olympia electronics GR-290/M Self Testing Non-Maintained Emergency Ceiling Mounted Luminaires Instruction Manual

June 12, 2024
olympia electronics

Instruction Manual

European Manufacture

GR-290/M Self Testing Non-Maintained Emergency Ceiling Mounted

Luminaires

TECHNICAL CHARACTERISTICS (for LED MODULE specifications see page 5)

  GR-290/M GR-291/M GR-292/M GR-293/M
OPERATION VOLTAGE 220-240V AC / 50-60Hz
MAX. SUPPLY CURRENT 19.5mAAC
MAXIMUM POWER CONSUMPTION 4.3W / 4.7 VA
MINIMUM POWER FACTOR (A) 0.9
U-OUT 6V
BATTERY 4.8V/1.2Ah, NiMH (4KRMT 15/51)
INSULATION BETWEEN SUPPLY & CONTROL TERMINALS Basic insulation
INSULATION BETWEEN SUPPLY& BATTERY CIRCUIT Basic insulation
WORKING VOLTAGE AT WHICH THE INSULATION IS DESIGNED 500V
BATTERY PROTECTION Deep discharge and overcharge protection
BATTERY VOLTAGE RANGE 4-6V
BATTERY SUPPLY CURRENT DURING EMERGENCY (Vbat=4.8V):500mA I (Vbat=4.8V):230mA
BATTERY CHARGE CURRENT RANGE 130 – 200mA (normal charge) / 20 – 30mA (trickle

charge)
BATTERY DISCHARGE CURRENT RANGE| 400 – 600mA| 180 – 300mA
INDICATIONS – CONTROLS| Charge, lamp fault, battery fault
CHARGE TIME| 24 hours
MINIMUM DURATION| 1.5 hour| 3 hours
LIGHT SOURCE| 1 white power LED
EMERGENCY ILLUMINATION| 300Im| 150lm
DEGREES OF COVER PROTECTION| IP40
PRODUCED IN ACCORDANCE WITH| EN 60598-1, EN 60598-2-22, EN 55015, EN 61547, EN 61000-3-2, EN 61000-3-3
OPERATION TEMPERATURE RANGE| 5 to 40 °C
Prated/Irated| 2.1 W/660mA| 1 W/320mA
CONTROL GEAR MAX.TEMPERATURE (tc)| 65°C at Q2
RELATIVE HUMIDITY| Up to 95%
CONSTRUCTION MATERIAL| ABS/PC
EXTERNAL DIMENSION| 0125 x 65 mm
WEIGHT| 442gr.
GUARANTEE| 3 years (1 year for the battery)
TEST CONTROL FUNCTION GEAR WITH AUTOMATIC| EL-T

Controlgear is suitable for LED module only
The controlgear has mains-connected windings of transformer
Do NOT stare at operating light source.The luminaire should be positioned so that prolonged staring into the luminaire at a distance closer than 0.4m is not expected.
Ethr = 718 lux.
Thank you for your trust in our products
Olympia Electronics – European manufacturer
GENERAL
This device is used indoors (ta 40 C) in places where emergency luminaires are needed. Each device must be permanently connected to mains power supply. The luminaires GR-290/M and GR-292/M are suitable for corridors lighting and the GR-291/M and GR-293/M for open area lighting. In normal operation the battery is charging. In case of a mains power supply failure, the device enters emergency mode and the illumination LED turns on. When the mains power supply is restored the device turns to normal operation.
Manual Operational Test
This test can be done by pushing the test button.
The light source and the emergency circuit of the device are tested. The manual test can be conducted only if the mains power supply and the battery are connected. During this test period the LAMP TEST LED will blink. The battery must have adequate charge. This test lasts for 3 seconds.
Manual Autonomy Test
A duration test can be conducted by pushing thebutton steadily for 5 to 10 seconds. In order to be performed, the mains power supply should be connected and the battery should be fully charged.
The luminaire enters emergency mode, the CHARGE LED is turned OFF and the BATTERY FAULT LED starts blinking. Its duration is the stated autonomy duration of the luminaire. If at the end of the test the autonomy is lower than the nominal, the BATTERY FAULT LED will lit and battery needs to be replaced. If the result of the test is good then the luminaire enters charging mode and the CHARGE LED starts blinking until the battery is fully charged.
Automatic Operational Test
This test includes all the operations that are provided in Manual Operational Test and is conducted automatically every 15 days and lasts 3 seconds.
Automatic Autonomy Test
The Automatic Autonomy Test is conducted every 6 months and measures the device’s back up operation and emergency duration. This test includes all functions of the Manual Autonomy Test.
ΑΤΤΕΝΤΙΟΝ!!!

  1. Operations for installation, maintainance or testing must be done by authorized personnel only.
  2. The device must be connected to the mains power supply through a fuse dependent by the total amount of the line’s power load.\
  3. The replacement of the battery and the light source must be done using parts of the same type, by the manufacturer or by a competent person.
  4. In case of inactive use for a period greater than 2 months, disconnect the battery by pulling out the battery’s connector.
  5. **** It is not allowed to discard batteries into ti common trash bins, they must be discarded only in battery recycling points. Do not incinerate.

NOTE: LED= Light Emitting Diode LABELING EXPLANATION:
X: Self contained
0: Non maintained ()
A: Including test device
F: Automatic test gear complying with IEC 613472-7 denoted EL-T
90: 1.5 hour duration
180: 3 hour duration
0X A F 1 8 0
(
) Non Maintained operation: The luminaire turns on illumination source, only in case of power supply failure.
Connectors:
CN1: Power supply & communication signals
CN5: Battery connector
CN2: Non user connector
CN3: Non user connector
Status of LEDs

LEDs Description of indication
CHARGE : Battery charging, : battery charged, : disconnected or unfunctional

battery
LAMP FAULT| : Operation check, : lamp fault, : normal operation
BATT. FAULT| : Autonomy test, : battery fault, : normal operation
Note| : Blinking, : constantly on, : off

INSTALLATION INSTRUCTIONS

BEWARE of electric shock after reflector removal. Controlgear relies on the luminaire for protection against electric shock.

  1. Untighten the screw and pull up the reflector.

  2. Always use in any case round mains cable, with a diameter of 5-10mm (H05RN-F type 2x1mm² or any other type, at least equal to it’s mechanical and electrical properties). ATTENTION!! The cable must not be deformed in any way (This requirement is important to ensure the ΙΡ rating).
    Install the included gaskets in to the cable entry holes (verify that are not deformed). Make a hole in the center by using a small screwdriver. Pass the round cable through the gasket. Detach the power terminal, connect the wires as shown in the picture and attach the power terminal (10A max). Supply voltage polarity is irrelevant.

  3. Place the battery’s connector to the corresponding connector on the PCB. Beware of correct polarity.

  4. Refit the reflector (mind the correct orientation), tighten the screw securely and the luminaire is ready for mounting.
    NOTE!! After finishing the installation you must power the luminaire for at least 24 hours in order to completely charge the battery. The rated autonomy duration can be achieved after that time.

Battery replacement.
It can be done only by a competent person and after the mains interruption.

  1. Remove the luminaire from the suspended ceiling (figure 3).
  2. Follow the step 1 of the installation instructions.
  3. Disconnect the connector and remove the old battery.
  4. Connect the new battery with the same type (step 3 of the installation instructions) and place it in the position of the old one.
  5. Replace the removed parts (step 1 and 4) and power the device.

Important notice for the installed luminaires in one area !!!
The installer must connect the battery’s connector first and then should power the luminaire.
The time between batteries connection must be, at least 1.5 minute.
With this variation, it is ensured that the non synchronized Automatic Autonomous Test for two or more luminaires installed in one area, is not conducted in the same day.

MOUNTING THE LAMP IN SUSPENDED CEILING

Set up the lamp to the suspended ceiling as it is shown bellow (Required opening 110mm):
Step 1
Bend the springs, to get into the hole of the suspended ceiling, as you can see to the next figure. Step 2
Push up the luminaire, as shown in figure 2. Step 3
Continue to push upwards until the lamp locks. If you want to pull off the device, put a flat blade screwdriver, between the device and the ceiling.

SURFACE MOUNTING

Step 1. Follow the step 1 of the installation instructions.
Step 2. Unfasten the retaining screw (Figure 4) and detach the part for suspended ceiling installation.
Step 3. Drill 2 holes on the base using a 4mm drill bit in order to permit the retaining screws to pass. Mark these two drilled points on the required mounting location, drill the holes and install the supplied plastic plugs. ATTENTION!! Especially for the GR-290/M and GR-292/M luminaire installation on the ceiling you must align the base with the indications on the luminaire’s base (Figure 5).
Step 4. Next use the screw to fasten the unit to the surface (Figure 6).
Step 5. Install the decorative rim (package included). Next, use the 2 fasteners to install the unit to the require location.
Step 6. Follow the step 2 of the installation instructions.

LED MODULE CHARACTERISTICS

| GR-290/M| GR-291/M| GR-292/M GR-293/M
Manufacturer| Olympia Electronics S.A.
Model Number| 405185
Voltage Range| 2.7-3.3V DC
Nominal Power| 2.1W| 1W
Connections| Non reversible connection between main pcb and led module
Temperature (tc)| 60 °C max. across the board
LED Module Type| BUILT IN

CAUTION : Do not view directly with bare eyes.
The light source contained in this luminaire shall only be replaced by the manufacturer, or his agent, or a similar qualified person.
NOTE! The light source is non-user replaceable.
WARRANTY
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty is specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which accompanies each product. This warranty ceases to exist if the buyer does not follow the technical instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods provided or has any repairs or re-setting done by a third party, unless Olympia Electronics has fully agreed to them in writing. Products that have been damaged can be returned to the premises of our company for repair or replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.
HEAD OFFICE
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.com
info@olympia-electronics.gr

923293003_09_007

Documents / Resources

| olympia electronics GR-290/M Self Testing Non-Maintained Emergency Ceiling Mounted Luminaires [pdf] Instruction Manual
GR-290-M, GR-291-M, GR-292-M, GR-293-M, GR-290 M, GR-291 M, GR-292 M, GR-293 M, GR-290 M Self Testing Non-Maintained Emergency Ceiling Mounted Luminaires, Self Testing Non-Maintained Emergency Ceiling Mounted Luminaires, Non- Maintained Emergency Ceiling Mounted Luminaires, Emergency Ceiling Mounted Luminaires, Ceiling Mounted Luminaires, Luminaires
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

olympia electronics User Manuals

Related Manuals