- Package Contents:
- 1 Detector
- 1 Detector Base
- Mounting Accessories
- Manual
- Installation:
- The detectors should be placed in the ceiling in visible points without side obstacles, away from places that are barely ventilated or with strong air currents and water vapor.
- Each detector BSR-6155/MAR covers an area of 100m2 and each detector BSR-6157/MAR & BSR-6160/MAR covers an area of 50m2.
- For distances and mounting points, consult the local/national regulation.
- The detectors must be placed at least 50 cm away from fluorescent lamps.
- Cable cross-section should be from 0.5 to 2.5mm2.
- CAUTION:
- After installation, the device must not be covered with dust or be painted or anything else that will block the smoke from reaching the sensor.
- The user assumes full responsibility for proper operation afterwards.
- UID:
- In every device, there is a double sticker with the UID (Unique Identifier) number. This number is unique for each device.
- Installation Instructions:
- Remove the detector from its base by rotating it to the left till the side marks are aligned.
- Fasten the base with the supplied mounting accessories.
Technical Characteristics:
- Communication Protocol: Olympia A Protocol
- Main Voltage: 12-30V DC
- Standby Consumption: 195
- Alarm Consumption: 2.5mA (with activated on board LED)
- Smoke Concentration Sensitivity: Adjustable from 0.107 to 0.300 in 0.010db/m steps
- Temperature Sensitivity (BSR-6157): Adjustable from 57 to 90 in 1.5C steps
- Temperature Sensitivity (BSR-6160): Adjustable from 57C to 120C
- Indicators: Alarm LED
- Output: Remote LED driver
- Class: A1R/A1S
- Maximum Loop Current (lc max, -L in/out): 1A
- Maximum Switch Current (ls max, -L in/out): 5A
- Maximum Series Resistance (Zc max, -L in/out): 300m
- Maximum Leakage Current in Isolation Mode (lL max, -L in/out): 25mA pulses (6ms duration every 2 sec)
- Isolation Voltage (Vso min-max): 8.8 – 11
- Reconnect Voltage (Vso min-max): 10.2 – 13
- Degrees of Cover Protection: IP42
- Produced in accordance with: EN54-7, EN54-17, EN54-5
- Operating Temperature Range: N/A
- Relative Humidity: N/A
- Construction Materials: N/A
Package Contents
- 1 Detector
- 1 Detector Base
- 1 Mounting Accessories
- 1 Manual
General
The user have to read carefully the following instructions, in order to be
properly informed and keep them for future use.
The BSR-6155/MAR is an analogue addressable smoke detector which integrates
the function of optical smoke detection and it can work with any fire panel
supports Olympia A Protocol. It can be adjusted to detect multiple levels of
smoke offering flexibility and rich functionality. Also, it integrates a short
circuit isolation circuit which is automatically activated and disconnects the
defective node from the remaining loop, allowing it to be located by the
panel.
The detector sends to the main panel an analogue value which depends on the
concentration of smoke. The value is 100 in concentration of 0.107dB/m (small
amount of smoke) and increases proportionally to 120 in concentration of
0.300dB/m.
By default the panel is set to sound an alarm when the concentration of smoke
is 0.107dB/m. The user can change this setting from the panel for each
detector and define any level of smoke concentration between the lower and the
upper limits, specifying the sensitivity of the system depending on the
requirements of each site.
The BSR-6157/MAR is an analogue addressable smoke detector which integrates
functions of optical smoke and heat detection and it can work with any fire
panel supports Olympia A Protocol. It can be adjusted to detect multiple
levels of smoke and heat offering flexibility and rich functionality. Also, it
integrates a short circuit isolation circuit which is automatically activated
and disconnects the defective node from the remaining loop, allowing it to be
located by the panel.
The detector sends to the main panel an analogue value which depends on the
concentration of smoke and heat. The value is 100 in concentration of
0.107dB/m (small amount of smoke) or a temperature of 57oC and increases
proportionally to 120 in concentration of 0.300dB/m or a temperature of 90oC.
When a sudden increase in temperature is detected the detector sends the value
of 121.
By default the panel is set to sound an alarm when the concentration of smoke
is 0.107dB/m or the temperature is 57oC. The user can change this setting from
the panel for each detector and define any level of smoke concentration or
temperature between the lower and the upper limits, specifying the sensitivity
of the system depending on the requirements of each site. Also, the user can
select A1R or A1S working mode through the panel.
The BSR-6160/MAR is an analogue addressable heat detector which integrates the
function of rate-of-rise heat detection and it can work with any fire panel
supports Olympia A Protocol. It can be adjusted to detect multiple levels of
heat offering flexibility and rich functionality. Also, it integrates a short
circuit isolation circuit which is automatically activated and disconnects the
defective node from the remaining loop, allowing it to be located by the
panel.
The detector sends to the main panel an analogue value which depends on the
heat. The value is 100 at 57oC (A1R or A1S) or 89°C (CS) and increases
proportionally to 120 at 90oC (A1R or A1S), or 120°C (CS). When a sudden
increase in temperature is detected the detector sends the value of 121. By
default the panel is set to sound an alarm when the temperature reaches the
lower level of each working mode, namely 57°C (A1R or A1S), or 89°C (CS). The
user can change this setting from the panel for each detector and define any
level of temperature between the lower and the upper limits, specifying the
sensitivity of the system depending on the requirements of each site. Also,
the user can select A1R, A1S, or CS working mode through the panel.
They are composed by two parts. A plastic base which is placed on the ceiling
and the main body of the detector which fits on the plastic base with a simple
rotation to the right. The detectors have a 360o visible led and a remote led
driver which are light up constantly in case of detection of fire, till
cancelled from the panel. Also, they are staying lit even if the sirens are
silenced from the panel, so the detector which detected the alarm is visible.
They are turned off only when a reset command is given from the panel. The
indicator led blinks every 10 sec indicating the connection status with the
main panel.
INSTALLATION
The detectors should be placed in the ceiling in visible points without
side obstacles, away from places that are barely ventilated or with strong air
currents and water vapor. Each detector BSR-6155/MAR covers an area of 100m2
and each detector BSR-6157/MAR & BSR-6160/MAR covers an area of 50m2. For
distances and mounting points consult the local/national regulation. Also,
they must be placed at least 50 cm away from fluorescent lamps. Cable cross-
section should be from 0.5 to 2.5mm2.
MAINTENANCE & FUNCTIONAL TESTING
The detector has fault diagnosis and dust compensation functions, which
automatically informs you when replacement or cleaning actions are required.
These functions combined with periodic manual testing ensure maximum security
level. The manual testing procedure is carried out by spraying a small amount
of smoke into the detector with a testing spray or a counterpart product. It
is suggested to carry out a test every 6 months or after a change in the
position of the sensor. A key element of its proper function is the air to be
able to freely circulate inside it. So be careful not to block the openings of
the outer cover. Before the manual testing it is suggested to enable the
special “walk in test” mode from the panel.
CAUTION !!
After installation the device must not be covered with dust or be painted or
anything else happen that will block the smoke to get to the sensor. Special
attention must be given during the installation and the use of the device,
since the user assumes full responsibility for proper operation afterwards.
Additional features of the device :
- Integration of dynamic algorithms for noise and false alarm rejection.
- Dust compensation and automatic generation of cleaning notifications. Stable level of detection regardless of detector’s working hours.
- Compensation of smoke measurements based on ambient temperature which ensures high precision measurements even under extreme environmental conditions.
- Automatic fault diagnosis.
- Adjustable smoke alarm level for maximum flexibility.
- Adjustable smoke and temperature alarm level for maximum flexibility.
- 360o optically visible LED.
UID:
In every device there is a double sticker with the UID (Unique Identifier)
number. This number is unique for each device.
During site works place the plastic cover to the detector (only for BSR-6155/A & BSR-6157/A) as shown in the picture above to protect the device from dust.
Installation Instructions
Remove the detector from its base rotating to the left till the side marks are aligned.
Fasten the base with the supplied mounting accessories.
Connect the power cables (minding the correct polarity) according to the requirements of the installation. (Figure 1, 2)
CONNECTION
- + IN/OUT : Connect to (+L) of the loop.
- – IN : Connect to (iL) of the loop.
- – OUT : Connect to (-L) of the loop.
- – R : External LED connection
- Connected to the cable’s shield (when shield is used).
Place the detector carefully so that the side marks are on the same position and rotate the detector clockwise until it locks. Power the device and after 3-5 seconds it is ready for operation.
Technical Characteristics
Warranty
Olympia Electronics guarantees the quality, condition and operation of the
goods. The period of warranty is specified in the official catalogue of
Olympia Electronics and also in the technical leaflet, which accompanies each
product. This warranty ceases to exist if the buyer does not follow the
technical instructions included in official documents given by Olympia
Electronics or if the buyer modifies the goods provided or has any repairs or
re-setting done by a third party, unless Olympia Electronics has fully agreed
to them in writing. Products that have been damaged can be returned to the
premises of our company for repair or replacement, as long as the warranty
period is valid.
Olympia Electronics reserves the right to repair or to replace the returned
goods and to or not charge the buyer depending on the reason of defection.
Olympia Electronics reserves the right to charge or not the buyer the
transportation cost.
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece www.olympia-
electronics.com
info@olympia-electronics.gr
Thank you for your trust in our products Olympia Electronics – European manufacturer
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>