BS-530-1-WP Waterproof Siren
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE | 21-28V DC |
---|---|
MAXIMUM CONSUMPTION | 1.2W |
MAXIMUM SOUND OUTPUT in1m | 94dB (sound effect 1) |
ΤYPE OF APPLICATION ENVIRONMENT | Τype B |
MOUNTING | Wall |
DEGREES OF COVER PROTECTION | IP 65 |
PRODUCED IN ACCORDANCE WITH | EN 54-3:2001 +A1:2002 +A2:2006 |
OPERATION TEMPERATURE RANGE | 0 to 60 C |
RELATIVE HUMIDITY | Up to 95% |
CONSTRUCTION MATERIAL | ABS/PC, PC |
EXTERNAL DIMENSIONS | 141 x 141 x 95 mm |
TYPICAL WEIGHT | 230gr. |
GUARANTEE | 2 years |
Thank you for your trust in our products.
Olympia Electronics – European manufacturer.
GENERAL
This device is a sounder for fire detection panels that offer a strong sound
that covers many square metres. It features two inputs (N1, N2) for the
production of two different sounds.
This device can co-operate with any fire detection panel (BSR-2104,
BSR-2114,BS-1632, BS-1634, BS-1636, BS-636).
Installation and Connection
-
First, remove the retaining screw, place a flat blade screwdriver in the holes of the plastic hooks and remove the plastic cover (Image 1 on page 2).
-
Use the supplied mounting parts to install the siren’s base on the wall. Place the plastic plugs and fasten the screws to the mounting holes.
-
Insert the included sealing rings around the respective recesses (image 2,3 page 2).
-
Place the caps and make a hole in the center using a small screwdriver. Pass through the caps the cables to connect the device.
-
The (+N1 or the +N2) terminal block is connected to the (+) output of Alarm-1 or Alarm-2 of the panel and the (-) of the terminal block is connected to the (-) output of Alarm-1 or Alarm-2 of the panel.
Accordingly connect in parallel all the sirens. (The maximum number of sirens depends on the type of the panel). -
To select various sound effects use the dipswitch 1, 2 and 3 and choose the desirable sound effect, according to tables 2 and 3 on page 3.
-
On the last siren of the line, we must connect in parallel with its power cables, the terminal resistor that was removed from the alarm contacts of the panel.
-
Refit the plastic cover until the plastic hooks are securely attached (step 1) and fasten the retaining screw (torque0.6Nm).
-
Test the device after installation.
TABLE 2
Fire Detection Panel connection to +N1
DSW| Nr| Sound effect| Tone in accordance to:| dB| mA
| 0| 970Hz continuous| BS5839-1 :2002 – “evacuate” BS5839 Part 1 1988| 91| 21
| 1| 970Hz (1 sec ON – 1 sec OFF)| BS5839-1 :2002 – “alert” BS5839 Part 1
1988| 94| 22
| 2| From 1200Hz to 500Hz in 1 sec| BS5839-1 :2002 – DIN -Tone DIN33404 Part
3| 90| 22
| 3| From 500Hz to 1200Hz in 3.5 sec – 0.5 sec OFF| NEN2575 (Netherlands)| 87|
31
| 4| 800Hz – 970Hz alternate at 1Hz| BS5839-1 :2002| 91| 29
| 5| Intermittent 2850Hz (0.5 sec ON – 0.5 sec OFF)| IS08201 High Frequency|
82| 27
| 6| 970Hz (0.5 sec ON 970 Hz OFF x3 times +1.5 sec OFF)| IS08201 Low tone –
US Temporal Tone LF| 92| 24
| 7| 2850Hz (0.5 sec ON 2850 Hz OFF x3 times +1.5 sec OFF)| IS08201 High tone
– US Temporal Tone HF| 83| 27
TABLE 3
Fire Detection Panel connection to +N2
DSW| Nr| Sound effect| Tone in accordance to:| dB| mA
| 0| 970Hz (1 sec ON – 1 sec OFF)| BS5839-1 :2002 – “alert” BS5839 Part 1
1988| 94| 22
| 1| 970Hz continuous| BS5839-1 :2002 – “evacuate” BS5839 Part 1 1988| 91| 21
| 2| From 500Hz to 1200Hz in 3.5 sec – 0.5 sec OFF| NEN2575 (Netherlands)| 87|
31
| 3| From 1200Hz to 500Hz in 1 sec| BS5839-1 :2002 – DIN -Tone DIN33404 Part
3| 90| 22
| 4| Intermittent 2850Hz (0.5 sec ON – 0.5 sec OFF)| IS08201 High Frequency|
82| 27
| 5| 800Hz – 970Hz alternate at 1Hz| BS5839-1 :2002| 91| 29
| 6| 2850Hz (0.5 sec ON 2850 Hz OFF x3 times +1.5 sec OFF)| IS08201 High tone
– US Temporal Tone HF| 83| 27
| 7| 970Hz (0.5 sec ON 970 Hz OFF x3 times +1.5 sec OFF)| IS08201 Low tone –
US Temporal Tone LF| 92| 24
WARRANTY
Olympia Electronics guarantees the quality, condition and operation of the
goods. The period of warranty is specified in the official catalogue of
Olympia Electronics and also in the technical leaflet, which accompanies each
product. This warranty ceases to exist if the buyer does not follow the
technical instructions included in official documents given by Olympia
Electronics or if the buyer modifies the goods provided or has any repairs or
re-setting done by a third party, unless Olympia Electronics has fully agreed
to them in writing. Products that have been damaged can be returned to the
premises of our company for repair or replacement, as long as the warranty
period is valid.
Olympia Electronics reserves the right to repair or to replace the returned
goods and to or not charge the buyer depending on the reason of defection.
Olympia Electronics reserves the right to charge or not the buyer the
transportation cost.
HEAD OFFICE
72nd km. Ο.N.R. Thessaloniki-Κaterini
P.C. 60061 Greece
www.olympia-electronics.com
info@olympia-electronics.gr
Certification
The waterproof sounder BS-530/1/WP is certified from H.E.E.Q.A.C. Also
H.E.E.Q.A.C. controls the production under CPR number:
BS-530/1/WP
WATERPROOF SOUNDER 0848
0848-CPR-023
EN 54-3:2001 +A1:2002 +A2:2006