Danfoss DSV 10 Change-Over Valve Installation Guide
- June 12, 2024
- Danfoss
Table of Contents
DSV 10 Change-Over Valve
Installation Guide
Installation Guide
Change-over valve
DSV 10
DSV 10 Change-Over Valve
Refrigerants
Applicable to R717, R744, HFC and HCFC
Temperature range
-50 °C – 100 °C (-58 °F – 212 °F)
Pressure range
The DSV 10 valve is designed for a max. working pressure of 65 bar (944
p.s.i.g).
Installation
The DSV change-over valve is installed together with safety valves (SFA).
This installation guide must be complemented with the installation guide for
the specific safety valves to secure all details are covered.
Important:
The inlet/outlet pipe dimensions must not be smaller than those of the
welding nipples.
The valve is designed to withstand a high internal pressure. However, the
piping system should be designed to avoid liquid traps and reduce the risk of
hydraulic pressure caused by thermal expansion. It must be ensured that the
valve is protected from pressure transients like “liquid hammer” in the
system.
During welding avoid welding debris and dirt in the threads of the connections
and in the adjacent pipes.
Before assembly clean all parts exposed to debris and dirt.
DSV 10 G inlet connection with welding nipple (see fig. 1a)
- Assemble the union nut and welding nipple and place the assembly further to the system piping
- Fully weld the welding nipple to the system piping and cool down the assembly
- Place the alugasket inside the union nut and install the DSV 10 by turning the union nut counter-clockwise
- Tighten to torque 110 Nm (81 ft lb)
DSV 10 G inlet connection with adapter (see fig. 1b)
- Place alugasket (G) inside the union nut with “RH” marking to the inlet
- Connect the union nut with inlet
- Turn clockwise and tighten to torque 110 Nm (81 ft lb)
- Place the alugasket inside the other union nut and connect to the system piping by turning the union nut clockwise and tighten sufficiently
Important:
Counter-hold one union nut when turning the other union nut to avoid
unintentionally loosening of the nut!
DSV 10 NPT inlet connection (see fig. 1c)
- Put sufficient Teflon tape or similar sealing material on the DSV 10 inlet
- Mount the DSV 10 inlet by turning it clockwise
- Align and tighten by applying a sufficient torque
Adapter/ blind cap installation (see fig. 2)
- Place alugasket (G) on the A/B outlets
- Connect SFA 10 adapters (G) to the outlets A/B. For pressure testing set-up use blind caps (G) or plugs (NPT) with sufficient Teflon selling to seal A and B
- Turn counter-clockwise and tighten sufficiently. On G-version to torque 110 Nm (81 ft lb)
Important:
Assure a tight assembly by counter-holding the nut at the DSV inlet when
turning adapters/SFAs at DSV outlet.
SFA 10 G (x2) installation (see fig. 3a)
- Place the alugasket inside the union nut, add G4500 grease (148F3064) to thread a, and install the SFA by turning the union nut counter-clockwise
- Tighten to torque 100 Nm (74 ft lb)
- Prepare and assemble the outlet connection as described in the DSV 10 G inlet connection section
- Add G4500 grease (148F3064) to thread b, and tighten the outlet connection to torque 100 Nm (74 ft lb)
Important:
Assure a tight assembly by counter-holding the nut at the DSV inlet when
turning adapters/SFAs at DSV outlet.
SFA 10 NPT (x2) installation (see fig. 3b)
- Put sufficient Teflon tape or similar sealing material on the SFA 10 inlet and outlet
- Mount the SFA 10 inlet by turning it clockwise
- Align and tighten by applying a sufficient torque
- Connect the SFA 10 outlet to the discharge piping system
Operating Instructions (see fig. 4)
When the spindle is turned fully clockwise to mechanical stop, the DSV is
opened to outlet B. When the spindle is turned fully counterclockwise to
mechanical stop the DSV is opened to outlet A.
Corrosion protection
The DSV valves are factory painted with a red oxide primer. The external
surface of the valve housing must be prevented against corrosion with a
suitable protective coating after installation and assembly.
Danfoss/S
Climate Solutions • danfoss.com • +45 7488 2222
Any information, including, but not limited to information on selection of
product, its application or use, product design, weight, dimensions, capacity
or any other technical data in product manuals, catalogues descriptions,
advertisements, etc. and whether made available in writing, orally,
electronically, on line or via download, shall be considered informative, and
is only binding if and to the extent, explicit reference is made in a
quotation or order confirmation. Danfoss cannot accept any responsibility for
possible errors in catalogues, brochures, videos and other material.
Danfoss reserves the right to alter its products without notice. This also
applies to products ordered but not delivered provided that such alterations
can be made without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/Soar Danfoss group
companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/5. All
rights reserved.
AN32022465179401-000301
© Danfoss | Climate Solutions | 2023.07
Documents / Resources
|
Danfoss DSV 10 Change-Over
Valve
[pdf] Installation Guide
DSV 10, DSV 10 Change-Over Valve, Change-Over Valve, Valve
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>