SBi Double Wall Close Clearance Connector Black Pipe Instruction Manual

June 12, 2024
SBI

SBi Double Wall Close Clearance Connector Black Pipe

Product Information

The Close Clearance Connector Pipe is a double wall black pipe designed for use with solid fuel appliances such as wood stoves, freestanding fireplaces, and furnaces. It meets the requirements of NFPA 211, CSA B365, and ULC S641 Standards. The minimum clearance from the pipe to combustible material is 6 inches, which can be reduced to 5 inches if the assembled pipe sections have no adjustable length. The product is listed and tested following ULC standards as a close clearance connector pipe between the appliance and chimney.

Permits
Before installation, it is recommended to contact local Building and Fire Officials to inquire about permits, restrictions, and installation inspections in your area.

Recommendations & Limitations

  • Use only Double Wall Black Pipe and Listed components. Do not mix with other manufacturers’ products.
  • Do not install damaged connector pipe or components.
  • For installations with offset, a maximum of 15′ (4.5 m) length is recommended. Without offset, do not exceed 20′ (6 m) length.
  • Ensure all sections are solidly fastened together and supported as required.

Product Usage Instructions

  1. Read through the installation instructions provided in this manual before beginning your installation.
  2. Ensure that you have obtained the necessary permits and have complied with local building and fire regulations.
  3. Inspect the Double Wall Black Pipe and Listed components to ensure they are in good condition and not damaged. Do not install if any parts are damaged.
  4. Determine the appropriate clearance required from combustible materials. The minimum clearance to combustible side walls and ceilings is 6 inches. If the assembled pipe sections have no adjustable length, the clearance can be reduced to 5 inches.
  5. Install the Double Wall Black Pipe and Listed components according to the manufacturer’s instructions, ensuring that all sections are securely fastened together.
  6. Support the pipe as required to prevent sagging or instability.
  7. If there is an offset in the installation, ensure that the total length of the pipe does not exceed 15′ (4.5 m). Without offset, do not exceed 20′ (6 m) in length.
  8. After installation, check that all connections are tight and secure.
  9. Test the appliance and chimney to ensure proper operation and venting.
  10. Maintain the required clearances (air spaces) to combustible materials to minimize the risk of chimney-related fires.

Solid fuel
Close Clearance Connector Pipe

INSTALLATION INSTRUCTIONS

A MAJOR CAUSE OF CHIMNEY-RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCES (AIR SPACES) TO COMBUSTIBLE MATERIALS. IT IS OF THE UTMOST IMPORTANCE THAT THIS DOUBLE WALL CONNECTOR PIPE BE INSTALLED ONLY IN ACCORDANCE WITH THESE INSTRUCTIONS.
This Close Clearance Connector Pipe meets the requirements of the NFPA 211, CSA B365 and ULC S641 Standards.
Read through these instructions before beginning your installation. Failure to install according to these instructions will void the manufacturer’s warranty and may have an effect on your homeowner’s insurance and ULC Listing status.

INTENDED USE OF PRODUCT
This close clearance connector is intended for use with solid, including wood stoves, freestanding fireplaces and furnaces. It may be used in any instance where single wall stovepipe is called for.

LISTED CLEARANCE
Double Wall Black Pipe was tested and Listed following the ULC standards as a close clearance connector pipe between (listed) appliance and chimney. The minimum clearance from pipe to combustible material is 6 inches to combustible side walls and 6 inches to combustible ceilings. If the assembled pipe sections have no adjustable length, the clearances to combustible side walls and to combustible ceilings may be reduced to 5 inches.

CLEARANCE COMPATABILITY
Solid fuel appliances have a minimum clearance to combustible construction. The minimum clearance on the appliance must be adhered to. If two clearances are in conflict, always use the larger clearance distance. Certain applications, such as mobile homes, sometimes require clearances greater than 6 inches.

PERMITS
Contact local Building and Fire Officials about permits, restrictions and installation inspection in your area.

RECOMMENDATIONS & LIMITATIONS

  • Every wood-burning stove requires its own separate connector. Connect only one solid fuel burning appliance to a chimney. Do not connect an oil or gas burning appliance to a chimney venting a solid fuel burning appliance.
  • Choose a stove that is listed by an accredited testing agency.
  • For installation and operation follow the stove manufacturer’s instructions and safety manual for maximum efficiency and safety. Over firing can damage both stove and double wall connector pipe. Be certain to maintain required clearances to combustible materials.
  • Burn only the fuels your stove is designed to burn according to the manufacturer’s instructions and safety manual.
  • Do not burn sea driftwood, treated lumber, or plastic.
  • Not all stoves can be used in Mobile Homes. See the manufacturer’s instructions.
  • Do not enclose this Double Wall Black Pipe.
  • This connector is not a chimney. It must NOT pass through floors, attics, closets, walls, or ceilings.

DOUBLE WALL BLACK PIPE

Close Clearance Connector Pipe

PARTS LIST

Part Description Ø 6″ Ø 7″ Ø 8″
Pipe – 6″ Length CVDB0606 CVDB0706 CVDB0806
Pipe – 12″ Length CVDB0612 CVDB0712 CVDB0812
Pipe – 18″ Length CVDB0618 CVDB0718 CVDB0818
Pipe – 24″ Length CVDB0624 CVDB0724 CVDB0824
Pipe – 36″ Length CVDB0636 CVDB0736 CVDB0836
Pipe – 48″ Length CVDB0648 CVDB0748 CVDB0848
Slip Section – 6″ Length CVDB0606SL N/A N/A
Slip Section – 12″ Length CVDB0612SL N/A N/A
Slip Section – 18″ Length CVDB0618SL N/A N/A
Telescoping Section 18″ – 31″ Length CVDB06ST CVDB07ST CVDB08ST
Telescoping Section 25″ – 50″ Length CVDB06MT CVDB07MT CVDB08MT
Telescoping Section 40″ – 68″ Length CVDB06LT CVDB07LT CVDB08LT
Elbow – 45°, Fixed CVDB0645F CVDB0745F CVDB0845F
Elbow – 90°, Fixed CVDB0690F CVDB0790F CVDB0890F
Tee (with cover) CVDB06T CVDB07T CVDB08T
Masonry Adapter CVDB06MA N/A N/A
Vented Stove Adapter CVDB06VSA N/A N/A
Stove Adapter CVDB06SA CVDB07SA CVDB08SA
Damper Section CVDB06DS N/A N/A
Finishing Band (Trim Plate) CVDB06FB CVDB07FB CVDB08FB
Ceiling Hanger CVDB06H CVDB07H CVDB08H
Reducer – 7″ to 6″ (male end – 7″) CVDB76
Reducer – 8″ to 7″ (male end – 8″) CVDB87
Reducer – 8″ to 6″ (male end – 8″) CVDB86
Increaser – 6″ to 7″ (male end – 6″) CVDB67
Increaser – 7″ to 8″ (male end – 7″) CVDB78
Increaser – 6″ to 8″ (male end – 6″) CVDB68
Oval to Round Adapter (8″ oval flue outlet to 8″ round) CVDB08OA

INSTALLATION NOTES

  • Use only Double Wall Black Pipe and Listed components. Do not mix with other manufacturers’ products. Do not install damaged connector pipe or components.
  • While there is no limitation to the total length of Double Wall Black Pipe that may be used for a single installation, except as stipulated in NFPA 211 (USA) or CSA B365 (Canada), we recommend a maximum of 15’ (4.5 m) if there is an offset. Do not exceed 20’ (6 m) without offset. It is important to insure that all sections are solidly fastened together and supported as required.
  • Double Wall Black Pipe is used to connect a solid, fuel fired appliance to a factory built or masonry chimney.
  • The chimney must be installed and connected according to the applicable 2100 insulated chimney manufacturer’s Installation Instructions.
  • In all cases, when pipe is correctly placed and aligned, be sure to securely attach all pipe sections to each other, to the Stove Adaptor, the Tee, Elbow, Wall Thimble, and Ceiling Support connector by drilling at least (3) 1/8” holes and fastening with (3) #8 X 1/2” self-drilling screws in every joint.
  • A Pipe Hanger (F) must be used for any horizontal run over 4 feet long. Use an additional hanger for every 4-foot section thereafter; i.e. 2 per 8 ft. (2.4 m), 3 per 12 ft. (3.6 m), etc.
  • The assembly should be as short and direct as possible between the stove and chimney. The use of two 45-degree elbows is often preferable to a single 90-degree elbow because less turbulence is created in the exhaust flow and they result in less horizontal run.

INSTALLATION PROCEDURE

TO-THE-CEILING INSTALLATION

  1. Position stove and floor shield to conform to the stove manufacturer’s clearance specifications. Position appliance and chimney so as to avoid cutting any ceiling joists, roof rafters, or wall studs.

  2. Install ceiling support box (C) according to the installation instructions in your 2100 insulated chimney kit (D).

  3. Install the Double Wall Black Pipe onto the installed Universal Adapter of the 2100 Chimney Pipe that has been securely installed in the ceiling support box. Attach using (3) #8 X 3/4” self- tapping screws (see Detail A).
    Sbi-double-wall-close-clearance-connector-black-pipe-fittings-
\(1\)

  4. Attach Stove Adapter (A) to stove.1 If needed attach Tee (E) to Stove Adapter using at least (3) #8 X 1/2” self-drilling screws (see Detail B).

  5. Make sure Stove Adapter and/or Tee align vertically with Universal adapter.

  6. Install Pipe Sections (B), Adjustable Telescoping Section (B) between the Tee/Stove Adapter and Universal Adapter

  7. Fasten all pipe sections together, including Telescoping Sections and Slip Sections with at least (3) #8 X 1/2” self-drilling screws.

TO-THE-WALL INSTALLATION

  1. Position stove and floor shield to conform to the stove manufacturer’s clearance specifications. Position the appliance and chimney so as to avoid cutting any ceiling joists, roof rafters, or wall studs.

  2. Install Wall Thimble according to the installation instructions in your 2100 insulated chimney kit.

  3. Install the Black Double Wall Pipe onto the installed Universal Adapter (H) of 2100 Chimney Pipe that has been securely installed through the Wall Thimble. Attach using
    (3) #8 X 3/4” self-tapping screws (see Detail C).

  4. Slide Finishing Band (G) over Universal Adapter up to end of the Double Wall Pipe (see Detail C).

  5. Attach Stove Adapter (A) to stove.2 If needed, attach Tee (E) to Stove Adapter using at least (3) #8 X 1/2” self-drilling screws.

  6. Make sure Stove Adapter and/or Tee align vertically and horizontally with chimney adapter.

  7. Install Pipe Sections (B), Adjustable Telescoping Sections (B) and/or Slip Section (B) to Tee or Stove Adapter using (3) #8 X 1/2” self-drilling screws.

  8. Install two 45° Elbows (I) (recommended installation) or a 90° Elbow (I) (see Detail D) to top of pipe section using (3) #8 X 1/2” self-drilling screws.

  9. Install a Telescoping Section or a fixed length Pipe Section and Slip Section horizontally between Elbow and Universal Adapter using at least (3) #8 X 1/2” self-drilling screws at each pipe joint. Use a Pipe Hanger (F) if needed.

  10. Fasten all pipe sections together, including Telescoping Sections and Slip Sections with at least (3) #8 X 1/2” self-drilling screws.

Sbi-double-wall-close-clearance-connector-black-pipe-fittings-
\(1\)

MASONRY CHIMNEY

Have your chimney inspected by a professional chimney sweep or Fire Department Inspector before connecting to it for use. Masonry chimneys should only be used if they are in good condition and have been built according to NFPA 211 (Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances) in the USA or CSA B365 (Installation code for solid-fuel-burning appliances and equipment) in Canada.

  1. There should be a horizontal opening into the chimney through a non-combustible wall. Fit the Masonry Adapter (J) into this hole. Attach the adapter collar (K) to the masonry wall using screws and masonry anchors (not supplied). Seal the joint between the collar and the masonry wall with a high temperature silicone caulking (see Detail E).
  2. When installing Double Wall Black Pipe into a relined masonry chimney, follow the procedure as above, making sure the masonry adapter slides onto the tee take-off by at least 2 inches. Firmly attach using 3 self-tapping screws or a Quick Connector™ (sold separately).
  3. Attach connector pipe to appliance using previous instructions.3

Sbi-double-wall-close-clearance-connector-black-pipe-fittings-
\(3\)

DOUBLE WALL BLACK PIPE MAINTENANCE

WARNING FOR SOLID FUEL APPLICATIONS
Creosote and Soot-Formation and Need for Removal:
When wood is burned slowly, it produces tar and other organic vapors, which combine with expelled moisture to form creosote. The creosote vapors condense in the relatively cool chimney flue of a slow-burning fire. As a result, creosote residue accumulates on the flue lining. When ignited, this creosote makes an extremely hot fire.

DOUBLE WALL BLACK PIPE CLEANING

  • Access – Double wall connector pipe must be installed so that access is provided for inspection and cleaning.
    Schedule – The double wall connector pipe system must be cleaned and inspected on an annual basis by a chimney professional at intervals of no more than 12 months each,

  • starting at the date of purchase. The connector and chimney should be inspected at least once every month during the heating season to determine if creosote or soot buildup has occurred. If creosote or soot has accumulated, it should be removed to reduce the risk of a chimney fire.

  • Cleaning – It is recommended to clean thoroughly the double wall connector pipe and chimney after every heating season. During summer, the air is damper and with minimal air circulation within the chimney system, it can mix with creosote and/or sooth deposits in the double wall connector pipe and chimney system to form an acid that could accelerate the corrosion process and induce premature decay of the steel. Have your connector and chimney cleaned by a professional chimney sweep. Use a plastic or steel brush.

  • Chemicals – Do not use chemical cleaners. Their use does not eliminate the need for mechanical cleaning and they may be highly corrosive.

  • In Case of Fire – If a flue fire occurs, close all appliance draft openings and call your Fire Department. Do not use the appliance again until the chimney, connector and stove have been inspected by a professional chimney sweep and/or Fire Department Inspector.

SBI VENTING DIVISION LIMITED LIFETIME WARRANTY

– Double Wall Stove Pipe –
The warranty:
The manufacturer’s warranty applies only to the original purchaser and is not transferable. Subject to the conditions and exclusions set forth below, the manufacturer warrants that its products will be free from manufacturing if properly installed. This warranty only covers replacement of defective double wall stove pipe components in a residential installation. This warranty is void if the double wall stove pipe is used in a different application than what it is designed for.

Warranty conditions:
The warranty of the double wall stove pipe and its components are subject to the following conditions:

  1. Brand new products with proof of purchase only;
  2. Products must have been purchased from an authorized Olympia Chimney of Canada dealer;
  3. Installation in accordance with the instructions supplied with this product and all local and national building codes;
  4. Normal use with a residential wood appliance that has been certified by an accredited laboratory: wood fireplace, wood stove, wood furnace or wood boiler;
  5. The double wall stove pipe is designed to operate at a maximum continuous temperature of 650 °C (1,200 °F) or less;
  6. The double wall stove pipe system must be cleaned and inspected on an annual basis by a chimney professional at intervals of no more than 12 months each, starting at the date of purchase and as long as the warranty period applies. Receipts verifying that maintenance was performed must be kept;
  7. Products under this warranty must have been produced after the revision date indicated at the end of this document;
  8. The chimney must have a cap installed;
  9. Parts or components from other manufacturers are not covered by this warranty. Warranty application in the case of a replacement:

| 0 to 10 years 1| 11 to 15 years 1| 16 years and more 1
---|---|---|---
Double Wall Stove Pipe| 100%| 100%| 100%
Supports and brackets
| 100%| 100%| 100%
Labor| 100$2| N/A| N/A

  • Covers perforation only.
  • From date of purchase.

Maximum compensation upon evidence of the original installation and replacement done by a professional. Claim is subject to approval by the manufacturer.
The paint used on the black Double Wall Black Pipe is 100% covered by a 1 year warranty on peeling.
This warranty covers the transportation costs for replacement parts. These will be delivered FOB Saint-Augustin-deDesmaures (Quebec) to your nearest Olympia Chimney of Canada retailer.
The parts covered by lifetime warranty are subject to a limit of one replacement on the useful life of the product.
The manufacturer may, at its discretion, fully discharge all obligations with respect to this warranty by refunding the wholesale price of any warranted but defective parts or supply any replacement parts under warranty without any charge.

Warranty exclusions:
This warranty does not cover:

  1. Labor and installation costs (unless specified by the manufacturer);
  2. Products that have been altered, modified or repaired since shipment from factory;
  3. Products that have been moved from their original installation site;
  4. Any non-stainless components mounted or connected to the chimney or venting system;
  5. Damage (to products, appliances or structure) caused by misuse, abuse, improper installation, lack of maintenance, improper inspection or any other negligence;
  6. This warranty does not cover incidental or collateral damages caused by smoke, fire, flood, strong winds, “acts of God”, or any other contingency beyond the manufacturer’s control;
  7. Use of improper chimney cleaners or any improper solvents/chemicals will void all applicable warranties;
  8. Does not cover any solid fuel other than wood;
  9. Damage resulting from the use of driftwood, pressure-treated lumber, wood containing salt, chemicals, or any prohibited material will void all applicable warranties.

Claim process:
Shall your unit or any component be defective, contact immediately your SBI Venting Division dealer. Prior to your call, make sure that you have the following information necessary for your warranty claim treatment:

  • Your name, address and telephone number;
  • Model name as indicated on the certification label or instruction sheets;
  • Original invoice and dealer’s name;
  • Nature of the defect and any relevant information.

Before shipping your unit or defective component to the manufacturer, you must first obtain a return authorization number. Any merchandise shipped to the manufacturer without authorization will be refused automatically and returned to sender.