OLYMPIA BS-304 Gas Detection Panel Instruction Manual
- June 12, 2024
- OLYMPIA
Table of Contents
OLYMPIA BS-304 Gas Detection Panel
Product Information
The BS-3XX panel series are gas detection panels manufactured by Olympia Electronics. These panels come in four different models: BS-304, BS-308, BS-312, and BS-316. They are designed to support up to 16 inputs for gas detection. Each input can be connected to a single gas detector with a 4-20 mA output.
The panel features a liquid crystal display (LCD) and a series of indication LEDs that provide information about its status. The LEDs include the General Alarm indicator (red), Disable Point indicator (yellow), Test indicator (yellow), General Fault indicator (yellow), Power indicator (green), and Fault Battery indicator (yellow).
The panel also has different access levels, with Level 1 offering two functions. Pressing key number 1 silences the internal buzzer in the event of an Alarm or Fault condition. Pressing key number 2 (lamp test) conducts a sequential LED and Display test when the panel is in standby mode.
The LCD screen displays various information about the system, including the panel name, technician information, and the condition of each sensor input.
Operation instructions
Thank you for purchasing this product of Olympia Electronics. A European
manufacturer.
This section contains general information and information regarding the use of
the panel. All users of the panel should read these instructions very
carefully in order to be able to act in the event of an alarm or a fault
condition.
Description
The BS-3XX panel series are gas detection panels with 4, 8, 12 or 16
inputs. On each input it can be connected only one gas detector 4-20 mA.
Indications and Controls
The panel incorporates one liquid crystal display (LCD) and a series of
indication LEDs that informs the user about its status. The indication LEDs
give general information (i.e. if an alarm becomes true, then the general
alarm indicator LED will turned ON.) and on display appears information about
each event ( i.e. Alarm sensor 1,that means alarm from sensor 1) .
Under the display there are 6 buttons for controlling the panel. On each button there is a number 1-6 and corresponds to the functions left, right, up, down, enter, escape (exit or one step back). Generally by pushing a button one action happens immediately or one menu appears with some functions. Inside the menu the buttons 1, 2, 3, 4 operate as dimension buttons and we can move inside the menu, the button 5 (enter) to select and button 6 (esc) to come back. During the next pages we will refer to the buttons using the corresponding numbers.
All LEDs are grouped for easier indication. In detail the LEDs show the following:
General Alarm (RED) | General Fault (Yellow) | |
---|---|---|
General alarm indicator | Lights in the event of a Fault |
Disable Point (Yellow)| | Power (Green)
Lights to show a disabled inputs| General operation indicator of the panel
|
Test (Yellow)| Fault Battery (Yellow)
Lights to show that we are in TEST mode| Lights to show a battery problem
Access level
This level contains 2 functions that can be implemented by pressing a single key.
- In the event of an Alarm or Fault condition, if the key number (1) is pressed then the internal buzzer is silenced. For as long as the event is in effect the internal buzzer sounds once in every 30 seconds. Should the panel see a new event in this state then the buzzer will start to sound continuously.
- When the panel is in standby mode (no alarm or fault events have occurred) then if the key number (2) (lamp test) is pressed the system conducts a sequential LED and Display test.
When the system is in quiescence state, the lcd screen shows info about the system. The below screen shows some information about the system
The below screen shows the panel name and the technician information.
The next screen shows the condition of each sensor (input)
The sensors 4-20mA incorporates the current have the next situations:
- FAULT – (<1 mA)
- UNDERFLOW (from 1 to 3.5 mA)
- NORMAL (from 3.5 to 21 mA) inside these limits we can do the setup of alarm 1, alarm 2 and alarm
- OVERFLOW (from 21 to 24mA)
- FAULT+ (24mA and Higher).
There is the disable situation (ΝΟ CONFIGURATION)
In case alarm or fault the LCD display shows the corresponding message.
Events Menu
All the events of the system can be shown by pressing the key “3” View Events and then the key Enter.
Access level 2 (User access level)
All the functions of access level 2 can be accessed from a menu that is
displayed when we push the button “4″ User menu.
To Reset the panel, from the central menu, we press button “5” and button
“ENTER” and the next message is displayed.
The user code is 1-1-1-1.
So the key “1” must be pressed four times. After this the panel resets.
Installation instructions
In this section there is information about the connectivity of panel, its peripherals, the programming of all the functions and troubleshooting. All installers who want to connect and enable the gas detection panel must read this manual carefully. The whole knowledge of the panel and its peripherals is necessary for work and installation.
Security
The panel cannot be installed correctly if the installation guide is not read.
This product must be installed, operated and maintained by skilled technician:
- Using all rules of electrical product installation in buildings.
- Installation guide.
- The operation voltage is 100-240V AC / 50-60Hz.
- Must be connected to the electrical panel of the building, but with a separate fuse.
Mounting
The mounting of panel must be in a visible place with easy access by the
users. The panel BS-316 is a product for easy wall mounting and indoor use.
The mounting on the wall can be done by using plugs and screws that are
included in the panel package.
Description of the internal parts of the panel
Cabling
After plastic glands are removed place special gaskets in order to protect the
cable.
The panel has pre-opened passages from where the installation cables will
enter the panel.
The terminal blocks of the panel are capable of handling cable with a cross-
section of up-to 2.5mm.
Connecting the panels with the mains power supply (230V AC) and with the
batter y
To connect the cable with the mains power supply, a cable with double
insulation must be used. The connection is done using the special terminals
found on the right side of the panel as shown in the.
The battery can be placed on the bottom side of the panel.
The battery Α-986 of olympia electronics can be used. The charging circuit of
the panel is also calculated for the specific battery type. In case of
replacement, the new battery must be of the same type.
Two cables with connectors are used to connect the battery to the panel. The black cable is connected to the negative pole of the battery (marked with (-) or with black color) and the red cable is connected to the positive pole of the battery (marked (+) or with red color).
Warnings
- During the installation, the connections to the mains power supply and the battery must be done after all other connections are finished.
- The panel connection with the mains supply must be done via a 16A external fuse or an automatic circuit breaker rated at 16A.
- Always use cables with double insulation.
- The diameter of the cable must be at least 1mm.
- The inner insulation of each cable must not be cut more than 1cm
- The outer insulation must not be cut more than 1cm away from the internal insulation.
Sensor connectivity
Before connecting any sensor to the panel, the main power supply must be
disconnected. There are two ways of connect the sensors depending on the
number of contacts.
NOTE: For both following detector connections, ferrite must be applied on each detector input cable, inside the panel, to meet compliance standards of EN61000-6-1 & EN61000-6-3. Ferrites are included in the package.
Sensors with 3 contacts 4÷20mA
The connection of sensors with 3 contacts 4÷20mA, must be between «+», «-» and
“S” of sensor that correspond to «+», «-» and “S” of panel as shown in figure
5.
Figure 4: Connection diagram with three pad sensor
The cross-section of the cable depends on the cable length (see next table). The sensors with 3 contacts do not require coaxial cables.
Sensor series with three contacts
Ranges| Cable type
From 0 to 300 meters| 3 x 0,75 mm²
Up to 400 meters| 3 x 1 mm²
Up to 500 meters| 3 x 1.5 mm²
Up to 600 meters| 3 x 2.5 mm²
AUX INPUT (AUXILIARY RELAY)
On the AUX input we can connect fire detection buttons between inputs «-» and
“S” of (Figure 5).
Output connectivity
On the panel there are up to 16 programmable outputs relay. Each relay has a
triple connector NO, NC, C. For more information about output setup see
paragraph 2.7.1.
Other outputs and their use
The panel has the following outputs:
-
Output AUX. This is an auxiliary power output (between «-» and «+») that has the capability of providing 20Vdc for maximum load of 300mΑ.
NOTE The maximum drawn from output “AUX” must not be more than 300mA. -
Connectors F_OUT. Open collector output. If there is a general fault (Fault) it is enabled (0V).
Network connection
- It is possible to have network of panels. In each network, each panel has a unique address.
- The central panel has address 1 and sub-panels have address from 2 to 16. The figure below shows the network connection.
- The interface cable is two cable twisted. The connection topology is parallel, for example should the cable from one table to go to another and there are no interconnections
- Caution resistors 120Ohm / 0,5 W should be placed at the beginning and end of the cable.
Technician menu
Access Technician menu
All the functions of access level 3 can be accessed from the menu that
displayed when we press button “5″ in the technician menu.
The panel prompts for the technician code
The technician code is 2-3-3-3.
After the code in entered, the operator has access to level 3 functions.
Configuration: In the configuration menu the technician can configure the sensors, the relays and the zones.
Sensor configuration
The available options in the configuration sensor menu, are shown below,
with Setup you can setup a sensor from scratch, with Copy you can copy the
setup from one sensor to another and with Delete you can delete the setup of a
sensor.
If you choose the setup a sensor the next screen is shown:
where you can choose which sensor you want to setup.
The above picture shows the menu to setup a sensor. With the help of the first selection “LOAD SETUP SENSOR” the defaults values are loaded to the variables of the sensor.
The variables above are:
- NAME: the name of the sensor. You can put up to 20 characters.
- UNIT: Units to meter the gas. There are two kinds of units in ppm or %LIE or %.
- INCREASING: if the value is increasing or decreasing.
- ZERO: Minimum (start up of scale). Default is 0.
- RANGE: Maximum (maximum value of scale). The value range is from 20 to 300.
- ALARM 1 : Alarm 1 level.
- ALARM 2 : Alarm 2 level.
- ALARM 3: Alarm 3level.
- RELAY ALARM 1: the relay that will be activated when there is an Alarm 1 level at the sensor.
- RELAY ALARM 2 : the relay that will be activated when there is an Alarm 2 level at the sensor.
- RELAY ALARM 3: the relay that will be activated when there is an Alarm 3 level at the sensor.
- RELAY FAULT: the relay that will be activated when there is a fault at the sensor.
- ZONE: the zone of the sensor.
At next table we can see some typical values.
Type| Gas| Zero| Limit| Unit| Alarm 1| Alarm
2| Alarm 3
---|---|---|---|---|---|---|---
TS282KG| LPG| 0| 20| %LIE| 7| 10| 20
TS282KM| Methane gas| 0| 20| %LIE| 6| 10| 20
TS282EC-S| Carbon Monoxide| 0| 300| ppm| 25:50| 100| 200
TC282EA| Ammonia| 0| 300| ppm| 10| 20| 50:100
TS293KG| LPG| 0| 20| %LIE| 7| 10| 20
TS293KN| Methane gas| 0| 20| %LIE| 6| 10| 20
TS293EA| Ammonia| 0| 300| ppm| 10| 20| 50:100
TS293EO| Oxygen*| 0| 25| %| 18| 19| 22
TC-100N/LPG| LPG| 0| 100| %LIE| 8| 12| 20
TC-100N/CNG| Methane gas| 0| 100| %lie| 8| 12| 20
The parameter increase must be set to NO.
To connect other detector except these of our catalogue, contact our technical
support.
Relay programming
All the relays of panel are programmable for connecting any application. The relay programming options in the configuration of relay menu are shown below,
with Setup you can setup the relay from scratch, with Copy you can copy the setup from one relay to another, and with Initialise you can load the default values.
The above diagram shows the menu for the configuration of a relay:
The parameters are:
- DELAY ON : it is the delay time (max 250 seconds) of the output activation from the moment when the gas concentration is in the alarm setting.
- DELAY OFF : it is the delay time (max 250 seconds) of the output deactivation from the moment when the gas concentration returns under the alarm setting.
- TIME ON : it is the maximum time (max 250 seconds) of the output activation when the sensor is in an alarm condition. After this time the relay is deactivated.
- LOGIC CONTACT : it indicates if the relay works normally activated (Positive Logic) (NC) or normally deactivated (Negative Logic) (NO).
- LATCHED OUTPUT: it indicates if you want to keep the output active even if the gas concentration returns under the alarm setting.
Zones configuration
Below is the zone menu
Information menu
From this selection the technician can be informed for all the system. The
below diagram shows the menu
-
An example of the information of a sensor screen are.
The above left screen shows the number of the sensor, the condition (FAULT -), the current consumption and the name of the sensor.
The right screen shows the ZERO, RANGE, ALARM1, ALARM2,ALARM3, RELAY ON ALARM1, RELAY ON ALARM2, RELAY ON ALARM3, RELAY ON FAULT and ZONE respectively.
To change the sensor, use the button “3” or “4”. -
An example of the information relay screen is the above screen shows the delay on, delay off, time on and positive logic respectively To change the relay, use the button “3” or “4”. To change the relay, use the button “3” or “4”.
-
An example of the battery information
-
An example of the main supply information
-
An example of the VCC voltage
Parameters menu
The parameters menu is for configuration of the general parameters of the
system.
The selections are:
- SCREEN BACKLIGHT: “ CONTINUOUS” means that the screen panel is lighting continually (this selection reduces the autonomy of the system) “NO CONTINUOUS” means the backlight of the display will be ON when there are events or one button is pressed.
- BUZZER AT FAULT : “NO SOUND” no sound if there is a fault only on alarm. “SOUNDS” the panel buzzer sounds on alarms and on faults.
- ADDRESS PANEL: we can change the address of the panel
If we put address 0 the network is disabled. If the address is the panel is a master panel. If the the address is from 2 to 16 the panel is a subpanel.
- NETWORK DETECTION: if the panel is a master panel ( address 1) we can make a network detection.
- FACTORY DEFAULTS: Load factory defaults to the panel.
- CHANGE LANGUAGE: change the language of the screen ( Greek or English)
- ADJUST HOUR : adjust the time of the panel
- DATE ADJUST : adjust the date of the panel.
- DELETE RECORD : this option deletes all the recorded events from memory.
- PANEL NAME : the name of the panel with a maximum of 20 characters.
- TECHNICIAN INFO: change the technician information with a maximum of 20 characters
Enable menu
The enable menu is used to enable a sensor or all the sensors:
Disable menu
This menu is used to check the hardware of the pane
- On Check sensors the below screen appears to see the other sensors press “3” or “4”
- The screen to check the relay is To change the relay press button “3” or “4”. To change the status press button “ENTER”.
- With lamp test you can test all the LEDs and LCD backlight for correct operation.
Useful notes to setup the panel
For the correct mounting and setup of the panel, the user must do some
basic steps:
- First of all, the technician has to design the schematic which includes the way of installation of the panel and the devices, the length of the cable and the point where the device is connected. This diagram will be useful for the fault detection (short-circuits, alarms and faults).
- The user disables all the system.
- Next the user configures the sensors and the inputs.
- When finished the user enables the inputs that are required.
- The panel must be isolated from the main power supply when we install the sensors. After all connections are finished, the power to the panel is restored.
- Leave the panel working for about 20 minutes without cutting off the power supply. Check the current of every sensor. The current must not be over 4mA. If it isn’t, wait about 1 hour and then re-check. If the current of the sensor is not about 4mA, then perhaps the sensor needs setup.
- If there is one short circuit in the power supply of a sensor (terminals +,-) for a moment, the panel shows a fault. To clear the fault first we have to correct the short circuit and then to reset the panel via the keyboard.
In case there is a fault you must check point to point, which is out of communication.
Technical Characteristics
BS- 304 | BS- 308 | BS- 312 | BS-316 | |
---|---|---|---|---|
Gas detection control panel up to 16 inputs | ||||
Power Supply | 100-240V AC / 50-60Hz | |||
Consumption | 23W/60VA | |||
Battery type | 12V / 7Ah Pb or 2X12V/7Ah | |||
Charge Circuit | Power supply 13.8V / 500mA | |||
Inputs | 4+AUX | 8+AUX | 12+AUX | 16+AUX |
Programmable relays (5A/230V) | 5 | 9 | 13 | 17 |
Outputs | Up to 16 programmable relays (5A/230VAC). 1 fault output 20V/300mA, 1 |
AUX
Wrap protection class| IP30
Operating temperature range| 5 to 40 oC
Humidity| Up to 95% humidity
Dimensions| 445 x 345 x 95 mm
Weight| 6160 gr
In compliance with| EN50270 (TYPE I), EN61000-6-3(Use of Ferrite required),
EN61000-3-2, ΕΝ61000- 3-3, EN62368-1:2014
Warranty| 2 years
Warranty
- Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty is specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which accompanies each product. This warranty ceases to exist if the buyer does not follow the technical instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods provided or has any repairs or re-setting done by a third party, unless Olympia Electronics has fully agreed to them in writing. Products that have been damaged can be returned to the premises of our company for repair or replacement, as long as the warranty period is valid.
- Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.
Record Setup
We suggest completing the next tables for your setup and keep them for future
reference.
Title : …………………………………………………………………………………………………….
| 1| 2| 3| 4| 5| 6| 7| 8| 9|
10| 11| 12| 13| 14| 15| 16
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Sensor’s Model| | | | | | | | | | | | | | | |
ZERO| | | | | | | | | | | | | | | |
RANGE| | | | | | | | | | | | | | | |
UNIT| | | | | | | | | | | | | | | |
Alarm 1| | | | | | | | | | | | | | | |
OUTPUT 1| | | | | | | | | | | | | | | |
Alarm 2| | | | | | | | | | | | | | | |
OUTPUT 2| | | | | | | | | | | | | | | |
Alarm 3| | | | | | | | | | | | | | | |
OUTPUT 3| | | | | | | | | | | | | | | |
| 1| 2| 3| 4| 5| 6| 7| 8| 9|
10| 11| 12| 13| 14| 15| 16
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
DELAY ON| | | | | | | | | | | | | | | |
DELAY OFF| | | | | | | | | | | | | | | |
TIME ON| | | | | | | | | | | | | | | |
POSITIVE (YES/NO)| | | | | | | | | | | | | | | |
LATCHED| | | | | | | | | | | | | | | |
N otes: ……………………………………………………………………………….
contact
- HEAD OFFICE 72nd km. O.N.R. Thessaloniki-Katerini
- P.C. 60300 P.O. Box 06 Εginio Pierias Greece
- www.olympia-electronics.com
- info@olympia-electronics.gr
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>