SAFETY PRODUCTS
Safety relays Sentry BSR10
Product Manual 2TLC010060M0201
Rev.G
ORIGINAL INSTRUCTIONS
BSR10 Safety Relays Sentry
Read and understand this document
Please read and understand this document before using the products. Please
consult your ABB Electrification Sweden representative if you have any
questions or comments.
Suitability for use
ABB shall not be responsible for conformity with any standards, codes, or
regulations that apply to the combination of products in the customer’s
application or use of the product. Third party certificates for the products
are available at https://new.abb.com/low-voltage/products/safety-products.
This information by itself is not sufficient for a complete determination of
the suitability of the products in combination with the end product, machine,
system, or other application or use.
The following are some examples of applications for which particular attention
must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be
suitable for the products:
- Outdoor use uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this document.
- Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, and installations subject to separate industry or government regulations.
- Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE ABB PRODUCT IS PROPERLY RATED AND INSTALLED
FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Descriptions and examples show how the product works and can be used. It does
not mean that it fulfills the requirements for all types of machines and
processes. The buyer/user is responsible for installing and using the product
according to applicable standards and regulations. We reserve the right to
make changes to the product and the documentation without prior notice
Introduction
1.1 Purpose of document
The purpose of this document is to describe the functions and to provide
instructions for installation, operation, maintenance and troubleshooting of
the product.
1.2 Intended audience
This document is intended for authorized personnel.
1.3 Reading prerequisites
It is assumed that the reader of this document has:
- Basic knowledge of ABB safety products.
- Knowledge of machine safety.
- Knowledge of safety devices.
1.4 Special notes
Pay attention to special notes in this document:
Warning!
Risk of severe personal injury!
An instruction or procedure which, if not carried out correctly, may result in
injury to the technician or other personnel.
Caution!
Risk of damage to the equipment!
An instruction or procedure which, if not carried out correctly, may damage
the equipment.
Note! Important or explanatory information.
Safety
2.1 Intended use
The intended use of the Sentry safety relay is to monitor the state of a
safety device and depending on the state, activate or inactivate the outputs
within the system response time.
The protective function of the safety device is only safe if the safety relay
is correctly connected and configured. The safety relay is not by itself a
complete protective device.
- Use the safety relay as a safety monitoring device.
- Use the safety relay as expansion device of safe outputs
- The safety relay is not intended for use in explosive or easily flammable adjacent air.
- Other use than defined as correct is considered as incorrect use.
2.2 Safety precautions
Warning!
The safety precautions must be followed during installation, operation,
maintenance and troubleshooting.
Warning!
The safety functions must be tested at start up or at replacement before the
system is put in operation.
Installation shall be conducted by authorized personnel following the Safety
regulations, standards and local legal regulations. Carefully read through the
entire original instruction before using the device.
Make sure that these instructions are included together with the documentation
of the system. Make sure that these instructions always are available for
users of the system.
The safety relay must be selected so its safety related capacity meets or
exceed the performance level (PL) or safety integrity level (SIL) that has
been estimated in the risk analysis. The safety relay must only be used after
it has been selected according to related instructions, relevant standards,
rules and regulations for protection and safety at work.
The entire dangerous zone must be visible from the position where the reset
button is installed. The reset button must be positioned out of reach from the
dangerous zone.
The safety functions must be tested after installation or replacement of
components or cables. The safety relay must be exchanged within 20 years.
Failure to comply with instructions, operation that is not in accordance with
the use prescribed in the instructions, improper installation or handling can
affect the safety of people and the system. Failure to comply with the
instructions or standards, excludes any liability.
Product description
3.1 Sentry safety relays
Sentry safety relays provide safe stop and start of monitored devices to
prevent errors. The following safety device types are applicable for the
Sentry safety relays:
- 1 channel safety device.
- 2 channel safety device with equivalent contacts.
- 2 channel safety device with antiviolent contacts.
- Expansion of safety modules.
- Pressure sensitive safety device (short-circuit detection).
- Two-hand safety device.
- OSSD safety device.
Examples of devices for connection to the Sentry safety relays:
- Light beams.
- Light curtains.
- Three position safety device.
- Safety interlock switches.
- Emergency stop buttons.
- Bumpers, contact edges and safety mats.
3.2 Sentry product range
The Sentry product range has the following groups of safety relays:
BSR (Basic function Safety Relay) group
The BSR group include BSR10, BSR11 and BSR23. The safety relays have basic
monitoring functions for 1- and 2-channel safety devices. The safety relay can
be used as an expansion of other safety modules.
SSR (Single function Safety Relay) group
The SSR group includes SSR10, SSR10M, SSR20, SSR20M, SSR32 and SSR42. The
safety relays have single safety device functions and limited configuration
possibilities for automatic and manual reset. SSR32 and SSR42 have a timer
function.
TSR (Timer function Safety Relay) group
The TSR group includes TSR10, TSR20 and TSR20M. The safety relays have timer
functions and configuration possibilities. TSR10 is fully configurable with
preset selection possibilities and password protection.
USR (Universal function Safety Relay) group
The USR group include USR10 and USR22. The safety relays have multiple
functionalities for monitoring safety device including timer functions. The
USR group is fully configurable with preset selection possibilities and
password protection.
3.3 Safety relay overview
A. Connection block, top side back.
B. Connection block, top side front.
C. Product name.
D. Print for connection block, top side back.
E. Print for connection block, bottom side front.
F. Relay output configuration.
G. Print for connection block, top side front.
H. Print for connection block, bottom side back.
J. LEDs for status indication.
K. Connection block, bottom side front.
L. Connection block, bottom side back.
M. DIN rail latching device.
Installation
4.1 Installing precautions
Follow the instructions carefully to avoid personal injury or damage to the
device.
The safety relay shall be attached on a 35 mm DIN rail in a lockable enclosure
that has at least protection class IP54. Sentry safety relays shall be
installed in an upright position.
Make sure there is at least 10 mm distance between the safety relay and other
non-Sentry units to prevent uncontrolled heating. Make sure there is at least
50 mm distance above and below the safety relay and other units for correct
air flow in the venting holes of the safety relay.
Caution!
Sentry safety relays can be installed without distance to other Sentry safety
relays, with exception of BSR23. Make sure there is at least 5 mm distance
between BSR23 and other Sentry safety relays
4.2 Attaching the safety relay on the DIN rail
- Make sure that the DIN rail latching is reset.
- Hang the top rear side of the safety relay on the DIN rail.
- Push the bottom rear side of the safety relay on the DIN rail until a click is heard.
4.3 Removing the safety relay from the DIN rail
- Use a screwdriver to unlock the DIN relay latching device from the DIN rail.
- Pull the bottom rear side of the safety relay away from the DIN rail until a click is heard.
- Lift the top rear side of the safety relay away from the DIN rail.
4.4 Resetting the latching device
- Pull the bottom side of the DIN rail latching device from the safety relay and push it upwards to release it to its original position.
4.5 Connecting precautions
Warning!
Disconnect the power supply before attaching or removing the connection
blocks.
Make sure that connection blocks and wires are clearly marked for correct
connections. Use applicable requirements in IEC 60204‑1 for wire connections.
Make sure that the wires are fitted with crimp terminals or ferrules before
connection, unless solid copper conductors are used.
For connections of relay output contacts: Make sure that all power supplies or
signal sources are connected to one side of the safety relay and that all
power consumers or signal receivers are connected to the opposite side of the
safety relay.
Make sure to use at least one of the following methods to ensure correct wire
protection against short circuits for the safety relay outputs:
- The wires are permanently connected and protected against external damage, for example by wire ducts or other types of covers for protection.
- Use of separate multi-core wires.
- Use of cables with wires being individually shielded with earth connection.
The safety requirement is that fuses shall be used on the relay outputs.
4.6 Connection blocks
The connection blocks on the safety relay are detachable to simplify
installation and replacement. The safety relay can be ordered with two
different types of connection blocks, screw compression type or push-in type.
4.7 Coding the connection blocks
The coding kit is used to make each connection point individual to avoid
faulty connection. Place the coding parts in an specific order on the
connection block and match these with the pin header.
- The risk assessment must include the risk of mistakes when using the connection blocks without coding.
- If coding is used, a test of the outcome of the coding against the identified risks must be done.
4.8 Connecting to a screw compression type terminal
Use a screwdriver with slot size 3,5 mm.
- Open the terminal before inserting a wire.
- Insert the wire in the correct terminal.
- Close the terminal and secure the wire with torque 0,7 Nm ±0,1.
4.9 Connecting to a push-in type terminal
- Press the actuating lever.
- Insert the wire in the correct terminal.
- Release the actuating lever.
4.10 Wire properties
Wire area, screw compression type connection block
Wire with crimp sleeve, ferrule or single solid conductor. Two wires with the
same area must be used. Wire strip length 6,5 mm ±0,5.
Minimum 1×24 AWG and Maximum 1×12 AWG
Minimum 1×0,2 mm2 and Maximum 1×3,3 mm2
Minimum 2×24 AWG and Maximum 2×16 AWG
Minimum 2×0,2 mm2 and Maximum 2×1,5 mm2
Wire area, push-in type connection block
Wire with crimp sleeve, ferrule or single solid conductor. Two wires with the
same area must be used. Wire strip length 6,5 mm ±0,5.
Minimum 1×24 AWG and Maximum 1×14 AWG
Minimum 1×0,2 mm2 and Maximum 1×2,5 mm2
Minimum 2×24 AWG and Maximum 2×16 AWG
Minimum 2×0,25 mm2 and Maximum 2×1,5 mm2
4.11 Wire length
The maximum wire length is dependent on the wire voltage drop from the voltage
source to the safety relay input terminal. It is crucial to fulfill “Minimum
input high voltage (VIHmin)” requirement at “Maximum current sink (Isink)”.
Isink is typical 2.8/VR where VR is the voltage level measured at the R input
terminal. Consult the section for technical data for technical
characteristics.
Functions
5.1 Function overview
Power supply, 24 VDC via safety device
Relay output
- 3 NO + 1 NC
- One channel
- Two channels with equivalent contacts (no 2 channel monitoring)
- Expansion of PLC outputs
Test, start and reset interface
- Test and start
5.2 Power supply
24 VDC via safety device
The safety relay and the safety devices are supplied with 24 VDC and common
shared ground.
Warning!
The power supply must be of type PELV/SELV
5.3 Relay outputs
The safety relay output contacts are opened or closed based on the signals
from the safety device. Each safety relay output has two contacts in series,
one contact for each internal output relay.
A. Connectors: Terminals in connection blocks.
B. NO contact: The NO contact is open when the relay is inactivated and
closed when the relay is activated.
C. NC contact: The NC contact is closed when the relay is inactivated and
open when the relay is activated.
Caution!
A relay output is in safe state when the contact is open.
Caution!
The NC contact is intended to monitor the state of a safety device only. It is
not a safe output.
Note!
The NO contact is open at all types of internal failures and is a safe output.
**Note!
Arc suppression for inductive loads is recommended to get a longer lifetime
for the relay contacts.
5.4 Test, start and reset interface
The safety relay has an interface for test, start and reset functions. The
safety relay enters inactive mode when at least one input is not accepted. The
safety relay enters active mode when the inputs are accepted, and a reset is
performed.
5.5 Test and start**
The safety relay has a Test/Start connection, the X4 input can be connected
either directly to +24 VDC or to a test circuit for supervised contactors
and/or a button for Start.
The relay output will turn active if X4 is set to +24 VDC while it is powered
via R1/R2. After activation, X4 can be removed and the active state will be
kept solely by R1/R2.
The safety relay can be used as a safe expansion relay without external
monitoring since the internal output relays are monitored by the unit itself.
Connections
6.1 Connection groups
The connections are divided into groups.
R | Signal from safety device |
---|---|
X | Test/reset/start/indication |
13, 23, 33 | Safety output, NO |
14, 24, 34 | Safety output, NO |
41 | Output, NC |
42 | Output, NC |
Application connections
7.1 Connection examples
A. One signal from +24VDC, start and stop
B. Two signals from +24VDC / 0
C. One signal from +24VDC
D. One signal from +24VDC, start
E. One signal from +24VDC
Note!
Always use transient suppressors when inductive loads are connected to the
relay outputs.
Maintenance
8.1 Maintaining precautions
Comply to maintenance precautions. Risk of severe personal injury.
Warning!
A defective safety relay shall be replaced with a new. Never bypass the
safety circuit. Repair and exchange of parts of the safety relay is forbidden.
That may impair the safety of the system and could lead to serious personal
injury. In case of breakdown or damage to the safety relay, contact nearest
ABB Electrification service office or reseller.
ABB will not accept responsibility for failure of the functions if the
installation and maintenance requirements shown in this document are not
implemented. These requirements form part of the product warranty.
8.2 Scheduled test
Scheduled test, high demand application
All safety relays and connected safety devices used in high demand
applications must be tested once a year.
Scheduled test, low demand application
All safety relays and connected safety devices used in low demand applications
must be tested every third year.
Test sequence
Test should be conducted according to:
- Set inputs to inactivate outputs.
- Wait until all outputs are in off-state.
- Set inputs to activate outputs.
- Monitor that outputs are activated.
Troubleshooting
9.1 Front LEDs
The three LEDs in the safety relay front indicates operation status and errors
in the system.
A. ON 24 V on R1/R2
B. OUT Output status
C. X4 24 V on X4/R2
9.2 LED operation indication and error status
ON | OUT | X4 | Status | Action |
---|---|---|---|---|
off | off | off | Loss of power supply or too low voltage. Occurs during regular | |
operation | Measure R1/R2 voltage | |||
green | off | off | Input X4 is not powered with correct voltage. Occurs during | |
regular operation | Measure X4/R2 voltage. Troubleshoot the monitored device. |
Troubleshoot the test/start circuit
green| off| green| Safety relay internal error| Exchange the safety relay
off| off| green| No signal to R1/ R2. Occurs during regular operation| Measure
R1/R2 voltage
green| green| green| Normal operation|
green| green| off| Normal operation|
Model overview
10.1 Sentry models
The connection blocks are delivered without coding. The coding kit is an
optional accessory and is ordered separately.
Model | Order code | Description |
---|
BSR10
BSR1OP| 2TLA010040R0000
2TLA010040R0001| Screw compression connection blocks. 24VDC
Push-in connection blocks. 24VDC
BSR11 BSR11P| 2TLA010040R0200
2TLA010040R0201| Screw compression connection blocks. 24VDC
Push-in connection blocks. 24VDC
BSR23 BSR23P| 2TLA010041R0600
2TLA010041R0601| Screw compression connection blocks. 24VDC
Push-in connection blocks. 24VDC
SSR10 SSR1OP| 2TLA010050R0000
2TLA010050R0001| Screw compression connection blocks. 24VDC
Push-in connection blocks. 24VDC
SSR1OM
SSR1OMP| 2TLA010050R0100
2TLA010050R0101| Screw compression
connection blocks. 85-265VAC/120-375VDC
Push-in connection blocks. 85-265VAC/120-375VDC
SSR20 SSR2OP| 2TLA010051R0000
2TLA010051R0001| Screw compression connection blocks. 24VDC
Push-in connection blocks. 24VDC
SSR2OM
SSR2OMP| 2TLA010051R0100
2TLA010051R0101| Screw compression
connection blocks. 85-265VAC/120-375VDC
Push-in connection blocks. 135-265VAC/120-375VDC
SSR32 SSR32P| 2TLA010052R0400
2TLA010052R0401| Screw compression connection blocks. 24VDC
Push-in connection blocks. 24VDC
SSR42 SSR42P| 2TLA010053R0400
2TLA010053R0401| Screw compression connection blocks. 24VDC
Push-in connection blocks. 24VDC
TSR10 TSR1OP| 2TLA010060R0000
2TLA010060R0001| Screw compression connection blocks. 24VDC
Push-in connection blocks. 24VDC
Model| Order code| Description
---|---|---
TSR20
TSR2OP| 2TLA010061R0000
2TLA010061R0001| Screw compression connection blocks. 24VDC
Push-in connection blocks. 24VDC
TSR2OM
TSR2OM P| 2TLA010061R0100
2TLA010061R0101| Screw compression
connection blocks. 85-265VAC/120-375VDC
Push-in connection blocks. 85-265VAC/120-375VDC
USR10
USR1OP| 2TLA010070R0000
2TLA010070R0001| Screw compression connection blocks. 24VDC
Push-in connection blocks. 24VDC
USR22
USR22P| 2TLA010070R0400
2TLA010070R0401| Screw compression connection blocks. 24VDC
Push-in connection blocks. 24VDC
10.2 Accessories and spare parts
Type | Order code | Description |
---|---|---|
Connection block | 2TLA010099R0000 | Screw compression type |
Connection block | 2TLA010099R0001 | Push-in type |
Coding kit | 2TLA010099R0100 | For coding connection block |
Dimensions
All dimensions are in mm.
11.1 Sentry
Measure | Connection block type |
---|---|
Screw connection type | Push-in type |
A | 120 |
B | 22,5 |
C | 120 |
Technical data
12.1 Technical data
Manufacturer
ABB Electrification Sweden AB
SE-721 61 Vasteras
Sweden
Note!
While every effort has been taken to ensure the accuracy of the information
contained in this document, ABB cannot accept responsibility for errors or
omissions and reserves the right to make changes and improvements without
notice. Performance data given in
this document is provided as a guide for the user in determining suitability
and does not constitute a warranty. It may represent the result of ABB’s test
conditions, and the users must correlate it to actual application
requirements. Actual performance is subject to the ABB Warranty and
Limitations of Liability.
**Note!
There may be working points that will lead to higher performance for a
specific application. An example would be the combination of installation
distance between products, total load current and ambient temperature.
Caution!**
The difference between absolute maximum rating and max operating rating is the
following: The product will have full performance as long as all parameters
are within operating rating, in any combination If any of the values in
Absolute maximum rating are exceeded, the relay must be disposed.
Absolute maximum rating
Maximum voltage rating for R”te2| 30 VDC
Maximum voltage rating for X4 “te2| 30 VDC
Maximum operating breaking voltage for relay contacts| 500 Vp
Maximum voltage rating for NO/NC contacts| 265 VAC or 350 VDC
Maximum current rating for 1 NO relay contact| 8 A
Maximum current rating for 1 NC relay contact| 5 A
Maximum load capacity, Ylth2 Note 1| <722
Note 1: Ylth2 is the sum of the square for each relay output contact. For
example: 11 = 2 ARMS; 12 4 ARMS; 1 3 = 5 ARMS; 1 4 = 1 ARMS —> lith2 = 4 + 16
-
25 + 1 = 462
Note 2: Fault voltages up to 60 V is not dangerous but the safety relay might be broken or its performance might be degraded.
Power supplyInput signal type| PELV/SELV
Internal consumption| 2W
Note!
BSR10 is supplied with power through its signal input port R.
Relay output specification
Relay output configuration| 3 NO + 1 NC
Maximum operating switching voltage Note| 250 VAC
Overvoltage category| II
Rated impulse withstand voltage| 4 kV
Rated operational voltage| 250 VAC
Minimum operating contact load| 5 VDC / 10 mA (15 VDC / 3 mA)
Maximum operating switching frequency| 0.5 Hz
Rated isolation voltage| 400 V
Note!
In a 400 V system a 3 phase load shall only be used in a star connection.
NO contact
AC load (AC15, AC1)| Rated operating voltage (Ue) 250 VAC
Rated operating current (le)| 1 contact 5A
2 contacts 5A
3 contacts 4.6A
DC load (DC13, DC1)| Rated operating voltage (Ue) +24 VDC
Rated operating current (le)| 1 contact 6A
2 contacts 5.6A
3 contacts 4.6A
Required fuse| 6.3 A gG, >=1 kA short circuit protection (6 A according to U
L248)
NC contact
AC load (AC15, AC1)| Rated operational voltage (Ue) 250 VAC
Rated operational current (le) 0.5A
DC load (DC13, DC1)| Rated operational voltage (Ue) +24 VDC
Rated operational current (le) 2A
Required fuse| 4 A gG (4 A according to UL 248)
Safety device interface specification
Input (I) R1 and R2|
Maximum operating input voltage| 27.6 VDC
Minimum input high voltage (VIH,,,,,) Note 1| 15 VDC
Maximum input low voltage (VILmax) Note 2| 1 VDC
Maximum current sink (Isink) Note 3| 200 mA
Note 1: Voltage level above VI Hr„,,, is interpreted as logic “1”, in
worst case operating conditions.
Note 2: Voltage level below VILmax is interpreted as logic “0”, in worst
case operating conditions.
Note 3: If VIH ?15 VDC is applied to R1 and R2 (I sink is typical
2.8/VDCR).
Test/start/reset interface specification
Input/Output (I/O) X4
Minimum input high voltage (VIH,,,„) Note 1| 15 VDC
Maximum input low voltage (VILmax) Note 2| 2 VDC
Typical input impedance| 0,5-3 kΩ
Maximum current sink (1,,,k)| 55 mA
Test/start/reset interface specification
Note 1: Voltage level above VIH min is interpreted as logic “1”, in worst
case operating conditions.
Note 2: Voltage level below VIL max is interpreted as logic “0”, in worst
case operating conditions.
Response time
Response time at activation Start| ≤ 40 ms
Response time at inactivation| ≤ 20 ms
Electrical operations lifetime|
---|---
Load Σ lth 2 ≤ 64| AC1, AC15| 160 000 operations
DC1, DC13| 100 000 operations
Measurement conditions:
- Maximum breaking voltage for relay contacts: 250 V
- Maximum switching voltage for relay contacts: 400 V
- Rated current
- Switching frequency ≤ 0.1 Hz (Switching frequency > 0.1 Hz will shorten life.)
- T ≤ 55 °C
- No arc suppression (Usage of arc suppression will prolong life but may increase response time at inactivation.)
- 3 phase load in a star connection.
Mechanical data
Weight| | 190 — 230 g
Material| Housing| PA66 with 25 % fiberglass (UL94 VO)
Connection block, screw compression type| PA66 (UL94 VO)
Connection block, push-in type| PA66 with 25 % fiberglass (UL94 VO)
Opener, push-in type| PBT/GF (UL94 VO)
Color| Housing| Yellow
Connection block, screw compression type| Black
Connection block, push-in type| Black
Opener, push-in type| Orange
Attachment requirements| | 35 mm DIN rail (DIN 50022)
Environmental data
Pollution degree| II
Protection class| Safety relay| IP20
Enclosure for installation| At least IP54. Lockable.
Ambient temperature range for operation within specified operation range|
-25°C – +55°C
Ambient temperature range for storage| -40°C 5Ta 5 +70°C
Humidity range for operation| 10 % 5 Rh 5 90 %, no icing, occasional
condensation
Humidity range for storage| 10 % 5 Rh 5 95 ‘Vol no icing, occasional
condensation
Environmental data
Maximum temperature gradient| 2°C/min
Altitude| Suitable for use at ≤ 2000 meters above sea level
Vibration| 10-55 Hz sine, 0.35 mm (1 oct/ min 20 sweep cycles, all directions)
Shock| 5g, 11 ms Half sine +/- 100 Shocks
EU Directive Compliance|
Directives| European Machinery Directive 2006/42/EC
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU
RoHS3 Directive 2015/863
UK Regulations Compliance
Regulations| 2008 No.1597 Supply of Machinery (Safety)
Regulations (MD)
2012 No.3032 Restriction of the Use of Certain
Hazardous Substances in Electrical and
Electronic Equipment Regulations (RoHS) 2016 No.1091 Electromagnetic
Compatibility
Regulations (EMC)
US/CA Compliance
Application standard compliance| UL 60947-5-1:2014
CSA C22.2 No. 60947-5-1:2014
CSA B44.1
Standard compliance and approvals
Application standard compliance| EN ISO 13851:2019
EN ISO 13856-1:2013
EN ISO 13856-2:2013
EN ISO 13856-3:2013
Functional safety standard compliance| IEC 61508-1–4:2010, up to SIL3
EN ISO 13849-1:2015, up to PLe/Cat.4
EN 62061:2005, up to SILCL3
EN 61511-1:2003
UL 61508
Electrical safety standard compliance| EN 50178-1:1997
EN 60204-1:2018
EN 60664-1:2007
IEC 60947-5-1:2009
Electromagnetic compatibility standard compliance| EN 61326-3-1:2008
Approvals
CE
TÜV SÜD
Approvals
cULus
CCC
RCM
S
KC
UKCA
Standard
IEC 61508| PFHD 3.0E-9 and PFD 5.2E-6 (see chapter 8.2 Scheduled test)
EN ISO 13849-1, EN 62061| PFHD 3.0E-9
Mission time| 20 years
Information for use in USA/Canada
Intended use| Applications according to NFPA 79
Power source| A suitable isolating source in conjunction with a fuse in
accordance with UL248. The fuse shall be any (JDYX/7) fast acting, ratings
250V, 4 A,
IR200A, and be installed in the +24 VDC and 230VAC power supply to the device
in order to limit the available current.
Declaration of conformity
EC Declaration of conformity
(according to 2006/42/EC, Annex 2A)
We ABB Electrification Sweden AB SE-721 61 Västerås Sweden| declare that the
safety components of ABB AB manufacture with type designations and safety
functions as listed below, is in conformity with the Directives
2006/42/EC – Machinery
2014/30/EU – EMC
2011/65/EU – RoHS
2015/863 – RoHS3
---|---
Authorised to compile the technical file| ABB Electrification Sweden AB
SE-721 61 Vasteras Sweden
Product
Safety relay
Sentry, all versions of
USR10, USR22, SSR10M,SSR10,
SSR20M, SSR20, SSR32, SSR42,
TSR10, TSR20M, TSR20, BSR10,
BSR11, BSR23| EC type-examination certificate
M6A 049833 0032 Rev.00
Notified Body| TÜV Süd Product Service GmbH
Ridlerstrasse 65
80339 München Germany
Notified body No. 0123
Used harmonized standards| EN ISO 12100:2010, EN ISO 13849-1:2015,
EN 62061:2005+A2:2015, EN 60204-1:2006+A1:2009,
EN 60664-1:2007, EN 61000-6-2:2005, EN 61000-6-4:2007
Other used standards| EN 61508:2010
Magnus Backman
R&D Manager
Kungsbacka 2021-11-02
Declaration of conformity
(according to 2008 No 1597)
We ABB Electrification Sweden AB SE-721 61 Vasteras Sweden| declare that the
safety components of ABB AB manufacture with type designations and safety
functions as listed below, is in conformity with UK Statutory Instruments (and
their amendments) 2008 No 1597 – Supply of Machinery (Safety) Regulations (MD)
2016 No. 1091 – Electromagnetic Compatibility Regulations (EMC) 2012 No 3032 –
Restriction of the Use of Certain Hazardous Substances in Electrical and
Electronic Equipment Regulations (RoHS)
---|---
Authorised to compile the technical file| ABB Ltd. Tower Court
Coventry CV6 5NX
United Kingdom
Product
Safety relay Sentry| USR10, USR22,
SSR10M,SSR10, SSR20M,
SSR20, SSR32, SSR42,
TSR10, TSR20M, TSR20,
BSR10, BSR11, BSR23
Used designated standards| EN ISO 12100:2010, EN ISO 13849-1:2015,
EN 62061:2005+A2:2015, EN 60204-1:2006+A1:2009,
EN 60664-1:2007, EN 61000-6-2:2005, EN 61000-6-4:2007
Other used standards| EN 61508:2010
Magnus Backman
R&D Manager
Västerås 2021-03-28
abb.com/lowvoltage
Original
https://new.abb.com/low-voltage/products/safety-products
2TLC010060M0201 Rev.G
ABB Electrification Sweden AB
SE-721 61 Vasteras
SwedenSentry
BSR10 Product Manual (EN) revG 2TLC010060M0201