Installation Instructions
LED BATTEN LIGHT (B18W-CC-MS-E & B36W-CC-MS-E)
Before installation, read the instructions completely and carefully.
Step1:
Turn off the power supply;
Slide the end caps;
Remove the LED diffuser from the base housing;
Set specific application by
Dip Switch on Sensor (refer to next page);
Select suitable color temperature by external dip switch:
i.WW = Warm White 3000K
ii.NW = Natural White 4000K
iii.CW = Cool White 6000K
iv.Factory Setting = NWStep 2: Mount the fitting onto ceiling with wall plugs and
screws![NEDLANDS GROUP B18W-CC-MS-E LED Batten Emergency and Microwave Sensor
- Turn 1](https://manuals.plus/wp-content/uploads/2023/08/NEDLANDS-GROUP-B18W-
CC-MS-E-LED-Batten-Emergency-and-Microwave-Sensor-Turn-1.jpg) Surface
Mounted
(4pcs wall plugs & screws included)
Step 2: Secure the mounting bracket to the steel cable
Suspended Mounted
(suspension wires NOT included)
Step 3: Wire the cable in to the terminal block through the cable entry hole
(refer to next Page);
Insert connector between the base and diffuser;
Assemble the diffuser back to the base and also the two caps.Step 4: Turn on the
power supply to ensure the luminaire is working properly. * Turn off and
isolate the electrical supply before connecting this fitting to the building
wires.
- Must beinstalled or connected by licenced electrician.
- This product is indoor use only.Before installation, please read the instructions completely and carefully.
Wising Diagram
Testing
When luminaire is permanently connected to mains supply, allow the luminaire
to fully charge for 24 hours. Conduct following tests once the battery has
fully charged:
Test 1:
A commissioning discharge test must be carried out once the luminaire is
connected to mains supply. The emergency luminaire must remain illuminated for
at least 3 hours after disconnection from the mains power.
NOTE: The luminaire works on standard power when connected to mains
supply and switches to 3.5W power during emergency mode operation.
Test 2:
Subsequent tests, performed every 6 months, require the luminaire to
successfully operate in emergency mode for 90mins.
NOTE: A record shall be maintained of all the discharge tests performed
on site at all times.
Test Switch and LED Indicator:
The Test Switch and LED indicator on the luminaire provide an indication of the status of the luminaire during testing and normal operation
Test Switch &LED indicator | ON | OFF |
---|---|---|
• Depress the test switch-luminaire |
will operate in Emergency mode
• LED indicator will be off during Emergency mode| • On releasing the Test
switch the luminaire will automatically connect to mainssupply
• LED indicator will illuminate
| • Luminaire is working on mains supply| • Luminaire is working in Emergency
mode
• Luminaire has malfunctioned
Be sure to power off before adjusting DIP switch setting.
Setting
Factory Setting: Detection Area 100%, Hold Time 3min, Daylight Sensor Disable, Standby Dimming 20%, Second-Order Delay 15min.
- Hold Time refers to the time period the lamp remains at 100% illumination after no motion detected.
- Disable means the daylight sensor does not work. When set to Disable mode, the daylight sensor will switch on the lamp when motion is detected, Regardless of ambient light level. 30lux is twilight operation.
- Standy Dimming is the low light level that you would like to have after the hold time in the long absence of people.
- Second-Order Delay refers to the time period the lamp remains at a low light level before it completely switches off in the long absence of people. When set to “∞”, the low light is maintained until motion is detected. When set to “15min”, the light will turn off after 15min.
Application Demo
- When the ambient light is bright enough, the light will not automatically light up even if a moving object is detected.
- When the ambient light is lower than the preset photosensitive threshold, the light will automatically light up when the sensor detects a moving object.
- After the moving object leaves, the sensor will enter the delay time when it cannot detect the moving object and keep the light on.
- After the preset delay time, the light will automatically turn off.
Free Call: 1800 909 306
Fax: +61 3 8669 4097
Website: nedlandsgroup.com.au
Email: sales@nedlandsgroup.com.au
VIC Office Unit 1 / 181 Proximity Drive, Sunshine West VIC 3020
WA Office Unit 3 / 5 Edison Circuit, Forrestdale, WA, 6112
A&K Investments (Australia) Pty Ltd T/A Nedlands Group ABN 95 164 389 762
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>