GOODWAY CTV-1501 Cooling Tower Water Basin Vacuum User Guide

June 12, 2024
goodway

GOODWAY CTV-1501 Cooling Tower Water Basin Vacuum

Product Information

Product Name: CTV-1501
Product Type: Cleaning Tool
Optional Accessory: CTV-F2 Optional Filter
Manufacturer: Goodway
Contact Information: Email: goodway@goodway.com, Website: www.goodway.com

Product Usage Instructions

Priming the CTV-1501

  1. Ensure that the water supply is turned on.
  2. Submerge the cleaning tool under the surface of the water in the cooling tower basin.
  3. Open the prime valve to purge the air from the inlet hose.
  4. Wait until the air bubbles stop.
  5. Go back to the machine and turn the power switch on.
  6. Partially open the outlet valve.
  7. Close the prime valve when a full column of water is flowing.
  8. Begin vacuuming the basin, keeping the cleaning tool under the surface of the water.
  9. If the unit fails to prime, consult the Operating and Maintenance Manual.

Please note that additional safety instructions and guidelines can be found in the Operators Manual. It is important to review and follow these instructions for proper usage and safety.

Note: The CTV-F2 Optional Filter is sold separately and can be used with this product for enhanced performance and filtration.

About Goodway:
Goodway is a manufacturer of HVAC and facility maintenance solutions. For more information about our products and services, please contact us via email at goodway@goodway.com or visit our website at www.goodway.com.

PLEASE REVIEW IMPORTANT SAFETY INSTRUCTIONS LOCATED IN OPERATORS MANUAL

Proper Startup Essentials

GETTING READY

PRIMING THE CTV-1501

  1. With the water supply turned on, submerge the cleaning tool under the surface of the water in the cooling tower basin.
  2. Open the prime valve to…
  3. Purge the air from the inlet hose.
  4. When the air bubbles stop, go back to the machine and turn the power switch on and partially open the outlet valve.
  5. Close the prime valve when a full column of water is flowing. Begin vacuuming the basin, keeping the cleaning tool under the surface of the water. If the unit fails to prime consult the Operating and Maintenance Manual.

HVAC & FACILITY MAINTENANCE SOLUTIONS
GOODWAY® TECHNOLOGIES CORPORATION
420 West Avenue, Stamford, CT 06902 USA
Tel : 203-359-4708 · Toll-Free Tel: 800-243-7932
Fax : 203-359-9601 · Toll-Free Fax: 800-359-9625
Email : goodway@goodway.com
Visit : www.goodway.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals