SUNAMP D0085 Thermino ePlus xPlus with PV Instruction Manual
- September 21, 2024
- SUNAMP
Table of Contents
D0085 Thermino ePlus xPlus with PV
Specifications:
- Model: 4 Noks Power Reducer SA
- Cable Type: 2.5 mm2, 3 Core H05VV-F sheathed cable
- Input Voltage: ~230V, 16A
- Switch Type: Double pole isolating switch, Min. 16A
- CT Clamp: Yes
Product Usage Instructions:
Installation:
-
Refer to the provided Installation Manual for detailed wiring
instructions. -
Ensure proper cable size and type are used for
connections. -
Connect the input terminals (L, N) and output terminals (A, B)
as per the provided diagram. -
Use a double pole isolating switch rated at minimum 16A for
safe operation.
Operation:
-
Ensure the power supply is connected to the designated input
terminals. -
Monitor the device for proper functioning and check connections
periodically. -
Follow any specific instructions provided by additional
components like heat battery controllers.
Maintenance:
-
Regularly inspect cables and connections for signs of wear or
damage. -
Keep the device clean and free from dust or debris that may
affect performance.
FAQ:
Q: What should I do if the device is not functioning
properly?
A: Check all connections, ensure power supply is stable, and
refer to the troubleshooting section in the manual. If issues
persist, contact customer support.
Q: Can I use a different cable type for connections?
A: It is recommended to use the specified 2.5 mm2, 3 Core
H05VV-F sheathed cable for optimal performance and safety.
· ·
· · ·
4 Noks Power Reducer SA
Morsetto 2
TA+ TA- +10V CTRL GND A
Morsetto 1/ OUTPUT
A
B
Morsetto 3/ INPUT
L
N
Solar Live Solar Earth Solar Neutral
Solar Live Solar Earth Solar Neutral
OUTPUT
2.5 mm2 , 3 Core H05VV-F sheathed cable
Neutral
L1 L2 N1 N2 Solar Neutral Solar Earth Solar Live
PCBA Live Relay 1 Live PCBA Neutral Relay 1 Neutral
2.5 mm2 , 3 Core H05VV-F sheathed cable
INPUT
Solar Clamp Double pole isolating switch, Min. 16A
0.75 mm2 , 3 Core H05VV-F sheathed cable
~230V, 16A
supply
Permanent Earth Permanent Neutral Permanent Live
Note: 1) Heat Battery Controller Connection above only shows Power Terminal connections, for other Heat Battery wiring, please reference to Installation Manual provided with Heat Battery. 2) Solar Clamp should be placed based on the Instructions provided in the 4 Noks Power Reducer SA Installation manual.
Morsetto 1/ OUTPUT A B
Morsetto 2
TA+ TA- +10V CTRL GND A
Morsetto 3/ INPUT L N
0.75 mm2 , 2 Core H05VV-F sheathed cable
Volt-Free Grid Boost Switch
· · ·
SUPPLY L NE
MyEnergi EDDI
CT1 CT2 – + – +
HEATERS L1 L2 N N E E
Solar Live Solar Neutral
Solar Earth
2.5 mm2 , 3 Core H05VV-F sheathed cable
Double pole isolating
switch, Min. 16A
~230V, 16A
supply
Neutral
0.75 mm2 , 3 Core H05VV-F sheathed cable
2.5 mm2 , 3 Core H05VV-F sheathed cable
PCBA Live Relay 1 Live PCBA Neutral Relay 1 Neutral
L1 L2 N1 N2
Permanent Earth Permanent Neutral Permanent Live
Solar Earth Solar Neutral
Solar Live
Note: Heat Battery Controller Connection above only shows Power Terminal connections, for other Heat Battery wiring, please reference to Installation Manual provided with Heat Battery.
· ·
· · ·
·
·
·
·
·
·
·
· · ·
· · ·
LOAD
MyPV AC Thor
LAN connection
Temperature sensor
Single Phase Mains Connection
Solar Live Solar Neutral
Solar Earth
2.5 mm2 , 3 Core H05VV-F sheathed cable
PCBA Live Relay 1 Live PCBA Neutral Relay 1 Neutral
Neutral
L1 L2 N1 N2 Solar Earth Solar Neutral Solar Live
2.5 mm2 , 3 Core H05VV-F sheathed cable
Double pole isolating
switch, Min. 16A
0.75 mm2 , 3 Core H05VV-F sheathed cable
~230V, 16A
supply
Permanent Earth Permanent Neutral Permanent Live
Note: Heat Battery Controller Connection above only shows Power Terminal connections, for other Heat Battery wiring, please reference to Installation Manual provided with Heat Battery.
Find a short Quickstartguide here
Find a full operation manual here
· · ·
Power Diverter Model 3
A In N In E
A Out N Out E
Economy Rate Sense
AN E
CT Clamp
1 2 3
Solar Earth Solar Neutral Solar Live
Solar Earth Solar Neutral Solar Live
2.5 mm2 , 3 Core H05VV-F sheathed cable
Double pole isolating
switch, Min. 16A
~230V, 16A
supply
Neutral
0.75 mm2 , 3 Core H05VV-F sheathed cable
2.5 mm2 , 3 Core H05VV-F sheathed cable
PCBA Live Relay 1 Live PCBA Neutral Relay 1 Neutral
L1 L2 N1 N2
Permanent Earth Permanent Neutral Permanent Live
Solar Earth Solar Neutral
Solar Live
Note: Heat Battery Controller Connection above only shows Power Terminal connections, for other Heat Battery wiring, please reference to Installation Manual provided with Heat Battery.
· ·
· · · · ·
· · · ·