Οptional Mounting Methods (Upon Request)
Flag mounting A-1133 SET (only for ZLD-28/24V/ADR/EM, ZLD-34/24V/ADR/EM)
Hanging mounting A-1130, A-1131, A-1132 SET
| Tube
---|---
Α-1130| Α=1m
Α-1131| Α=0.5m
Α-1132| Α=0.25m
Dimensional Drawings (mm)
- ZLD-28/24V/ADR/EM : 290x172x38
- ZLD-34/24V/ADR/EM : 350x242x3
- ZLD-44/24V/ADR/EM: 450x295x38
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
-
b: Central Supply
-
1 : Maintained operation (*)
-
C : Including inhibiting mode
-
G : Internally illuminated safety sign
-
z 1 C C
Maintained operation : The luminaire lights its illumination source, when
it is powered by the mains power supply or not.
Non Maintained operation : The luminaire lights its illumination source,
only in mains power supply’s failure.
Technical Characteristics
LUMINAIRE TYPE| ZLD-28/24V/ADR/EM| ZLD-34/24V/ADR/EM|
ZLD-44/24V/ADR/EM
---|---|---|---
OPERATION VOLTAGE| 15-30V DC| 15-30V DC| 20-28V DC
MAX. POWER CONSUMPTION| 1.6W| 1.8W| 1.9W
MAX. OUTPUT VOLTAGE (U-OUT)| 25V|
SUPPLY CURRENT| 70mA| 75Ma| 80mA
Irated| 120mA| 140mA| 160mA
Prated| 1.1W| 1.3W| 1.5W
WIRE CROSS SECTION| 0.3mm – 3.3mm (22-12AWG)
LIGHT SOURCE| 18 white LEDs| 21 white LEDs| 24 white LEDs
LIGHT SOURCE LUMINOUS FLUX| 150lm| 175lm| 200lm
PRODUCED IN ACCORDANCE WITH| EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ
61000-3-2, ΕΝ 61000-3-3
VIEWING DISTANCE| 16m| 30m| 38m
OPERATION TEMPERATURE RANGE| -30 to 50 C
RELATIVE HUMIDITY| Up to 95%
CONSTRUCTION MATERIAL| Aluminum, Acrylic Plate, ABS/PC
EXTERNAL DIMENSION (L x W x H)| 290 x 172 x 38 mm| 350 x 242 x 38 mm| 450 x
295 x 38 mm
WEIGHT| 650gr| 990gr| 1480gr
GUARANTEE| 3 years
ELECTRONIC CONTROL GEAR| EL
The controlgear is suitable for LED modules only
LED Characteristics
LUMINAIRE TYPE| ZLD-28/24V/ADR/EM| ZLD-34/24V/ADR/EM|
ZLD-44/24V/ADR/EM
---|---|---|---
MANUFACTURER| Olympia Electronics S.A
MODEL NUMBER| 1111153| 1211153| C MODEL NUMBER 1211153 3
VOLTAGE RANGE| 8.5-10.5V DC| 8.5-10.5V DC| 8.7-10.8V DC
NOMINAL POWER| 1200mW| 1400mW| 1600mW
CONNECTIONS| Non reversible connection between main pcb and led module
TEMPERATURE (tc)| 45 C max. across the board
Package Contents
- Luminair
- Mounting accessories
- Manual
General
These luminaires are for indoors use, only (ta 50 C) where emergency luminaires (CBS) are needed. Each luminaire must be permanently connected to mains power supply.
ΑΤΤΕΝΤΙΟΝ
- Operations for installation, maintenance or testing must be done by authorized personnel only
- The device must be connected to the mains power supply through a fuse dependent by the total amount of the line’s power load.
- Set the luminaire’s address before the installation. The luminaire must be connected only to the GR-8600 panel via its ADR line
- Always use in any case round mains cable, with a diameter of 5-10mm (H05RN-F type 2x1mm² or any other type, at least equal to it’s mechanical and electrical properties).
ATTENTION!! The cable must not be deformed in any way (This requirement is important to ensure the ΙΡ rating).
Installation Instructions
SET THE ADDRESS
Set the luminaire’s address by using the dip-switches.
Address | Dipswitch setting |
---|---|
1 | |
2 | |
3 | |
4 | |
5 | |
6 | |
7 | |
8 | |
9 | |
10 | |
11 | |
12 | |
13 | |
15 | |
16 | |
17 | |
18 | |
19 | |
20 | |
21 | |
22 | |
23 | |
24 | |
25 | |
26 | |
27 | |
28 | |
29 | |
30 | |
31 | |
32 |
Surface mounting on a Wall with A-1134 base (Included in the package)
Single sided luminaire
Make the connections installation
Warranty
specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which accompanies each product. This warranty ceases to exist if the buyer does not follow the technical instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods provided or has any repairs or re-setting done by a third party, unless Olympia Electronics has fully agreed to them in writing. Products that have been damaged can be returned to the premises of our company for repair or replacement, as long as the warranty period is valid. Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.com
info@olympia-electronics.gr
Thank you for your trust in our products Olympia Electronics – European manufacturer
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>