NEDLANDS GROUP B18W-CC-MS-E LED Batten Emergency and Microwave Sensor Instruction Manual

June 12, 2024
Nedlands Group

NEDLANDS GROUP logo B18W-CC-MS-E LED Batten Emergency and Microwave Sensor
Instruction Manual

Installation Instructions

LED BATTEN LIGHT (B18W-CC-MS-E & B36W-CC-MS-E)
Before installation, read the instructions completely and carefully.
Step1:
Turn off the power supply;
Slide the end caps;
Remove the LED diffuser from the base housing;
Set specific application by
Dip Switch on Sensor (refer to next page);
Select suitable color temperature by external dip switch:
i.WW = Warm White 3000K
ii.NW = Natural White 4000K
iii.CW = Cool White 6000K
iv.Factory Setting = NWNEDLANDS GROUP B18W-CC-MS-E LED Batten Emergency and
Microwave Sensor - TurnStep 2: Mount the fitting onto ceiling with wall plugs and screws![NEDLANDS GROUP B18W-CC-MS-E LED Batten Emergency and Microwave Sensor

Suspended Mounted
(suspension wires NOT included)
Step 3: Wire the cable in to the terminal block through the cable entry hole (refer to next Page);
Insert connector between the base and diffuser;
Assemble the diffuser back to the base and also the two caps.NEDLANDS GROUP
B18W-CC-MS-E LED Batten Emergency and Microwave Sensor -
WireStep 4: Turn on the power supply to ensure the luminaire is working properly. * Turn off and isolate the electrical supply before connecting this fitting to the building wires.

  • Must beinstalled or connected by licenced electrician.
  • This product is indoor use only.NEDLANDS GROUP B18W-CC-MS-E LED Batten Emergency and Microwave Sensor - icon 2Before installation, please read the instructions completely and carefully.

Wising Diagram

NEDLANDS GROUP B18W-CC-MS-E LED Batten Emergency and Microwave Sensor - Wire
1

Testing

When luminaire is permanently connected to mains supply, allow the luminaire to fully charge for 24 hours. Conduct following tests once the battery has fully charged:
Test 1:
A commissioning discharge test must be carried out once the luminaire is connected to mains supply. The emergency luminaire must remain illuminated for at least 3 hours after disconnection from the mains power.
NOTE: The luminaire works on standard power when connected to mains supply and switches to 3.5W power during emergency mode operation.
Test 2:
Subsequent tests, performed every 6 months, require the luminaire to successfully operate in emergency mode for 90mins.
NOTE: A record shall be maintained of all the discharge tests performed on site at all times.

Test Switch and LED Indicator:

The Test Switch and LED indicator on the luminaire provide an indication of the status of the luminaire during testing and normal operation NEDLANDS
GROUP B18W-CC-MS-E LED Batten Emergency and Microwave Sensor -
test

Test Switch &LED indicator ON OFF
• Depress the test switch-luminaire

will operate in Emergency mode
• LED indicator will be off during Emergency mode| • On releasing the Test switch the luminaire will automatically connect to mainssupply
• LED indicator will illuminate
| • Luminaire is working on mains supply| • Luminaire is working in Emergency mode
• Luminaire has malfunctioned

Be sure to power off before adjusting DIP switch setting.

Setting

Factory Setting: Detection Area 100%, Hold Time 3min, Daylight Sensor Disable, Standby Dimming 20%, Second-Order Delay 15min.NEDLANDS GROUP B18W-
CC-MS-E LED Batten Emergency and Microwave Sensor -
Detection

  1. Hold Time refers to the time period the lamp remains at 100% illumination after no motion detected.
  2. Disable means the daylight sensor does not work. When set to Disable mode, the daylight sensor will switch on the lamp when motion is detected, Regardless of ambient light level. 30lux is twilight operation.
  3. Standy Dimming is the low light level that you would like to have after the hold time in the long absence of people.
  4. Second-Order Delay refers to the time period the lamp remains at a low light level before it completely switches off in the long absence of people. When set to “∞”, the low light is maintained until motion is detected. When set to “15min”, the light will turn off after 15min.

Application Demo

  1. When the ambient light is bright enough, the light will not automatically light up even if a moving object is detected.NEDLANDS GROUP B18W-CC-MS-E LED Batten Emergency and Microwave Sensor - When
  2. When the ambient light is lower than the preset photosensitive threshold, the light will automatically light up when the sensor detects a moving object.NEDLANDS GROUP B18W-CC-MS-E LED Batten Emergency and Microwave Sensor - ambient
  3. After the moving object leaves, the sensor will enter the delay time when it cannot detect the moving object and keep the light on.NEDLANDS GROUP B18W-CC-MS-E LED Batten Emergency and Microwave Sensor - After
  4. After the preset delay time, the light will automatically turn off.NEDLANDS GROUP B18W-CC-MS-E LED Batten Emergency and Microwave Sensor - preset

NEDLANDS GROUP logo Free Call: 1800 909 306
Fax: +61 3 8669 4097
Website: nedlandsgroup.com.au
Email: sales@nedlandsgroup.com.au
VIC Office Unit 1 / 181 Proximity Drive, Sunshine West VIC 3020
WA Office Unit 3 / 5 Edison Circuit, Forrestdale, WA, 6112
A&K Investments (Australia) Pty Ltd T/A Nedlands Group ABN 95 164 389 762

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals