FALCON MPPT Source MPPT Solar charge controller 12V 24V Solar system User Manual

June 13, 2024
Falcon

FALCON logo Bluetooth Communication
MPPT Solar charge controller
12V/130WFALCON MPPT Source MPPT Solar charge controller 12V 24V Solar
system User Manual

Functions

Falcon intelligent MPPT solar controller is programmable, waterproof and well- suited for a wide range of solar systems. The charging efficiency of this controller is higher than a traditional PWM controller, helping to get the most out of the solar panel.
It comes with a number of outstanding features, such as:

  • Innovative Maximum Power Point Tracking(MPPT) technology, tracking efficiency >99.9%
  • High charge conversion efficiency up to 96.5%
  • Adjustable 5-stage timer for load output
  • Use high performance, ultra-low power consumption Bluetooth dedicated chip
  • Adopt Bluetooth 5.0 and BLE technology
  • Suitable for Gel, Liquid, AGM and Lithium battery
  • Four stage charging: MPPT, boost, equalization, float
  • 0°C Charging Protection(Lithium)
  • When BMS power off because of LVD, it can activate the system automatically
  • Day/Night threshold can adjust automatically
  • Waterproof IP67, Strong and durable aluminum case
  • Full automatic electronic protect function

Dimensions

FALCON MPPT Source MPPT Solar charge controller 12V 24V Solar system -
Dimensions

Installation

The following diagram provides an overview of the terminals. Please make sure to follow the proper order of connection.FALCON MPPT Source MPPT Solar
charge controller 12V 24V Solar system - diagram provides an
overview

  1. As the chart, Connect the load first with corresponding red(positive) and black (negative) cables, then seal them with tape.
  2. Connect the battery with corresponding positive and negative cables, load will be on.
  3. Connect panel with the corresponding red(positive) and black( negative) cables, the controller begins charging.
  4. Confirm the LED display status, please refer to the 8.2 Faults and Alarms to identify the reason.

Make sure the wire length between battery and controller is as short as possible. Recommended Wire size: 2.5mm?

Starting up the controller

4.1 Self Test
As soon as the controller is powered, it starts a self test routine. After this, the LED display will change to normal operation.
4.2 System Voltage
The controller applies to Lithium, AGM, Liquid and Gel battery, the factory default setting is suitable for Gel battery. It is your responsibility to check and ensure that these settings are correct for your battery, otherwise they must be amended.
When the controller is set to Lithium battery, the charging target voltage and charging recovery voltage can be set according to customer requirements.
If the battery voltage on start-up is 10V-15V , the controller infers a 12V system when the controller is set to Gel, Liquid or AGM battery. If the battery voltage is not within the normal operating rang(ca.10 to 15V) at start-up, please refer to 8.2 Faults & Alarms.

App installation

Search for “solarlife BT” in Google play or “solarlife” in Apple store and download and install it. For detailed instruction and settings, please read the Bluetooth APP user manual.

Andriod APP iOS APP

FALCON MPPT Source MPPT Solar charge controller 12V 24V Solar system -
Andriod APP| FALCON MPPT Source MPPT Solar charge controller 12V 24V Solar system - iOS
APP

BlueTooth

The controller has Bluetooth communication function, the Bluetooth module of the controller can be connected to mobile phone after installing APP.
For detailed operation, please read the “Bluetooth APP instructions “. App on mobile phone can view the realtime working state of the controller and set parameters, including device and battery parameters.
6.1 Charging Voltage (Liquid/ GEL/AGM)
When choosing Liquid, GEL or AGM for battery type, the parameters of boost, equalization and float charging voltage can be set by mobile phone APP. The range of parameters is as follows.
The following voltage parameters are 25°C/12V system parameters.

Charging stage| Charging Voltage Range| Default charging voltage
---|---|---
Boost| 14.0∼14.8V| 14.5V
Equalization| 14.0∼15.0V| 14.8V
Float| 13.0∼14.5V| 13.7V

6.2 Charging Voltage Parameters(Lithium)
When choosing lithium battery type, the overcharge protection and overcharge recovery voltage of lithium battery can be set by mobile phone APP.
Overcharge protection voltage(CVT): 10.0-17.0V
Overcharge recovery voltage(CVR): 9.2-16.8V.
(Overcharge Recovery Voltage+1.5V) =Lithium
Overcharge Protection Voltage=(Overcharge Recovery Voltage+0.2V)
The required accuracy of PCM shall be at least 0.2V. If the deviation is higher than 0.2V, the manufacturer will assume no liability for any system malfunction caused by this.
6.3 Low Voltage Disconnect (LVD)
When the battery voltage drops below the LVD voltage, the controller will disconnect the load to prevent deep discharge of the battery. If this occurs, the battery should be well charged before resuming use.

  1. Lithium Battery
    LVD range: 9.0~15.0V(default: 9.0V).

  2. Gel, Liquid and AGM Battery
    The low voltage protection of the controller can be divided into two types: battery voltage control and capacity control.
    a. Battery voltage control
    Low voltage disconnect setting range: 10.8~11.8V (default: 11.2V).
    b. Battery capacity control
    Low voltage disconnect setting range: Soc1~Soc5

Soc Low voltage protection range
Soc1 11.0~11.6V
Soc2 11.1~11.7V
Soc3 11.2~11.8V
Soc4 11.4~11.9V
Soc5 11.6~12.0V

6.4 Low Volta.ge Reconnect (LVR)
If the low voltage disconnect is triggered, the controller will restore load connection only when the battery voltage increases above the LVR voltage.

  1. Lithium Battery
    LVR range: 9.6~16.0V.

  2. Gel, Liquid and AGM Battery
    LVR range: 11.4~12.8V.

The low voltage recovery voltage(LVR) should be higher than the low voltage disconnect voltage(LVD) at least 0.6V, if you want to improve LVD, you should first improve LVR.
6.5 0°C Charging (Lithium)
“0°C Chg” can be set to “Yes”, “Slow” or “No”. When the controller detects that the ambient temperature is higher than 0°C, the charging function is normal. when the ambient temperature is low than 0°C, if the “0°C Chg” is set to “Yes”, the charging function is normal, else if the “0°C Chg” is set to “slow”, the max charging current is 20% of the rated current, else if the “0°C Chg” is set to “No”, the controller does not charge the battery.
The user can select the appropriate charging method.
6.6 Day/Night Threshold, Day/Night Delay
The controller recognizes day and night based on the solar array open circuit voltage. This day/night threshold can be modified according to local light conditions and the solar array used.
Day/Night threshold setting range: 3.0~8.0V.
The actual time of turning on can be delayed by up to 30 minutes from the time the threshold was reached using the Day/Night delay setting (D/N delay).
Day/Night delay time setting range: 0~30min. FALCON MPPT Source MPPT Solar
charge controller 12V 24V Solar system - Figure 1 Day/Night threshold voltage of load disconnect is 1V higher than the setting data, means the load will disconnect when the solar voltage at 4.0~9.0V.
The controller will automatically adjust the day/night threshold. If the lowest solar voltage is higher than the day/night threshold. The load will have no output the first night, then 24 hours later the controller will automatically adjust the setting to give output the following night.

Load Output Timer Modes

The Falcon controller has advanced day/night time control functions. The modes of lighting can be based on customer needs.
7.1 Standard (24H)FALCON MPPT Source MPPT Solar charge controller 12V
24V Solar system - Figure 2 If “Time1” is set to “24H” and sent to the controller successfully, the controller’s load will always be on.

7.2 Dusk to Dawn (D2D)FALCON MPPT Source MPPT Solar charge controller
12V 24V Solar system - Dusk to Dawn If “Time1” is set to “D2D”, the controller works in dusk to dawn mode.

  1. The dimming setting will still be active in this mode.
  2. If “Time1” is set to D2D mode, “Time4” cannot be set to TOT mode.

7.3 Five-stage Night Mode FALCON MPPT Source MPPT Solar charge
controller 12V 24V Solar system - Night ModeTime 1-5 and Dim 1-5 can be set individually to give variable load power throughout the night.

7.4 TOT mode(can set the load on time before dawn) FALCON MPPT Source
MPPT Solar charge controller 12V 24V Solar system - load on time before
dawnIf “Time4” is set to “TOT”, this mode is TOT mode. If “Time4” is set to “TOT” then the controller will determine Time4 based on Time5 and previous data on the time of sunrise.
While “Time4” is set to TOT mode, “Time1” cannot set to D2D mode.

LED indicators, Faults & Alarms

8.1 LED Display Explanation

LED Status Function

Green
LED| On| Solar panel is correctly connected, but not charged
Flash fast(0.1/0.1s)| MPPT charging
Flash(0.5/0.5s)| Equal or Boost charging (Gel, Liquid or AGM)
Flash slowly(0.5/2s)| Charging
Yellow
LED| Off| Over voltage protection
On| Battery is normal
Slow flash(0.5/2s)| Battery voltage is low
Fast flash(0.1/0.1s)| Low voltage protection
Red
LED| Off| Work normal
On| The output power is 0.
Flash(0.5s/0.5s)| Over temperature
Fast flash(0.1/0.1s)| Short circuit or over * current protection

  • Detailed fault information can be read by S-Unit remote controller.
    8.2 Faults & Alarms
Fault Status Reason Remedy
Loads are not powered Low volt. protection Low Battery capacity Recharge

battery above LVR.
Overcurrent, short circuit protection| Overload or load short-circuit| Switch off all loads, remove short-circuit, load will be reconnected after 1 minute.
Over temp. protection| Controller temp is too high| Controller will turn the system off until temperature is below 60 °C.
High voltage at battery| Over voltage protection| Battery overvoltage >15.5W
(Li: CVT+0.2V)| Check if other sources overcharge the battery.
If not,controller is damaged.
Battery wires or battery fuse damaged,
battery has high resistance.| Check battery wires, fuse and battery.
Incorrect system voltage| All LED
fast flashinc| Battery voltage not in right  range| Charge or discharge battery to correct the voltage
Battery is empty after a time short| Low voltage protection| Battery has low capacity| Change battery
Battery not charging| Green LED is on| PV panel fault or reverse connection| Check panels and wire connections

Safety Features

| Solar terminal| Battery terminal| Load terminal
---|---|---|---
Reverse polarity| Protected¹| Protected| Protected¹
Short circuit| Protected²| Protected³| Switches off immediately
Over current| ———–| ———–| Switches off with delay
Reverse Current| Protected| ———–| ———–
Over voltage| Max.45V| Max. 25V| ———–
Under voltage| ———–| ———–| Switches off
Over temp.| The controller cuts off the load if the temperature reaches the set value.

  1. Controller can protect itself, but load might be damaged.

  2. When the PV doesn’t charge,the controller will not be damaged if short-circuit just happened in the PV array.
    Warning: It is forbidden to short-circuit the PV array during charging .Otherwise, the controller may be damaged.

  3. Battery must be protected by fuse.

Warning:
The combination of different error conditions may cause damage to the controller.
Always remove the error before you continue connecting the controller.

Safty Instructions and Liability Waiver

10.1 Safety

  1. The solar charge controller may only be used in PV systems in accordance with this user manual and with solar panels specifications in line with the requirements of this controller. No energy source other than solar panels may be connected to the solar charge controller.
  2. Batteries store a large amount of energy, never shortcircuit a battery under any circumstances. We strongly recommend connecting an in-line fuse or circuit-breaker on the “+” wire between the battery and controller, no more than 15cm from the battery terminal.
  3. Batteries can produce flammable gases. Avoid sparks and flames near the batteries. Make sure the battery is installed in a well ventilated area.
  4. Avoid touching or short circuiting wires or terminals. Be aware that the voltages on special terminals or wires can be several times greater than the battery voltage. Use isolated tools and only perform any work in a dry environment.
  5. Keep children away from batteries and the charge controller.

10.2 Liability Exclusion
The manufacturer shall not be liable for damages to the controller or battery caused by use other than as instructed in this manual, or if the battery manufacturer’s recommendations are neglected. The manufacturer shall not be liable if there has been service or  repair carried out by any unauthorised person, unusual use, incorrect setup, or bad system design.

Technical Data

| Item| FN-MPPT1050-BT
---|---|---
BatteryPara meters| Max Charging Current| 10A
System Voltage| 12V
Max volt on Bat. Terminal| 25V
Battery Type| Lithium, Liquid, Gel, AGM (Programmable, default: Gel)
Linuid, 4 AGM and Gel| MPPT Charging Voltage| <14.5V@25°C
Boost Voltage| 14.0 ∼ 14.8V(Programmable), default: 14.5V@25°C
Equalization Voltage| 14.0 ∼ 15.0V(Programmable), default: 14.8V@25°C
Float Voltage| 13.0 ∼ 14.5V(Programmable), default: 13.7V@25°C
Low Volt. Disconnect| 10.8 ∼ 11.8V,S0C1 ∼ 5(Default: 11.2V) (Programmable)
Reconnect Voltage| 11.4 ∼ 12.8V(Programmable)
Overcharge Protect| 15.5V
Temp. Compensation| -4.17mV/K per cell (Boost Equalization), -3.33mV/K per cell (Float)
Lithium| Charging voltage target| 10.0 ∼ 17.0V(Programmable)
Charging voltage recovery| 9.2 ∼ 16.8V(Programmable)
Low voltage disconnect| 9.0 ∼ 15.0V(Programmable)
Low voltage reconnect| 9.6 ∼ 16.0V(Programmable)
0°C Charge Protection| Yes, No, Slow(Lithium, default: Yes)
Panel Para meters| Max input power| 150W @12.8V lithium battery
Max volt on PV terminal| 45V
Dusk/Dawn detect volt.| 3.0 ∼ 8.0V(Default: 5.0V)
Day/Night delay time| 0 ∼ 30Min(Programmable, default: Omin)
MPPT tracking range| (Battery Voltage + 1.0V) _Voc0.9²
Max tracking efficiency| >99.9%
Load| Output Current| 10A
System Parameters| Max charge conversion| 97.%
Communication distance| 10m
Self consumption| 8mA
Dimensions| 85.8 81 23.1mm
Weight| 260g
Ambient temperature| -35∼+60°C
Ambient humidity| 0∼100%RH
Protection degree| IP67
Max Altitude| 4000m

  1. PV panel Voc can not exceed this value, otherwise it will damage the controller.
  2. Voc means the open circuit voltage of the solar panel.

FALCON logo

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>