M, L *] A – _ [ E** ] A – A
- 5A at 240V~ (ac) or 30V (dc) maximum resistive load
- Requires a minimum load of 20mA at 24V
- 125 VA pilot duty at 120/240V~ (ac), 25 VA at 24V~ (ac)
- 100,000 cycles at rated load
- Output does not supply power.
- For use with ac or dc
- See Quencharc note (page 4).
Note:
For part number FM LA-_EBA-A _ output 1 is fixed as the limit output.
***** Not available in the D4T.
NO-ARC Relay, Form A
FMMA – H A – A _
-
12A at 122°F (50°C), 85 to 264V~ (ac) resistive load only
-
2,000,000 cycle rating for rated load
-
100mA minimum load
-
2mA maximum off state leakage
-
Do not use on dc loads.
-
Output does not supply power
-
Do not drive another relay or solenoid with this output type
-
-
Mechanical Relay, Form A
FM [ M, L ] A – J A – A _
- 5A at 240V~ (ac) or 30V (dc) maximum resistive load
- 20mA at 24V minimum inductive load
- 125 VA pilot duty at 120/240V~(ac), 25 VA at 24V~(ac)
- 100,000 cycles at rated load
- Output does not supply power.
- For use with ac or dc
- See Quencharc note (page 4).
Note:
For part number FM L A- J A-A _ output 2 is fixed as the limit
output.
Solid-State Relay, Form A
FMMA – [ K ] [ K ] A – A
-
0.5A at 149°F (65°C) to 1A at 50°F (10°C), 24 to 264V~ (ac) maximum resistive load
-
20 VA 120/240V~ (ac) pilot duty
-
Opto-isolated, without contact suppression
-
Maximum off state leakage of 105µA
-
Output does not supply power
-
Do not use on dc loads
-
See Quencharc note (page 4)
-
-
Switched DC / Open Collector
Switched DC
- 30mA dc maximum supply current
- Short circuit limited to < 50mA
- 22 to 32V (dc) open circuit voltage
- Use dc- and dc+ to drive external solid-state relay.
- DIN-A-MITE compatible
Open Collector
- 100mA maximum output current sink
- 30V (dc) maximum supply voltage
- Any switched dc output can use the common terminal.
- Use an external class 2 or Safety Extra Low Voltage (SELV) power supply to control a dc load, with the load positive to the positive of the power supply, the load negative to the open collector and common to the power supply negative.
FM [ M, L ] A – [ C ] [ C ] A – A
Switched DC
Open Collector
Universal Process
FMMA – F A – A _
-
0 to 20mA ±30μA into 800Ω maximum load with 5μA nominal resolution
-
0 to 10V (dc) ±15mV into 1 kΩ minimum load with 2.5mV nominal resolution
-
Scalable
-
Output supplies power
-
Cannot use voltage and current outputs at same time
-
Output may be used as retransmit or control
-
Temperature stability 100ppm/°C
-
-
Warranty
F4T/D4T Flex modules are manufactured by ISO 9001 registered processes and are
backed by a three-year warranty to the first purchaser for use, providing that
the modules have not been misapplied.
This F4T/D4T Quick Start Guide (QSG) is copyrighted by Watlow Electric Manufacturing Company, © November 2016 with all rights reserved.
Symbol | Explanation |
---|---|
Unit is compliant with European Union directives. See Declaration of |
Conformity for further details on directives and standards used for
compliance.
| Unit has been reviewed and approved by Factory Mutual as a Temperature Limit
Device per FM Class 3545 standard. See:
www.fmglobal.com
| Unit has been reviewed and approved by CSA International for use as
Temperature Indicating-Regulating Equipment per CSA C22.2 No. 24. See: www
.csa-international.org
| Recognized component UL Files E185611 Process Control Equipment and E43684
Automatic Temperature Sensing Control Integrated Equipment, see conditions of
acceptability.
Specifications
Input Type| Max Error @ 25 Deg C| Accuracy Range| Operating
Range| Units
---|---|---|---|---
Low| High| Low| High
J| ±1.75| 0| 750| -210| 1200| Deg C
K| ±2.45| -200| 1250| -270| 1371| Deg C
T (-200 to 350)| ±1.55| -200| 350| -270| 400| Deg C
N | ±2.25| 0| 1250| -270| 1300| Deg C
E| ±2.10| -200| 900| -270| 1000| Deg C
R| ±3.9| 0| 1450| -50| 1767| Deg C
S| ±3.9| 0| 1450| -50| 1767| Deg C
B| ±2.66| 870| 1700| -50| 1816| Deg C
C| ±3.32| 0| 2315| 0| 2315| Deg C
D| ±3.32| 0| 2315| 0| 2315| Deg C
*RTD, 100Ω | ±2.00| -200| 800| -200 | 800| Deg C
RTD, 1kΩ | ±2.00| -200| 800| -200 | 800| Deg C
mV| ±0.05| 0| 50| – – –| – – –| mV
Volts| ±0.01| 0| 10| – – –| – – –| Volts
mAdc| ±0.02| 2| 20| – – –| – – –| mA DC
mAac| ±5| -50| 50| – – –| – – –| mA AC
Potentiometer 1k range| ±1| 0| 1000| – – –| – – –| Ohms
*NSF approved inputs
Thermistor Input
Resistance Range| Max Error @ 25 Deg C| Accuracy Range|
Units
Low| High
5k range| ±5 | 0| 5000| Ohms
10k range| ±10 | 0| 10000| Ohms
20k range| ±20 | 0| 20000| Ohms
40k range| ±40 | 0| 40000| Ohms
Series EZ-ZONE® Flex Modules
WATLOW Electric Manufacturing Company
ISO 9001 since 1996.
Declares that the following products:
Designation: | Series EZ-ZONE® Flex Modules |
---|---|
Model Numbers: | FMLA-(LAJ, LCJ, LEJ, MAJ, MCJ, MEJ, YEB¹ )A¹ -A¹ (A¹ ,F¹ ,B¹ |
,G¹ )X¹X¹
FMMA-X¹(A¹, C¹ , E, F¹ ,K)(A¹, C¹ , H, J, K)A¹ -A¹ (A¹ ,F¹ ,B¹ ,G¹ )X¹X¹
FMHA-(R¹ ,P¹ ,C¹ ,F¹ ,B¹ ,J,K,L¹ )A¹ A¹ A¹ -A¹ (A¹ ,F¹ ,B¹ ,G¹ ) X¹X¹
¹FMCA- X AAA-A(A,F,B,G) XX ; Note: X¹ = Any letter or number
Classification:| FMLA, FMMA and FMHA are Process Control modules, FMCA are
Communication modules; Modules are Integrated Controls in either EZ-ZONE®
CC, F4T or D4T Bases; Modules are IP10 when properly installed.
Rated Voltage and Frequency: | Relay, SSR or No-Arc Control outputs 24 to 240
V- (ac) 50/60 Hz, Switched DC, Process and communications; low voltage SELV
Rated Power Consumption: | See manual for de-rating at increased temperatures.
No-arc relays 15A 1.C, Dual SSR module 1.C 10A each output, Mechanical relay
5A 125 VA, 25 VA at 24 V- (ac) 1.B, Discreet SSR 1/2A 1.C 20VA, Quad SSR 1.C
1.5A 50 VA, Hex I/O ELV 1.5A, all others SELV limited energy.
Flex Modules are considered components and have no function in and of themselves, it is only when installed in a Watlow EZ-ZONE® CC, Series F4T or Series D4T Base enclosure that they have useful function. Modules were tested as parts of these systems for compliance with the following directives.
2014/30/EU Electromagnetic Compatibility Directive
EN 61326-1:2013| Electrical equipment for measurement, control and
laboratory use – EMC requirements (Industrial Immunity, Class B Emissions).
---|---
2014/35/EU Low-Voltage Directive
EN 61010-1:2010
All options compliant| Safety Requirements of electrical equipment for
measurement, control and laboratory use. Part 1: General requirements
---|---
EN 60730-1:2011
EN 60730-2-9:2010| Automatic electrical controls for household and
similar use – Particular requirements for temperature sensing controls.
¹ Food Service Compliant options.| Only certain output options comply with
60730 spacing and dielectric requirements, see order information for
compatible models.
Compliant with 2011/65/EU RoHS2 Directive
Per 2012/19/EU W.E.E.E Directive Please Recycle Properly.
See the Declarations of Conformity for Watlow EZ-ZONE® CC, Series F4T and Series D4T models for further details on standards used for compliance.
Joe Millanes
Name of Authorized Representative
Directory of Operations
Title of Authorized Representative
Signature of Authorized Representative
Winona, Minnesota, USA
Place of Issue
April 20, 2016
Date of Issue
1.888.610.7664www.calcert.com sales@calcert.com
References
- Calcert
- Product Certification & Standards Development - CSA Group
- Commercial Property Insurance | FM Global