olympia electronics BSR-6157 Analogue Addressable Optical Smoke User Manual

June 12, 2024
olympia electronics

Olympia-Logo

olympia Electronics BSR-6157 Analogue Addressable Optical Smoke

olympia-Electronics-BSR-6157-Analogue-Addressable-Optical-Smoke-
product

Product Information

This product is an analog addressable optical smoke and rate-of-rise heat detector with an integrated isolator. It is compliant with EN 54-5:2017, EN 54-7:2018, and EN 54-17:2005 standards. The model number of the product is BSR-6157.

The detector is designed for use in detecting smoke and rate-of-rise heat in various environments. It operates on the Olympia A Protocol and requires a main voltage of 12-30V DC. The standby consumption is 2.5mA (with activated LED), and the alarm consumption is 195mA. The smoke concentration sensitivity is adjustable from 0.107 to 0.300 in 0.010 dB/m steps, while the temperature sensitivity is adjustable from 57 to 90 in 1.5°C steps.

The detector features indicators such as an alarm LED and a remote LED driver. It has a maximum loop current of 1A and a maximum switch current of 5A. The maximum series resistance is 300mΩ, and the maximum leakage current in isolation mode is 25mA pulses (6ms duration every 2sec). The isolation voltage ranges from 8.8 to 11V, and the reconnect voltage ranges from 10.2 to 13V.

The device has a degree of cover protection of IP42 and is constructed using ABS/PC materials. Its external dimensions are approximately 103mm (diameter) x 55mm (height), and it weighs around 160 grams. The product comes with a guarantee of 2 years.

Product Usage Instructions

Setting the Address
Each detector must have a unique address to be recognized by the panel. It is important to ensure that no two devices in the same loop have the same address. To set the address, refer to the user manual of the panel for instructions on how to change the address point.

Installation
When installing the detectors, consider the following guidelines:

  • Place the detectors on the ceiling in visible points without any side obstacles.
  • Avoid installing them in areas with poor ventilation, strong air currents, or high water vapor.
  • Each detector covers an area of 50m², and the distance between two detectors should not exceed 15 meters.
  • Ensure a minimum distance of 50cm between the detectors and fluorescent lamps.
  • Use cables with a diameter ranging from 0.5mm to 2.5mm.

CAUTION: After installation, make sure that the device is not covered with dust or painted. It is essential to prevent anything that could block smoke from reaching the sensor. Take special care during installation and use, as the user assumes full responsibility for proper operation. During site works, use the plastic cover provided to protect the detector from dust.
Note : For detailed instructions and additional features of the device, refer to the complete user manual provided by Olympia Electronics.

|

TECHNICAL CHARACTERISTICS

---|---
CO| COMMUNICATION PROTOCOL| Olympia A Protocol
MA| IN VOLTAGE| 12-30V DC
ST| AND BY CONSUMPTION| 195μΑ
AL| ARM CONSUMPTION| 2.5mA (with activated LED)
SM| OKE CONCENTRATION SENSITIVITY| Adjustable from 0.107 to 0.300 in 0.010 dB/m steps
TE| TEMPERATURE SENSITIVITY| Adjustable from 57 to 90 in 1.5oC steps
IN| DICTATORS| Alarm LED
OU| OUTPUT| Remote LED driver
CL| ASS| A1R/A1S
MA| XIMUM LOOP CURRENT (Ic max, -L in/out)| 1A
MA| XIMUM SWITCH CURRENT (Is max, -L in/out)| 5A
MA| XIMUM SERIES RESISTANCE (Zc max, -L in-out)| 300mΩ
MA IN| MAXIMUM LEAKAGE CURRENT

ISOLATION MODE (IL max, -L in/out)

| 25mA pulses (6ms duration every 2sec)
IS| OLATION VOLTAGE (Vso min-max)| 8.8 – 11
RE| CONNECT VOLTAGE (Vsc min-max)| 10.2 – 13
DE| GREES OF COVER PROTECTION| IP42
PR| ODUCED BY| EN 54-5,EN 54-7, EN 54-17
OP| OPERATING TEMPERATURE RANGE| -40 to 70 οC
RE| NATIVE HUMIDITY| Up to 95%
CO| CONSTRUCTION MATERIALS| ABS/PC
EX| TERNAL DIMENSIONS| 103 (d) x 55 (h) mm
TY| PICAL WEIGHT| 160 gr.
GU| GRANTEE| 2 years

Thank you for your trust in our products Olympia Electronics
European manufacturer

GENERAL

The user has to read carefully the following instructions, to be properly informed and keep them for future use.

The BSR-6157 is an analog addressable smoke detector that integrates functions of optical smoke and heat detection and it can work with any fire panel that supports Olympia A Protocol. It can be adjusted to detect multiple levels of smoke and heat offering flexibility and rich functionality. Also, it integrates a short circuit isolation circuit which is automatically activated and disconnects the defective node from the remaining loop, allowing it to be located by the panel. The detector sends to the main panel an analogue value which depends on the concentration of smoke and heat. The value is 100 in the concentration of 0.107dB/m (small amount of smoke) or a temperature of 57oC and increases proportionally to 120 in the concentration of 0.300dB/m or a temperature of 90oC. When a sudden increase in temperature is detected the detector sends the value of 121.

By default, the panel is set to sound an alarm when the concentration of smoke is 0.091dB/m or the temperature is 57oC. The user can change this setting from the panel for each detector and define any level of smoke concentration or temperature between the lower and the upper limits, specifying the sensitivity of the system depending on the requirements of each site. Also, the user can select A1R or A1S working mode through the panel. They are composed of two parts. A plastic base is placed on the ceiling and the main body of the detector which fits on the plastic base with a simple rotation to the right. The detectors have a 360o visible LED and a remote LED driver which lights up constantly in case of detection of fire, till cancelled from the panel. Also, they stay lit even if the sirens are silenced from the panel, so the detector that

detected the alarm is visible. They are turned off only when a reset command is given from the panel. The indicator LED blinks every 10 sec indicating the connection status with the main panel.

SETTING THE ADDRESS
Each detector must have a unique address, with which it is recognized from the panel. It is forbidden for two devices in the same loop to have the same address. To set it up you can use the function of changing address point as described in the user manual of the panel.

INSTALLATION
The detectors should be placed in the ceiling in visible points without side obstacles, away from places that are barely ventilated or with strong air currents and water vapor. Each detector covers an area of 50 m2 while the distance between two detectors should not be more than 15m. Also, they must be placed at least 50 cm away from fluorescent lamps. The cable diameter should be from 0.5 to 2.5mm.

MAINTENANCE AND FUNCTIONAL TESTING
The detector has fault diagnosis and dust compensation functions, which automatically inform you when replacement or cleaning actions are required. These functions combined with periodic manual testing ensure maximum security level. The manual testing procedure is carried out by spraying a small amount of smoke into the detector with an A-752 spray or a counterpart product. It is suggested to carry out a test every 6 months or after a change in the position of the sensor. A key element of its proper function is the air to be able to freely circulate inside it. So be careful not to block the openings of the outer cover. Before the manual testing, it is suggested to enable the special “walk-in test” mode from the panel.

CAUTION
After installation the device must not be covered with dust or be painted or anything else that will block the smoke from getting to the sensor. Special attention must be given during the installation and the use of the device, since the user assumes full responsibility for proper operation afterward.

Also, during site work place the plastic cover on the detector as shown in the picture below to protect the device from dust.

Additional features of the device:

  • Integration of dynamic algorithms for noise and false alarm rejection.
  • Dust compensation and automatic generation of cleaning notifications. A stable level of detection regardless of the detector’s working hours.
  • Compensation of smoke measurements based on ambient temperature ensures high precision measurements even under extreme environmental conditions.
  • Automatic fault diagnosis.
  • Adjustable smoke and temperature alarm levels for maximum flexibility.
  • 360o optically visible LED.

UID: In every device, there is a double sticker with the UID (Unique Identifier) number. This number is unique for each device.

Installation process

olympia-Electronics-BSR-6157-Analogue-Addressable-
Optical-Smoke-fig- \(7\)

  1. Remove the detector from its base rotating to the left till the side marks are
  2. Fasten the base with the supplied mounting materials (point 5).
  3. Connect the power cables (minding the correct polarity) according to the requirements of the installation (Figure 1, 2).
  4. Place the detector carefully so that the side marks are in the same position and rotate the detector clockwise until it powers the device and after 3-5 seconds it is ready for operation.

CONNECTION

  1. + IN/OUT: Connect to (+L) of the loop.
  2. – IN: Connect to (-L) of the
  3. – OUT: Connect to (-L) of the
  4. – R: External LED
  5. : Connected to the cable’s shield (when the shield is used).olympia-Electronics-BSR-6157-Analogue-Addressable-Optical-Smoke-fig- \(9\)

BSR-6157  rateAnalogue addressable optical smoke mandatory


BSR-6157
Analogue addressable optical smoke and  rate-of-rise  heat  detector with integrated isolator

  • EN 54-5:2017,
  • EN 54-7:2018,
  • EN 54-17:2005
  • DoP: 921615700_59_001

EGINIO PIERIAS 60300 GREECE

WARRANTY

Olympia Electronics guarantees the quality, condition, and operation of the goods. The period of warranty is specified in the official catalog of Olympia Electronics and also in the technical leaflet, which accompanies each product. This warranty ceases to exist if the buyer does not follow the technical instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods provided or has any repairs or re-setting done by a third party unless Olympia Electronics has fully agreed to them in writing. Products that have been damaged can be returned to the premises of our company for repair or replacement, as long as the warranty period is valid.

Olympia Electronics reserves the right to repair or replace the returned goods and to not charge the buyer depending on the reason for defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

HEAD OFFICE:
72nd km. O.N.R. Thessaloniki-Katerini P.C. 60300 P.O. Box 06 Εginio Pierias Greece

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

olympia electronics User Manuals

Related Manuals