CENTURY CB00027 Wood Insert Owner’s Manual

June 12, 2024
CENTURY

CENTURY CB00027 Wood Insert Owner’s Manual
Wood Insert

CERTIFICATION PLATE

General Information
REFER TO INTENTEK’S DIRECTORY OF BUILDING PRODUCTS FOR SE REFERER AU REPERTOIRE DES PROOURS HOMOLOGUES D’INTERTER POUR PLUS D’INFORMATION US

CONTACT LOCAL BUILDING OFFICIALS ABOUT THE RESTRICTIONS AND INSTALLATION INSPECTION IN YOUR AREA COMMUNIQUER AVEC LES AUTORTES LOCALES DU BATMENT ET DE LA PREVENTION DES INCENDIES AU SUIET DES RESTRICTIONS INSTALLATION DANS VOTRE SECTEUR Intertek STANDARDS/NORMES D’ESSAI Control number: 4002461 Certified to

  • Certified to ULC S628
  • Certified to UL 1482
  • Certified to UL 737
  • Certified to CSA 8415.1-10
  • Certified to ASTM E3053-17
  • Certified to  ASTM E2515-11 (R2017)

Model
CW2100
Serial No:999999

INSTALL AND USE ONLY IN ACCORDANCE WITH SBI STOVE BUILDER INTERNATIONAL INSTALLATION AND OPERATION INSTRUCTIONS.

PREVENT HOUSE FIRES

  • • Install and use in accordance with the manufacturer’s Installation and operating instructions.
  • Contact local building or fire officials about restrictions and installation inspection in your area.
  • Use with solid wood fuel only.
  • Do not use other fuels.
  • For safety, keep screen doors or glass doors fully closed.
  • This stove must be installed as a free-standing heater with the clearances listed in the manufacturer’s installation instructions. It is strictly forbidden to install this stove in a factory-built fireplace,
  • Do not overfire unit. Replace with only ceramic glass 4mm thick.
  • Connect to a code-approved masonry chimney or listed factory-built fireplace chimney with a direct flue connector into the first chimney liner section.
  • The non-combustible floor protection in front of the unit should extend 16 inches (406 mm) (USA), 18 inches (457 mm) (CANADA) without a R value even if the hearth elevation is equal with the combustible floor
  • Do not connect this unit to a chimney serving another appliance. Install only in masonry fireplaces.
  • Do not remove bricks or mortar from masonry fireplace..
  • Inspect and clean chimney frequently.
  • Under certain conditions of use, creosote buildup may occur rapidly.
  • Do not use grate or elevate fire. Build wood fire directly on hearth.
  • This wood heater needs periodic Inspection and repair for proper operation.. Consult the owner’s manual for further Information. It is against US federal regulations to operate this wood heater in a manner inconsistent with the oneratin instructions in the owner Manual

WARNING:
This product can expose you to carbon monoxide, which is known to the State of California to cause cancer, birth defects or other reproductive harm. (For more information go to www.p65warnings.ca.gov

LISTED SOLID FUEL BURNING INSERT APPLIANCE

APPAREAL

For use with wood only

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS

Floor Celling
Floor Celling 
Blower/Ventilator:
115VOLTS, 0.8 AMPS, 60Hz

Ouverature
A : 16 in  (405 mm)
D )1 in. (25 mm)
B )1 in . (25 mm)
D -Combustible shelf (from base of the fireplace insert)
A -Sidewall (from door opening)
C )-Combustible side surround (from faceplate)
E :18 in  (457 mm) CANADA
E : 16 in  (406 mm) USA 1:
I : in./po. (203 mm) CANADA
J : 8 in  (203 mm) USA
U.S. ENVIRONMENTAL PROTECTION AGENCY Certified to comply with 2020 particulate emission standards using cordwood.

CAUTION

  • HOT WHILE IN OPERATION.
  • DO NOT TOUCH. KEEP CHILDREN, CLOTHING AND FURNITURE AWAY.
  • CONTACT MAY CAUSE SKIN BURNS. SEE NAME- PLATE AND INSTRUCTIONS.

16/06/2022 { # test) 27878

Stove Bulder International

Performances
Values are as measured per test method, except for the recommended heating area, firebox volume, maximum burn time and maximum heat output.

Models CW2100 (CB00027)
Type of combustion Non-catalytic
Fuel Type Dry Cordwood
Recommended heating area (sq. ft..)’ 250 to 1,200 ft2 (23 to 111 m2)
Overall firebox volume2 1.1 ft3 (0.031 m3)
Loading volume EPA 1.03 ft3 (0.0292 m3)
Maximum burn time’ 7 hours
Overall heat output rate (min. to max.)34 8,471 BTU/h to 31,700 BTU/h(2.48 kW

to 9.29 kW)
Average overall efficiency3 – Dry cordwood| 75 % (HHV)5| 80 % (LHV)8
Optimum efficiency’| 82 %
Optimum heat transfert efficiency8| 78 %
Average particulate emissions rate9| 1.5 g/h (EPA / CSA B415.1-10)10
Average CO”| 34 g/h

  1. Recommended heating area and maximum burn time may vary subject to location in home, chimney draft, heat loss factors, climate, fuel type and other variables. The recommended heated area for a given appliance is defined by the manufacturer as its capacity to maintain a minimum acceptable temperature in the designated area in case of a power failure.
  2. The overall firebox calculation is an approximation and is not intended to be used for loading. This volume includes a buffer zone to allow an easier fuel insertion, prevent ash spillage and allow the air wash to work properly.
  3. The maximum heat output (dry cordwood) is based on a loading density varying between 15 lb/ft3 and 20 lb/ft3. Other performances are based on a fuel load prescribed by the standard. The specified loading density varies between 7 lb/ft³ and 12 lb/ft3. The moisture content is between 19% and 25%.
  4. As measured per CSA B415.1-10 stack loss method.
  5. Higher Heating Value of the fuel.
  6. Lower Heating Value of the fuel.
  7. Optimum overall efficiency at a specific burn rate (LHV).
  8. The optimum heat transfer efficiency is for the low burn rate and represents the appliance’s ability to convert the energy contained in the wood logs into energy transferred to the room in the form of heat and does not take into account the chemical losses during combustion.
  9. This appliance is officially tested and certified by an independent agency.
  10. Tested and certified in compliance with CFR 40 part 60, subpart AAA, section 60.534(a)(1(ii) and ASTM E3053-
    1. based on the ALT-125 send by EPA on February 28th, 2018. 11 Carbon monoxide.
      Specifications Maximum log length12| 17 in (432 mm) east-west
      ---|---
      Flue outlet diameter| 6 in (150 mm)
      Recommended connector pipe diameter| 6 in (150 mm)
      Type of chimney| ULC S635, CAN/ULC-S640, UL 1777
      Baffle material| C-Cast or equivalent
      Approved for alcove installation| No
      Approved for mobile home installation13| No
      Type of door| Simple, glazed, with cast iron frame
      Type of glass| Ceramic glass
      Blower| Included (up to 90 CFM)
      Particulate emission standard”| EPA / CSA B415.1-10
      USA Standard (Safety)| UL 1482, UL 737
      Canada Standard (Safety)| ULC-S628
  11. North-south: ends of the logs visible, East-west: sides of the logs visible.
  12. Mobile homes (Canada) or manufactured homes (USA): The US Department of Housing and Urban Development describes “manufactured homes” better known as “mobile homes” as follows; buildings built on fixed wheels and those transported on temporary wheels/axles and set on a permanent foundation. In Canada, a mobile home is a dwelling for which the manufacture and assembly of each component is completed or substantially completed prior to being moved to a site for installation on a foundation and connection to service facilities and which conforms to the CAN/CSAZ240 MH standard.
  13. Tested and certified in compliance with CFR 40 part 60, subpart AAA, section 60.534(a)(1(ii) and ASTM E3053-17 based on the ALT-125 send by EPA on February 28th, 2018

Dimensions
Dimensions

CW2100 (CB00027)
© 2022, FABRICANT  ALL RIGHTS RESERVED
Dimensions
W2100 (CB00027)
COMBUSTION CHAMBE 2022, ALL RIGHTS RESERVED

EPA Loading
The charging methods shown below are those that were used during emissions certification.

Air control
The air control is located above the door. To open the air control, insert the removable handle onto the air control and push the air control handle completely to the right (High). This will increase the burn rate. To close the air control, push the air control handle completely to the left (Low). This will decrease the burn rate. **Do not leave the handle on the air control after use, as it will get very hot

**

High burn rate (primary air control open)
Open the air control completely. Criss cross 6 kindling wood pieces in the back of the firebox. Then, place six small pieces (2”x2”) of wood on the kindling crossing them at the greatest possible angle. Criss cross ten others kindling wood pieces on the small pieces of wood. Tie knot with five sheets of paper and place them on top of the kindling wood. Light up the paper and let the door completely open for two minutes. Close the door.

When the kindling and the small pieces of wood are almost completely burnt out and it is possible to break them into pieces, level the coal bed and put four logs in the firebox in an eastwest orientation. Place a medium log (about 4”x4”) in front of the combustion chamber and the biggest log (about 5”x5”) in the back of the combustion chamber. Place the last two medium pieces on top of the two others in an orientation that points to the right. Do not leave space between the pieces. Let the door open ajar at 90° for 5 minutes and close the door.

Medium and low burn rate
On a 2” coal bed that is still red, place five logs of approximatively 4”x4” or 3”x3” with an eastwest orientation. Place two logs on the coal bed with approximatively 4” between them and the other three on top. There should be air space between each logs and between the logs and the bricks. Let the door ajar at 90° for 5 minutes and then close the door with the primary air control fully open. Leave to burn with the primary air control open for approximately 10 minutes and then close the primary air control completely for the low burn rate and halfway for the medium burn rate.

WARNING
Before opening the door completely to add  wood to the insert, the fan must be turned OFF to avoid blowing ash outside the combustion chamber. Refer to section “5.1 Blower” of the owner’s manual for how to turn OFF the fan
Turn Off

Clearances to Combustible Material

When the insert is installed so that its surfaces are at or beyond the minimum clearances specified, combustible surfaces will not overheat under normal and even abnormal operating conditions.
NO PART OF THE INSERT MAY BE LOCATED CLOSER TO THE COMBUSTIBLE THAN THE MINIMUM CLEARANCE FIGURES GIVEN

Minimum Masonry Opening and Clearances to Combustibles
Masonry Opening
Figure 1 : Hearth opening and clearances to combustibles

| MINIMUM CLEARANCES
---|---
F| 16″ (406 mm)
I| 34″ (864 mm)
Q| 72″ (183 cm)
| MINIMUM MASONRY OPENING
---|---
J| 19″ (483 mm)
K15| 25″ (635 mm)
L| 15 ½” (394 mm)
| MAXIMUM THICKNESS
---|---
O| 3″ (76 mm)
P| 1.5″ (38 mm)
Q| 12″ (305 mm)
| FACADE CLEARANCES
---|---
From combustible side surround| 1″ (25 mm)
From combustible top surround| 1″ (25 mm)

15 If a fresh air intake is required, it is recommended to add at least 4″ to the width of the minimum opening of the hearth.

Floor Protection
It is necessary to have a floor protection made of non-combustible materials that meets the measurements specified below
Table 1 : Floor Protection

| FLOOR PROTECTION
---|---
Canada| USA
B16| 18″ (457 mm)| 16″ (406 mm)
M| 8″ (203 mm)| N/A
N| N/A| 8″ (203 mm)

Figure 2 : Floor Protection
Floor Protection
To determine the need to add floor protection (D) beyond the hearth extension (A), the following calculation must be done using the data in “ Table 2 : Data for Floor Protection Calculation ” of this section: D = B – G, where G = A-C
Figure 3 : Additional Floor Protection – Raised Installation
Raised Installation
Figure 4 : Additional Floor Protection – Not Raised Installation
Installation
Table 2 : Data for Floor Protection Calculation

| A| B| C| D| E| Air Jacket
---|---|---|---|---|---|---
Minimum Extended| Dimension of the hearth extension| See raised installation| 0″ (0 mm)| G = (A-C) D=B- G| 10 1/8″ (257 mm)| flush with fireplace facing

16 From door opening. The depth of the hearth extension in front of the insert is included in the calculation of the floor protector’s dimensions.
If the value (D) is negative or zero, additional floor protection in front of the unit is not needed because the masonry fireplace hearth extension is long enough. If the value (D) is positive, an additional floor protection in front of the hearth extension at least equivalent to the result (D) must be added.

R Value
There are two ways to calculate the R-value of the floor protection. First, by adding the R-values of materials used, or by the conversion if the K factor and thickness of the floor protection are given.

To calculate the total R value from R values of the materials used, simply add the R-values of materials. If the result is equal to or greater than the R-value requirements, the combination is acceptable. R-values of some selected materials are shown below.

MATERIAL| CONDUCTIVITY (K)
PER INCH| RESISTANCE (R)
PER INCH THICKNESS

---|---|---
Micore® 160| 0.39| 2.54
Micore® 300| 0.49| 2.06
Durock®| 1.92| 0.52
Hardibacker®| 1.95| 0.51
Hardibacker® 500| 2.3| 0.44
Wonderboard®| 3.23| 0.31
Cement mortar| 5.00| 0.2
Common brick| 5.00| 0.2
Face brick| 9.00| 0.11
Marble| 14.3 – 20.00| 0.07 – 0.05
Ceramic tile| 12.5| 0.008
Concrete| 1.050| 0.950
Mineral wool insulation| 0.320| 3.120
Limestone| 6.5| 0.153
Ceramic board (Fibremax)| 0.450| 2.2
Horizontal still air (1/8″ thick)18| 0.135| 0,920″

Exemple:
Required floor protection R of 1.00. Proposed materials: four inches of brick and one inch of Durock® board:

Installing Options on Your Product and Replacing Parts

Replacement and Adjustment

Door
Note: The images shown are for guidance only and may be different from your product, but the assembly remains the same.

In order for the insert to burn at its best efficiency, the door must provide a perfect seal with thefirebox. Therefore, the gasket should be inspected periodically to check for a good seal. The tightness of the door seal can be verified by closing and latching the door on a strip of paper. The test must be performed all around the door. If the paper slips out easily anywhere, either adjust the door or replace the gasket.
Door Opening

Gasket
It is important to replace the gasket with another having the same diameter and density to maintain a good seal.

  1. 1. Remove the door and place it face-down on something soft like a cushion of rags or a piece of carpet.
  2. Remove the old gasket from the door. Use a screwdriver to scrape the old gasket adhesive from the door gasket groove.
  3.  Apply a bead of approximately 3/16″ (5 mm) of high temperature silicone in the door gasket groove. Starting from the middle, hinges side, press the gasket into the groove. The gasket must\ not be stretched during installation.
  4. Leave about ½″ (10 mm) long of the gasket when cutting and press the end into the groove. Tuck any loose fibers under the gasket and into the silicone.
  5. Close the door. Do not use the insert for 24 hours.

Door Alignment

To align, open the door and loosen the pressures screws located on the lower and upper hinges of the door using a 3/32” Allen key to free the adjustable hinge rods.
Door Alignment

Using a flat screwdriver, turn the adjustable hinge rods in the direction shown to adjust the doors. Tighten all door hinge pressure screws when they are at the desired positions. Configurations 1-2-3-4-5-6, show in which direction these act on the adjustment of the door.

1 2 3 4
A A
B B

Flat Screwdriver

Flat Screwdriver

Glass Replacement

The glass used is a ceramic glass, 5/32″ (4 mm) thick,18 3/8″ X 9″ (467 mm x 229 mm) tested to reach temperatures up to 1400º F. If the glass breaks, it must be replaced by a ceramic glass from SCHOTT with the same specification. Contact your dealer to obtain a genuine replacement part. Tempered glass or ordinary glass will not withstand the high temperatures of this unit

WARNING : DO NOT USE SUBSTITUTE MATERIALS WHEN REPLACING THE GLASS.

To remove or replace the glass ( C ):

  1. Remove the door from its hinges and lay it on a soft, flat surface.

  2. Remove the screws (A) and the glass retainer (B).
    Remove the screws

  3. Remove the glass (C). If it is damaged install a new one in place. The replacement glass must have a gasket all around (see procedure below).
    Remove The Glass
    Figure 5 : Replacing the glass

  4. Reinstall the glass, being careful to centre the glass in the door and not to over-tightening the retaining screw.

The two main causes of broken door glass are uneven placement in the door and overtightening the retaining screw

  • Do not clean the glass when the stove is hot.
  • Do not abuse the glass door by striking or slamming shut.
  • Do not use the stove if the glass is broken
    Retaing Screws

Glass Gasket Replacement

The glass gasket is flat, adhesive-backed, woven fiberglass. The gasket must be centered on the edge of the glass.
Glass Gasket Replacement

  1. Follow the steps of the previous section to remove the glass.
  2. Remove the old gasket and clean the glass thoroughly.
  3. Peel back a section of the paper covering the adhesive and place the gasket on a table with the adhesive side up.
  4. Stick the end of the gasket to the middle of one edge, then press the edge of the glass down onto the gasket, taking care that it is perfectly centred on the gasket.
  5. Peel off more of the backing and rotate the glass. The gasket must not be stretched during installation.
  6. Cut the gasket to the required length.
  7. Pinch the gasket onto the glass in a U shape, all around the glass. By following these instructions, the edge clearances are maintain.

Mandatory Installation

  • Empty the combustion chamber (Figure 5) and unscrew the two screws (B) of the side refractory bricks supports (A). The bricks can then be removed in the order shown in Figure 6.
    Figure 6 :
    Empty the combustion chamber
    Mandatory Installation
    Figure 7
    : Remove brick supports
    Remove brick supports

Connecting the Blower With a BX Wire

CAUTION RISK OF ELECTROCUTION.
All electrical connections should be performed by a certified electrician.

  1. Remove the screws (A) to remove the plate (B) and gain access to the wires. Save the screws for later.
    Remove the screws

  2. Disconnect the black (C) and white (D) wires.

  3. Remove the ground screw (E) to remove the green wire. Save the screw for later.
    Remove the ground screw

  4. Strip a section of ½” of the black and white wires (F) that are in the box attached to the insert
    white wires

  5. Remove the piece of metal (G) from the plate (B) obstructing the hole to the left of the power cord (H) using pliers or a screwdriver. Cut the power cord (H) on each side of the black clamp.
    Remove The Piece

  6. Install the connector (I) supplied with the manual kit in the hole formed in the plate (B) in step 5.
    Install The Connector

  7. Pass the new wires through the connector (I) and install the sleeve (J) supplied with the manual kit on the BX wire.

  8. Join the black and white wires using marottes (K) (not supplied) and secure the ground wire with the screw (E) kept in step 3.

  9. Close the connection box by screwing in the plate (B) with the two screws (A) kept in step 1 and secure the BX wire by tightening the screw (L) of the connector (I).
    Installation

Changing the Side of the Blower Power Cord

  1. Unscrew both screws (A) to remove the grille (B) in front of the blower. Unscrew both screws (K) to remove the ash tray (L). Then unscrew the three plastic grommets (C) located on the base of the fan. Remove the wires from the grommets. Keep the screws.
    Changing The Side

  2. Disconnect the white wire (D) and the black wire (E) (follow the wires coming from the inside of the insert). Remove the four screws (F) that hold the connection box (G) to the insert and gently pull it out until the white and black wires come out of the insert. Keep the screws.
    Disconnect

  3. Unscrew the plate (H) on the other side of the insert. Keep the plate (H) and screws (I).
    Unscrew The Plate

  4. Pass the white (D) and black (E) wires through the hole formed in the previous step by pulling them towards the front of the insert. Then pass the wires through the grommet (J) located on the side at the front of the device.

  5. Screw the connection box (G) with the four screws (F) kept in step 2.
    Inserting

  6. Install the plate (H) with the screws (I) kept in step 3 to the initial location of the connection box (G).

  7. Pull the excess black and white wires into the insert to be able to connect them to their respective locations (the black wire is connected to the rheostat and the white wire is connected to the blower). An extension cable must be installed on the black wire to get to the rheostat (extension supplied with the manual kit).

  8. Secure the excess wires using the three plastic grommets (C) removed in step 1.

  9. Reinstall the grille (B) with the screws (A) kept in step 1.
    Installation

Blower Removal

  1. Remove the two screws (A) on each side of the grille (B) to be able to remove it.
    Remove The Two screws

  2. Unscrew the two wing nuts (C) on each side of the fan.
    Unscrew The two Wing Nuts

  3. Take out the fan (D).
    Take Out The Fan

Removable Air Control Handle
This insert comes with a removable handle for the primary air control. A holder for the handle is supplied with the manual. Here is an example of the holder installation.

CAUTION: Do not leave the handle on the air control after use, as it will get very hot.
Removable Air Control Handle

Faceplate Installation

  1. Lay the panels on a flat and non abrasive surface. Align the top panel holes (A) with the left and right panels (B) and (C). Secure together using the bolts (D) and nuts (E) provided.

  2. Install the grille on the assembled faceplate and bend the tabs using pliers
    Install The Grille

  3. Hang the assembled faceplate on the insert.
    Faceplate

Faceplate Decorative Panel Installation/Removal
It is possible to install the insert with or without the faceplate decorative panel. The latter is included with the insert and is already partially installed with two screws at each end. Here are the steps to remove or keep it :

Faceplate decorative panel removal

  • Remove the screws (B) at each end of the panel (A) to be able to remove it afterwards.
    Faceplate Panel Removal
    Faceplate decorative panel installation

  • Screw the panel with 6 additional screws (B).
    panel Installation

Optional Fresh Air Intake Kit Installation

The fresh air intake kit may be installed on the right or left end side of the unit. The unused side must be covered by the plate provided in the user manual kit.

  • Install the fresh air intake adapter (E) with four screws (F) then secure the flexible pipe19 (H) (not included) to the adapter using one of the pipe clamps (G). Secure the other end of the pipe to the outside wall termination (J) using the other pipe clamp. The outside wall termination must be installed outside of the home
    Kit Installation

Optional Fire Screen Installation
In the United States or in provinces with a particulate emissions limit (e.g.: US EPA), the use of open-door wood stoves with a rigid fire screen is prohibited.

  1. Open the door .
    Open the door

  2. Hold the fire screen by the two handles and bring it close to the door opening
    Door Opening

  3. Lean the upper part of the fire screen against the top door opening making sure to insert the top fire screen brackets in front of the primary air deflector.
    Top Door Opening

  4. Lift the fire screen upwards and push the bottom part towards the insert then let the fire screen rest on the bottom of the door opening.
    Bottom Door Opening

Air Tubes and Baffle Installation

  1. Starting with the rear tube, lean and insert the right end of the secondary air tube into the rear right channel hole. Then lift and insert the left end of the tube into the rear left channel.
    Air Tubes Installation

  2. Align the notch in the left end of the tube with the key of the left air channel hole. Using a

    • Wise grip » hold the tube and lock it in place by turning the tube as shown. Make sure the notch reaches the end of the key way
  3. Install the baffle.

  4. Repeat steps 1 and 2 for the two other tubes.

  5. To remove the tubes use the above steps in reverse order
    Baffle Installation

Note that secondary air tubes (A) can be replaced without removing the baffle board (B) and that all tubes are identical.
Secondary Air Tubes

Removal Instructions

  • For inspecting purposes, the insert may need to be removed. To remove the insert, follow these instructions:
  • Remove the blower grille (E) and faceplate (D) by lifting it and then pulling on it.
  • Remove the blower (C).
  • Remove the three screws securing the pipe connector (A).
  • Unscrew the bolts securing the insert to the floor on each side of the unit (B)
    Removal Instructions
    Removal Instructions

Exploded Diagram and Parts List
Parts List

IMPORTANT: THIS IS DATED INFORMATION.
When requesting service or replacement parts for this unit, please provide the model number and the serial number. We reserve the right to change parts due to technology upgrades or availability. Contact an authorized dealer to obtain any of these parts. Never use substitute materials. Use of non-approved parts can result in poor performance and safety hazards.

# Item Description Oty
1 21636 2.1 SERIE C.CAST BAFFLE 1
2 5E74778 SECONDARY AIR TUBE KIT 1
3 AC06600 SILICONE AND 5/8′ X 8′ BLACK DOOR GASKET KIT 1
4 22419 BOTTOM REFRACTORY BRICK 1
5 29000 4-xex1 1/4″ REFRACTORY BRICK 9
6 PL74860 3-1/4″ X 7-1/4″ X 155 DEG BRICK 2
7 SE31318 DOOR HINGE REPLACEMENT KIT 1
8 AC06400 3/4′ X 6′ FLAT BLACK SELF-ADHESIVE GLASS GASKET 1
9 SE74847 CW2100 CENTURY FACEPLATE 1
10 PL74850 FACEPLATE GRILL 1
11 PL74E49 RIGHT FACEPLATE 1
12 PL74847 TOP FACEPLATE 1
13 PL74848 LEFT FACEPLATE 1
14 SE46294 CB00027 INSTRUCTION MANUAL KIT 1
15 ACO5959 METALIJC BLACK STOVE PAINT – 342 g (12oz) AEROSOL 1
16 SE74798 GLASS. GASKET AND MOULDING KIT 1
17 5E74775 GLASS WITH GASKET 15 3/4″ X 10 1/8″ 1
18 PL74798 GLASS RETAINER 2
19 60013 POWER CORD 96 X18-3 type SIT (50 pcs per canon) 10
20 30124 SCREW 48 – 32 X 5/16″ TRUSS OUADREX ZINC 1
21 AC01213 FoGiO  FiKSCREEN 1
22 Ammo 3/8′ BLACK COIL HANDLE 1
23 AC01298 VO FRESH AIR INTAKE KIT 2
24 30337 SQUARE HEAD SET SCREW 1/2-13 X 1-1/2′ 1
25 44085 RHEOSTAT KNOB 1
26 44028 CERAMIC THERMODISC F110-20F 2
27 30154 BLACK SCREW 110 X 5/8′ OUADREX 02 TYPE A 1
28 SE74166 HANDLE 30898 REPLACEMENT KIT 1
29 SE74766 DAMPER ASSEMBLY 1
30 PL34052 LINER FIXATION BRACKET 1
31 44075 TANGENTIAL BLOWER 1800 115V-60112-30W (5) 90 CFM 1
32 5E74782 DOOR ASSEMBLY 1
33 PL74846 ASH TRAY 1
34 PL74845 FRONT HOUSING 1

CENTURY LIMITED LIFETIME WARRANTY CENTURY HEATING LIMITED WARRANTY

The warranty of the manufacturer extends only to the original retail purchaser and is not transferable. This warranty covers brand new products only, which have not been altered, modified nor repaired since shipment from factory.

This warranty applies to normal residential use only. This warranty is void if the unit is used to burn material other than cordwood (for which the unit is not certified by EPA) and void if not operated according to the owner’s manual. Damages caused by misuse, abuse, improper installation, lack of maintenance, over firing, negligence or accident during transportation, power failures, downdrafts, venting problems or under-estimated heating area are not covered by this warranty. The recommended heated area for a given appliance is defined by the manufacturer as its capacity t maintain a minimum acceptable temperature in the designated area in case of a power failure.

This warranty does not cover any scratch, corrosion, distortion, or discoloration. Any defect or damage caused by the us  of unauthorized or other than original parts voids this warranty. An authorized qualified technician must perform the installation in accordance with the instructions supplied with this product and all local and national building codes. Any reclamation related to an improper installation is not covered by this warranty.

The manufacturer may require that defective products be returned or that digital pictures be provided to support the claim. Returned products are to be shipped prepaid to the manufacturer for investigation. Transportation fees to ship the product back to the purchaser will be paid by the manufacturer. All parts costs covered by this warranty are limited according to the table below.

The manufacturer, at its discretion, may decide to repair or replace any part or unit after inspection and investigation of the defect. The manufacturer may, at its discretion, fully discharge all obligations with respect to this warranty by refunding the wholesale price of any warranted but defective parts. The manufacturer shall, in no event, be responsible for any uncommon, indirect, consequential damages of any nature, which are in excess of the original purchase price of the product. A one-time replacement limit applies to all parts benefiting from lifetime coverage. This warranty applies to products purchased after July 1st, 2020

DESCRIPTION| WARRANTY
APPLICATION•
---|---
PARTS
Combustion chamber (welds only) and cast iron door frame.| 5 years
Surrounds, heat shields, ash drawer, steel legs, pedestal and convector air- mate.| 2 years
Removable stainless steel combustion chamber components, secondary air tubes”, deflectors and supports.| 2 years
Glass retainers, handle assembly, and air control mechanism.| 2 years
Carbon steel combustion chamber components, vermiculite bafflenand ceramic glass.| 1 year
Blower, heat sensors, switches, rheostat, wiring, and other controls.| 1 year
Firebricks, paint and gaskets.| –
Any parts replaced under the warranty (Except firebricks, paint and gaskets)| 90 days

*Subject to limitations above. Picture required.**

Shall your unit or a components be defective, contact immediately your CENTURY. To accelerate processing of your warranty claim, make sure to have on hand the following information when calling:

  • Your name, address and telephone number;
  • Serial number and model name as indicated
  • Installation configuration; on the nameplate fixed to the back of your unit;
  • Nature of the defect and any relevant informatio

Before shipping your unit or defective component to our plant, you must obtain an Authorization Number from your CENTURY. Any merchandise shipped to our plant without authorization will be refused automatically and returned to sender.

This document is available for free download on the manufacturer’s website. It is a copyrighted document. Resale is strictly prohibited. The manufacturer may update this document from time to time and cannot be responsible for problems, injuries, or damages arising out of the use of information contained in any document obtained from unauthorized sources

ONLINE WARRANTY REGISTRATION
If the unit requires repairs during the warranty period, proof of purchase must be provided. The purchase invoice must be kept. The date indicated on it establishes the warranty period. If it can not be provided, the warranty period will be determined by the date of manufacture of the product. It is also highly recommended to register the warranty online at
Qr Code

https://www.century-heating.com/ca/en/warranty/warranty-registration

Dealer:___
Installer:_

Phone Number:_
Serial Number:___

Registering the warranty will help to quickly find the information needed on the unit.

Stove Builder International inc.
250, rue de Copenhague,
St-Augustin-de-Desmaures (Québec) Canada
G3A 2H3 1-877-356-6663
https://www.century-heating.com/ca/en/
tech@sbi-international.com

CENTURY Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

CENTURY User Manuals

Related Manuals