TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE | 21-28V DC |
---|---|
IDLE STATE POWER CONSUMPTION | 1mA |
ALARM POWER CONSUMPTION | 1.5 mA (with indication LED activated) |
SENSITIVITY | 0.120dB/m and 60 oC |
INDICATORS/OUTPUT | Alarm LED/to external LED driver (BS-572) |
CLASS | A2S |
DEGREES OF COVER PROTECTION | IP 20 |
PRODUCED IN ACCORDANCE WITH | EN 54-5, EN 54-7 |
OPERATION TEMPERATURE RANGE | -10 to 60 o C |
RELATIVE HUMIDITY | Up to 95% |
EXTERNAL DIMENSIONS | 103 (diam.) x 48 (height) mm |
TYPICAL WEIGHT | 160gr. |
GUARANTEE | 2 years |
Congratulations for your selection to buy this product. Olympia Electronics – European manufacturers.
GENERAL
Before installing the detector, the user must read these instructions
carefully and store this manual for future reference.
BSR-6057/A is an addressable optical smoke and thermal detector. It co-
operates with BSR1116 and BSR-2100 panels. The device transmits an analogue
value to the panel which depends on the amount of the smoke that there is in
the area. The analogue value is 100 with obscuration rate 0.120dB/m (small
amount of smoke).
The factory setting of the panel is to issue an alarm when the analogue value
is greater than 110.
The user can change from the panel this analogue value from 100 (high
sensitivity) up to 120 (low sensitivity).
At the temperature of 60 C the thermal detector is activated and gives an 120
value.
They have two parts, one plastic base which is installed on the ceiling and
the main unit of the detector which is fastened to the base by a simple
turning to the right.
The detectors have an indication led which lights continuously in case of fire
detection until there is a reset signal from the panel. When we silence the
sirens the LED remains lit to show us the detector that issued the alarm. The
LED goes off when we RESET the panel. The indication led also flashes every 8
sec to indicate good operation.
ADDRESS SETTING
To set each detector’s address you have to use the device BSR-2143 photo. 1.
(refer to it’s instruction manual). After the address setting mark this number
to the sticker on the detector’s base (ADR:XXX). Each detector must have an
address with which it is recognized from the panel.
It`s forbidden for two devices with same addresses to be connect to the same
loop.
OPERATION CHECK
The operation check can be done by spraying a small amount of smoke into the
detector’s chamber. You can use the special smoke device A-752 of our company,
or a similar device.
It is advised to conduct a good operation test every 6 months and every time
the detector position is changed.
It is essential to have good air circulation inside the detector. Therefore
care must be taken so that the vents of the detector are not covered.
NOTE
The detectors must be placed in the ceiling on visible areas with no side
obstacles and away from sides with no air circulation or strong air currents
and vapors. Each detector covers almost 2 50 m and the distance between two
detectors must not exceed 15m. Also the detectors must be placed away from
fluorescent tubes at least 50 cm.
The cables cross section must be from 0.5 to 1.5mm .
ATTENTION
After the device is installed, care must be taken, so that the detector vents
are not blocked by anything (i.e. dust, paint). Failing to do so will prevent
the smoke particles to enter the detection chamber.
After the installation, it is the sole responsibility of the user to maintain
the detector for good operation.
Installation Procedure
- Detach the detector from it’s base by turning it anticlockwise until the side marks are aligned.
- Install the base with the included mounting parts (point 5).
- Connect the power cables (respect to polarity) according to the installation requirements (figure 1,2).
- Place carefully the detector, so as to align the side marks and turn it clockwise all the way.
Power the device and after 3-5 seconds will be ready to operate.
CONNECTION
- IN-OUT -L: It is connected to the loop’s (-L).
- IN +L: It is connected to the loop’s (+L).
- OUT +R and -R : It is connected with BS-572.
Certification
The Addressable rate of rise heat detector BSR-6057/A is certified from DEDAL.
Also DEDAL. controls the production under CPR number:
WARRANTY
Olympia Electronics guarantees the quality, condition and operation of the
goods. The period of warranty is specified in the official catalogue of
Olympia Electronics and also in the technical leaflet, which accompanies each
product. This warranty ceases to exist if the buyer does not follow the
technical instructions included in official documents given by Olympia
Electronics or if the buyer modifies the goods provided or has any repairs or
re-setting done by a third party, unless Olympia Electronics has fully agreed
to them in writing. Products that have been damaged can be returned to the
premises of our company for repair or replacement, as long as the warranty
period is valid.
Olympia Electronics reserves the right to repair or to replace the returned
goods and to or not charge the buyer depending on the reason of defection.
Olympia Electronics reserves the right to charge or not the buyer the
transportation cost.
HEAD OFFICE
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60061 Greece
http://www.olympia-electronics.com/
info@olympia-electronics.gr
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>