olympia electronics GR-795-ST-DUO Emergency Chloe Spot Light Instruction Manual
- June 12, 2024
- olympia electronics
Table of Contents
European
manufacturers GR-795/ST/DUO
SELF TESTING NON-MAINTAINED
EMERGENCY CEILING MOUNTED LUMINAIRE
GR-795-ST-DUO Emergency Chloe Spot Light
Thank you for your trust in our products Olympia Electronics – European manufacturer
Package Contents
1 | Luminaire |
---|---|
1 | Lens Accessories |
1 | Mounting Accessories |
1 | Manual |
2 | Labels for 3 & 8 hours duration |
General
These devices are used indoors (ta 40 C) in places where emergency light is
needed. Each device must be permanently connected to mains power supply.
In normal operation the battery is charging. In case of a mains power supply
failure, the device enters emergency mode and the illumination LED turns on.
When the mains power supply is restored the device turns to normal operation.
Automatic Operational Test
This test is conducted automatically every 15 days and lasts 3 seconds. The
light source and the emergency circuit of the device are tested. The test can
be conducted only if the mains power supply and the battery are connected.
During this test period the light source will light up and the green LED will
flash quickly. The battery must have adequate charge.
Automatic Autonomy Test
The Automatic Autonomy Test is conducted every 6 months and measures the
device’s back up operation and emergency duration. In order to be performed,
the mains power supply should be connected and the battery should be fully
charged.
During this test period the light source will light up and the green LED will
flash quickly. This test lasts for the stated duration. In case the test shows
a battery fault, then the battery needs to be replaced. After the replacement,
the luminaire will charge the
Indications LED Status
GREEN (charge) | RED (Batt./Lamp Fault) | Description |
---|---|---|
Normal | ||
Charging (battery test not possible whilte charging) | ||
Mains off (battery not connected or charger fault) | ||
Battery Test (Duration: 1h, 3h, 8h) | ||
Battery Fault | ||
Light Source Test (Duration: 3s) | ||
Light Source Fault | ||
Battery Fault & Light Source Fault |
Indications
battery. When the charge
is finished, the luminaire will perform an automatic autonomy test which lasts
for the stated duration. If the battery is in good condition then the LED
indicator will turn off.
ΑΤΤΕΝΤΙΟΝ!!!
- Operations for installation, maintainance or testing must be done by authorized personnel only.
- Always use in any case round mains cable, with a diameter of 5-10mm (H05RN-F type 2x1mm² or any other type, at least equal to it’s mechanical and electrical properties). ATTENTION!! The cable must not be deformed in any way (This requirement is important to ensure the ΙΡ rating).
- The device must be connected to the mains power supply through a circuit breaker that is depends on the total line’s power load.
- In case of battery replacement, it must be replaced by the same type, by the manufacturer or a competent person.
- In case of inactive use for a period greater than 2 months, disconnect the battery by pulling out the battery’s connector.
- **** It is common trash bins, they must be discarded only in battery recycling points. Do notincinerate. not allowed to discard batteries into
Note:
| Permanently ON
---|---
| Fast Blink
| Slow Blink
| Off
Dimensions
Lens Installation
Anti-Panic
Escape Route
In order to place
the proper lens (Anti – Panic or Escape Route), first be sure that the
luminaire is not connected in the mains power supply and the battery is
disconnected. Place the proper lens and retaining cover on the luminaire. Be
careful not touch the LED with your hand. In order to change the lens, be sure
that the luminaire is not connected to the mains power supply and the battery
is disconnected. Use a flat bladed screwdriver to remove the retaining cover,
remove the placed lens and insert the new one with its retaining cover.
Be careful not to touch the LED with your hand.
Installation Instructions
- Place a flat blade screwdriver on the 5 marked positions and swift it, pull up gently the bottom cover and remove it.
- Mount the bottom cover on the ceiling, make sure that the light direction is correct (marked in bottom cover).
- The user can select one of the 3 available minimum autonomy durations: 1 hour, 3 hours and 8 hours. The selection must be done while the luminaire is disconnected from AC and battery supplies. The selection is achieved through Switches 2 & 3 of DS1. Switches 1 and 4 are not used. Two additional labels are included in the package, one for 3 hours duration (180) and one for 8 hour duration (480). Depending on the selected duration, the installer must cover the default 1 hour (60) printing with one label that has the required duration. Please take notice of the orientation of the label.
- Pass the mains cable through the hole and connect them to the terminal blocks. L for live wire N for neutral. The ground terminal is for termination purposes only.
- Battery Connection Connect the battery cable to its respective connector on the PCB.
- Refit the luminaire to the bottom cover. Pay attention to the orientation of the luminaire.
NOTE!!
After finishing the installation you must power the luminaire for at least 24
hours in order tcompletely charge the battery. The rated autonomy duration can
be achieved after that time.
Battery Replacement
It can be done only by a competent person and after the mains interruption.
- Disconnect mains.
- Carefully remove the luminaire from the bottom cover. (Step 1 of installation procedure)
- Disconnect the battery and install a new one of the same type and characteristics.
- Refit the luminaire to the bottom cover.
Important notice for the installed luminaires in one area !!!
The installer must connect the battery’s connector first and then should power
the luminaire.
The time between batteries connection must be, at least 1.5 minute.
With this variation, it is ensured that the non synchronized Automatic
Autonomous Tesfor two or more luminaires installed in one area, is not
conducted in the same day.
Note: In case of mains power disconnection for a period of more than two
months, the battery must be disconnected.
Note: In case of battery replacement, this must be replaced with parts of
the same type and characteristics. The replacement must be performed by the
manufacturer or a competent person.
Note: If the supply cable of the luminaire is damaged, it shall
exclusively be replaced by a competent person in order to avoid hazard.
ATTENTION
The light source of this luminaire is not user replaceable. When the light
source reaches its end of life the whole luminaire shall be replaced.
CAUTION : Do not view directly with bare eyes.
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
O:lympia in wOlympia unless the Olympia depending tr
0: Non maintained operation ()
A: Including test device
E: With non-replacable lamp(s) and/or battery
F: Automatic test gear complying with IEC 61347-2-7 denoted EL-T
60: 60 minutes duration
180: 180 minutes duration
480: 480 minutes duration
() Non Maintained operation: The luminaire lights its illumination source,
only in power supply’s failure.
Technical Characteristics
GR-795/ST/DUO
OPERATION VOLTAGE | 220-240V AC / 50-60Hz |
---|---|
MAXIMUM POWER CONSUMPTION | 3.3W / 3.8VA |
MAX. SUPPLY CURRENT | 17mA |
MINIMUM POWER FACTOR (λ) | 0.87 |
U-OUT | 5V |
Prated/Irated | 1.9W / 650mA |
INSULATION BETWEEN SUPPLY & CONTROL TERMINALS | Basic Insulation |
INSULATION BETWEEN SUPPLY & BATTERY CIRCUIT | Basic Insulation |
WORKING VOLTAGE AT WHICH THE INSULATION IS DESIGNED | 500V |
WIRE CROSS SECTION | 2 2 2.5mm (stranded) 4mm (solid) |
BATTERY (NiMH,
4HRMU15/15
)| 4.8V / 1.7Ah
CHARGE TIME| 24 hours
BATTERY PROTECTION| Deep discharge and overcharge protection The control gear
will recharge the battery normally after the test of 22.3
BATTERY SUPPLY CURRENT DURING EMERGENCY| (Vbat=4.8V): 1h: 400-550mA, 3h:
290-405mA, 8h:125-170mA
BATTERY CHARGE CURRENT RANGE| 110-135mA
BATTERY DISCHARGE CURRENT RANGE| 130-550mA
MINIMUM DURATION| 1, 3, 8 hours manually selected (default 1h)
LIGHT SOURCE| 1 White Power LED
EMERGENCY ILLUMINATION| 1h : 300lm 3h : 240lm 8h : 110lm
INDICATIONS| Charge – Fault (Lamp/Battery)
PRODUCED IN ACCORDANCE WITH| EN 60598-1, EN 60598-2-22, EN 55015 EN 61547, EN
61000-3-2, EN 61000-3-3
OPERATION TEMPERATURE RANGE| 5 to 40 o C
CONTROL GEAR MAX. TEMPERATURE:tc| o 80 C at LD4
DEGREES OF COVER PROTECTION| IP40
RELATIVE HUMIDITY| Up to 95%
CONSTRUCTION MATERIAL| ABS/PC
EXTERNAL DIMENSION (L x W x H)| Ø110 x 40mm
WEIGHT| 330gr.
GUARANTEE| 3 years (1 year for the battery)
CONTROL GEAR WITH AUTOMATIC TEST FUNCTION
Controlgear classification in accordance with IEC 62034: with automatic test
function
The controlgear has mains-connected windings of transformer
The controlgear is proof against supply voltage polarity reversal
LED Characteristics
MANUFACTURER | Olympia Electronics S.A. |
---|---|
MODEL NUMBER | 1303225 |
VOLTAGE RANGE | 2.7-2.95V |
NOMINAL POWER | 1.95W |
CONNECTIONS | Built-in main board |
TEMPERATURE (tc) | o 55 C max. across the board |
LED Module Type | BUILD IN |
Warranty
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty is specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which accompanies each product. This warranty ceases to exist if the buyer does not follow the technical instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods provided or has any repairs or re-setting done by a third party, unless Olympia Electronics has fully agreed to them in writing. Products that have been damaged can be returned to the premises of our company for repair or replacement, as long as the warranty period is valid. Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.com
info@olympia-electronics.gr
923795000_09_001
Documents / Resources
|
olympia electronics GR-795-ST-DUO Emergency Chloe Spot
Light
[pdf] Instruction Manual
GR-795-ST-DUO, GR-795-ST-DUO Emergency Chloe Spot Light, Emergency Chloe Spot
Light, Chloe Spot Light, Spot Light, Light
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>