olympia electronics BS-536 Conventional Manual Call Point Instruction Manual

June 12, 2024
olympia electronics

olympia electronics BS-536 Conventional Manual Call Point

olympia electronics BS-536 Conventional Manual Call Point-
PRODUCT

Product Information

  • Product Name: BS-536 Manual Call Point
  • Operation Voltage: 10-30V DC
  • Alarm Current: 8-30mA
  • Alarm Resistor: 470ohms
  • Use Type: Indoor Type A
  • Degrees of Cover Protection: IP 20
  • Produced in accordance with: EN 54-11
  • Operation Temperature Range: -10 to 70 oC
  • Relative Humidity: Up to 95%
  • Construction Materials: ABS/PC
  • External Dimensions: 98 x 94 x 58 mm
  • Typical Weight: 180gr.
  • Guarantee: 2 years

Product Usage Instructions

  1. First, unfasten the retailing screws and remove the plastic cover.
  2. Remove carefully the interior parts of the device.
  3. Use the supplied mounting parts to the A-A or B-B positions (refer to Figure 2).
  4. During installation, ensure that the distance between two buttons does not exceed 30 m.
  5. All buttons should be placed at a height of about 1.4 m from the floor (refer to Figure 1).

Note: Please refer to the provided figures for visual guidance during installation.

TECHNICAL CHARACTERISTICS

olympia electronics BS-536 Conventional Manual Call Point-
FIG4

Thank you for your trust in our products Olympia Electronics – European manufacturer

GENERAL

  • This is an emergency fire alarm button. Use this call point to manually activate the alarm system at the sight of fire. It is essential for it to exist in cooperation with other detectors. Using it is very simple. All you have to do is push the see-through plastic cover and the call point automatically activates the alarm system.
  • In this case the see-through plastic cover does not brake but it can be reset to it`s original position with the special plastic key which is included.
  • This way you can test a specific call point and maintenance the fire detection panel as well.
  • It is used as a signal to evacuate the building in case of fire.
  • In every fire detection system it is essential that you place one call point besides the control panel and the rest mainly in corridors and exits of the building.

Installation and Connection

  1. First, unfasten the retailing screws and remove the plastic cover.

  2. Remove carefully the interior parts of the device and use the supplied mounting parts to the A-A or B – B positions (Figure 2).

  3. During their installation must be attention taken that the distance between two buttons does not exceed 30 m and all buttons should be placed at a height of about 1.4 m from the floor.(Figure 1).

  4. Inside the call point there are four special terminal blocks with indications IN and OUT used to fasten the cables. The connection is made direct to the zone of the control panel regardless of polarity. If in a zone there are more than one then they are connected in parallel. If in the same zone there are detectors then the call point is connected in parallel with the detectors of this specific zone.
    If the last device installed on a zone is a call point then you must place on it the resistor which was removed from that zone. The Figure 4 below shows the connections between two call points and a detector to a zone of a fire detection panel It also shows the connection of the resistor to the last button of that zone.

  5. Reinstall the parts which have been removed during the previous steps and the device is ready to operate.

olympia electronics BS-536 Conventional Manual Call Point-
FIG1

Recovery Procedure
Insert the supplied plastic key into the input (Figure 1) rotate by 90 ° and pull it until the call point will be reset to it`s original position.

WARRANTY

Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty is specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which accompanies each product. This warranty ceases to exist if the buyer does not follow the technical instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods provided or has any repairs or re-setting done by a third party, unless Olympia Electronics has fully agreed to them in writing. Products that have been damaged can be returned to the premises of our company for repair or replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.