NXT POWER RT Seismic UPS Line Instruction Manual

June 13, 2024
NXT POWER

NXT POWER logo

NXT POWER
RT SEISMIC INSTALLATION INSTRUCTIONS

NXT POWER RT Seismic UPS Line

RT MOUNTING DIMENSIONS

HOLES FOR 3/8”-16 BOLT (6X)

NXT POWER RT Seismic UPS Line - Fig 1

RT SEISMIC ANCHORING INSTRUCTIONS:

  1. MOVE THE UPS TO THE INSTALLATION LOCATION
  2. BOLT UPS SEISMIC ANCHOR. NXT PART NUMBER 001-00136-01-FNL TO THE FLOOR USING 3/8″ GRADE 8 THREADED RODS (6X) AS DESCRIBED BELOW.

RT
SEISMIC ANCHORAGE UPPER FLOOR
BOLT TORQUE SPEC: 3NM / 27 IN LBS
UNIT WEIGHT:

NXT POWER RT Seismic UPS Line - Fig 2

RT
SEISMIC ANCHORAGE SLAB ON GRADE
BOLT TORQUE SPEC: 3NM / 27 IN LBS
UNIT WEIGHT:

  1. MOVE THE UPS TO THE INSTALLATION LOCATION
  2. BOLT UPS SEISMIC ANCHOR. NXT PART NUMBER 001-00136-01-FNL TO THE FLOOR USING 3/8″ GRADE 8 EXPANSION ANCHORS (6X) FOR CONCRETE AS DESCRIBED BELOW.

NXT POWER RT Seismic UPS Line - Fig 3