Thermo SCIENTIFIC CM-3CDEFT-32 3-Phase Couple Test System Instruction Manual
- June 12, 2024
- Thermo Scientific
Table of Contents
- Thermo SCIENTIFIC CM-3CDEFT-32 3-Phase Couple Test System
- Product Information
- Product Usage Instructions
- Product Safety
- Immunity Testing Guidelines
- Safety Concerns During Immunity Testing
- Inappropriate Uses
- Description
- Installation
- Electrical Supply Requirements
- Physical Environment
- Operating limits
- Storage limits
- Special Considerations for EFT Testing
- Handling, Transportation, Storage
- Introduction
- Maintenance
- Troubleshooting
- CONTACT
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Thermo SCIENTIFIC CM-3CDEFT-32 3-Phase Couple Test System
Product Information
Product Name | Thermo Scientific CM-3CDEFT-32 3-Phase Coupler/Decoupler |
---|---|
Manufacturer | Thermo Fisher Scientific Corporation |
Website | http://www.thermo.com/esd |
Contact Number | 978-275-0800 |
Address | 200 Research Drive, Wilmington, MA 01887-4442, USA |
Product Usage Instructions
Follow the below steps for installation:
- Refer to the assembly instructions provided in the manual.
- Select the appropriate voltage for the CM-3CDEFT-32.
- Ensure proper cabling and interconnections are made.
- Check the electrical supply requirements and connect the instrument accordingly.
- If using the CM-3CDEFT-32 with Ground-Fault Interrupters (GFI), follow the instructions provided.
- Consider the physical environment and ensure the instrument is placed within the specified operating limits.
- Take into account the storage limits for the instrument.
- If conducting immunity testing, prepare the test area accordingly.
- Take note of any special considerations for immunity testing or EFT testing.
- Handle, transport, and store the instrument with care.
Product Safety
The following safety instructions have been included in compliance with safety standard regulations. Please read them carefully.
- Read Instructions — Read all safety and operating instructions before operating the instrument.
- Retain Instructions — Retain all safety and operating instructions for future reference.
- Heed Warnings – Adhere to all warnings on the instrument and in the operating instructions.
- Follow Instructions — Follow all operating and use instructions.
- Water and Moisture — Do not use the instrument near water.
- Carts and Stands — Use the instrument only with a cart or stand that is recommended by the manufacturer or included as part of the CE Master system.
- Wall or Ceiling Mounting — Do not mount the instrument on a wall or ceiling.
- Ventilation — The instrument should be situated so that its location or position does not interfere with its proper ventilation. Do not install in a cabinet or other situation that may impede the flow of air through the ventilation openings.
- Heat — The instrument should be situated away from heat sources such as heat registers or other instruments which produce heat.
- Power Sources — Connect the instrument only to the type of power source described in the operating instructions or as marked on the instrument.
- Grounding or Polarization — Take precautions to insure that the grounding of the instrument is not defeated. Operate only with grounded power cord.
- Power Cord Protection — Place power supply cords so that they are not likely to be walked on or pinched by items placed on them or against them. Pay particular attention to cords at plugs, convenience receptacles, and the point where they enter and exit the instrument.
- Cleaning — Clean the instrument only as recommended by the manufacturer.
- Non-Use Periods — Unplug the power cord of the instrument when it will be left unused for a long period of time.
- Lifting and Carrying — When moving or installing a CM-3CDEFT-32 follow the instructions given in the Installation section of this manual; The CM-3CDEFT-32 requires two people for moving.
- Object and Liquid Entry — Take care that objects do not fall and that liquids are not spilled into the enclosure through openings.
- Defects and Abnormal Stress — Whenever it is likely that the normal operation has been impaired make the equipment inoperable and secure it against further operation. Normal operation is likely to be impaired if, for example, the instrument: Shows visible damage. Fails to perform the intended function. Has been subject to prolonged storage under unfavorable conditions. Has been subjected to severe transport stresses.
- Damage Requiring Service — The instrument should be serviced by qualified service personnel when: The power supply cord or the plug has been damaged. Objects have fallen or liquid has been spilled into the instrument. The instrument has been exposed to rain. The instrument does not appear to operate normally or exhibits a marked change in performance. The instrument has been dropped, or the enclosure has been damaged.
- Sitting or Climbing — Do not sit or climb upon the instrument or use it as a step or ladder.
- Adapters, cables, and accessories — Use only adapters, cables, and accessories which have been approved for use with this unit. Use only MultiContact Safety Plugs for connections to the front panel of the CM-3CDEFT- 32 – use of any other connections may result in risk of electric shock.
- EUT load may restart automatically — The thermal protection within the CM-3CDEFT- 32 is self-resetting. In the event of an Overload, as indicated by the chassis-mount Overload indicator, switch the EUT power switch off or remove EUT Mains input and wait for Overload to clear.
The CM-3CDEFT-32 3-Phase Coupler/Decoupler is designed to operate with the Thermo Scientific EMCPRO series. Use of the CM-3CDEFT-32 with any other equipment may result in risk of electric shock, damage to equipment, and risk of fire.
Immunity Testing Guidelines
- DO NOT WORK ALONE.
- Do not use the equipment in conditions other than reasonable laboratory conditions. There should be no condensing humidity or water standing on the floor or work surfaces; there shouldn’t be significant dust or other contamination.
- Ensure that NO ONE is touching the equipment under test (EUT) during the test or immediately after the test until AC power to the EUT has been turned off.
- Ensure that there is a barrier to act as protection in case the equipment under test explodes. This may happen due to power-follow1 after a failure. The barrier should be interlocked to prevent surging and to disconnect all AC if the barrier is removed.
- The equipment under test must be surrounded by sufficient insulating material to withstand twice the surge voltage. Consider distance to the floor or table and walls if air is the insulating material.
- Ensure that the proper supply mains voltages are applied to both Thermo Scientific equipment and to the equipment under test, and that the AC branch circuit is capable of supplying the current.
- The ground (protective earth), neutral and phase lines of the AC supply to the equipment under test supply must be connected properly. Do not defeat the protective earth connection.
- The ground (protective earth), neutral and phase lines of the AC supply to the Thermo Scientific equipment must be connected properly. Do not defeat the protective earth connection.
- When surging a powered EUT, the mains supply to the equipment under test must be capable of handling the potential AC fault current (e.g. do not use a UPS to power the EUT).
- Use only equipment which is designed to be safe for the test being performed.
- Do not test in a potentially explosive atmosphere (e.g. gas fumes).
- Never use equipment that is operating in a strange manner, or that shows clear indication of abuse.
- If probes are in use, be sure they are differential probes which have no ground connection to the surged ground or to the equipment under test.
Power-follow is a condition where the event causes a low-impedance path which full mains current may then flow through. One example of this is a gas-tube arrestor, which maintains a high impedance until a event switches it to a low- impedance state; the low-impedance state is maintained until the mains voltage drops below a critical threshold. Similar effects can be seen due to electrical arcs or exploded components.
Safety Concerns During Immunity Testing
Immunity testing is hazardous. The equipment under test (EUT) can ignite,
possibly explosively. Noxious, toxic and sometimes fatal fumes can be
generated by the burning equipment. Accumulated gases may ignite explosively
(i.e., flashover).
In an environment where Immunity testing takes place, it is absolutely
crucial that these minimum safety precautions be taken:
- Immunity testing should be performed only by properly trained test personnel who are experienced in conducting such test, or be observed and supervised by such experienced personnel. No person subject to heart or neurological conditions should be allowed to conduct surge tests. Persons with pacemakers should not be allowed in or near the area where testing is conducted.
- Never leave a procedure or a test setup unattended.
- All personnel working in the area must be shielded with appropriate eye protection, body protection and electrical protection. They should not be allowed to work in a direct line of a possible explosion of the equipment under test.
- The test area should be a clear and unobstructed environment dedicated to such tests.
- The test area should be equipped with ventilating hoods and blowers to remove gases that may be caused by exploding or burning components.
- The test area should have nonflammable walls and floors plus shielding to contain exploding parts and flames.
- There must be fire extinguishers certified for use in electrical and chemical fires readily available at the test site. DO NOT USE WATER TO EXTINGUISH AN ELECTRICAL FIRE.
- All flammable materials and debris must be outside the test area, and the area must be well marked, preferably by physical barriers, to prevent accidental intervention by nontest personnel while a test is in progress
Inappropriate Uses
- The unit must be kept within the environmental limits of the operating requirements. This includes not using the unit in condensing humidity.
- There are no User Serviceable parts inside; do not remove covers.
- Use only adapters and cables and accessories which have been approved for use with this unit.
- Connect only to Thermo Scientific equipment which has been approved for use with this unit. DO NOT connect to any other test equipment.
- DO NOT modify front panel jumpers for multiple line Surge coupling.
- Read and follow directions for connecting equipment.
Operating the CM-3CDEFT-32 with any equipment other than those recommended may damage equipment, create a shock hazard, and create a fire risk!
Description
The CM-3CDEFT-32 3-Phase Coupler/Decoupler is a single-enclosure, floor- standing ordesktop test system designed to couple EFT events to a 3-phase AC Mains. Single & Multiple line coupling for EFT per IEC standards with the Thermo Scientific EMCPRO PLUS Test System. A Coupler/Decoupler is required to apply surge and EFT to the AC Mains of the Equipment Under Test. The Coupler/Decoupler connects the output of a surge generator to the EUT AC Mains [Coupler] and minimize surge or EFT energy which may couple to the AC Mains of the building [Decoupler]. The CM-3CDEFT-32 is a manual tester, in which the EFT operation is programmed from the front panel via switches. Programming is fast and simple. Operation is semi-automatic when used with EMCPro series test equipment, a Personal Computer, and the CEWare software, where the CEWare software can provide pauses and prompt the operator to change switches .
Installation
Assembly Instructions
The CM-3CDEFT-32 requires two people for unpacking. Check the packaging
materials and follow any special unpacking instructions shipped with your
unit. The CM-3CDEFT-32 comes fully assembled. Save all shipping materials
(shipping boxes, foam pieces, bags, and special instructions) for possible
future shipments. The original shipping materials must be used whenever the
CM-3CDEFT-32 is returned for service. Carefully check all shipping materials
for accessories which may be packaged with the CM-3CDEFT-32.
Voltage Selection
The CM-3CDEFT-32 must be set for the mains voltage at your site. This is
usually done before shipment, but must be checked before installation and use.
On the rear of the CM-3CDEFT-32 check that the voltage select block is set to
the proper mains voltage. If not correct, remove line cord, pry the voltage
select block from the inletassembly using a small screw driver; rotate the
block to the proper voltage, as shown to the right, and fully insert in
holder.
Cabling and Interconnections
The CM-3CDEFT-32 can be placed alongside, placed on top or placed under an
EMCPro. The CM-3CDEFT-32 has an AC Mains cord which plugs into the rear of the
unit, via a standard IEC-320 connector. This provides fan and control power to
the CM-3CDEFT-32, and is required for operation. The EUT Power input is a pin
and sleeve connector, rated for the current and voltage of the Equipment Under
Test. A cord is provided to connect the CM-3CDEFT-32 to the building AC mains.
A matching pin and sleeve connector for connection to the building mains must
be provided by the customer, and installation of this connector may require
the services of an electrician. Connection to the Equipment Under Test — the
EUT Load Connection to the Equipment Under Test (EUT) is via five safety
sockets on the lower right of the CM-3CDEFT-32 front panel. Five, unassembled
safety socket connectors are provided with the CM-3CDEFT-32; additional
connectors are available from MultiContact. The cable to the Equipment Under
Test must be built to the customer requirements. Thiswiring should be done to
meet all applicable, local, safety requirements. In general — but not
exclusively — these requirements include the following:
- The wiring to the EUT must be rated to withstand the applied mains voltage.
- The wiring to the EUT should be rated to withstand twice the applied pulse voltage, or the wiring should be isolated from the operator and ground so that insulation breakdown does not create a hazard.
- The wiring to the EUT should be rated for the expected fault current of the CM-3CDEFT-32 (32 amperes) or additional current limiting and protection should be added.
- WHERE CONNECTION TO PE IS REQUIRED FOR SAFETY, A PE CONNECTION MUST BE PROVIDED.
It is considered good practice for the PE wired connection to be made longer
than any of the other connections; in the event of an accidental
disconnection, the PE terminal is disconnected last. In addition, some loads
may require proper phasing for proper operation. The user must determine the
phase relationships of the building AC mains and check this relationship at
the CM-3CDEFT-32 outputs
Caution: Construction and assembly of cord and connection of EUT loads
should be done only by trained personnel with knowledge of electrical safety
practices, and practical knowledge of the electrical and safety requirements
of the load. Connecting the EMCPro EFT Output to the CM-3CDEFT-32 Input Thermo
Scientific CM-3CDEFT-32 3-Phase Coupler/Decoupler
- The EFT cable connects the CM-3CDEFT-32 EFT inlet to the EMCPro EFT-Output jack.
- The cable is an HN-coax, which screws tight to each connection.
- The maximum programmed EFT voltage should not exceed the 4400V rating of the CM-3CDEFT-32
Direct Current Power to EUT
The CM-3CDEFT-32 can accept a single-phase AC, or Direct Current (DC) power
source at the EUT input and provide it to the EUT output. When connecting a
single-phase or DC source it is important to note the assignment of EUT inlet
and outlet connectors. The CM-3CDEFT-32 is internally protected at 32 or 16
amperes. When used with a singlephase AC, or Direct Current (DC) power source,
if the EUT load or cabling requires current limiting protection of less than
the CM-3CDEFT-32 rating, it is the responsibility of the user to provide that
protection.
Electrical Supply Requirements
The CM-3CDEFT-32 system power is configured for one of two voltage ranges:
- 100 – 120 Vac, 50/60 Hz
- 220 – 240 Vac, 50/60 Hz
The voltage range configured is identified by label on the rear panel of the CM-3CDEFT-32. The voltage range may be easily changed with a screwdriver, following the directions of the Installation, Voltage Selection section of this manual. The CM-3CDEFT-32 is rated for EUT/ AC power source of:
CM-3CDEFT-32
- 250/433 Vac, 32 ampere, 3-phase, 5-wire, 50/60 Hz (U.S.)
- DC : 30Adc up to 24Vdc; 25A up to 48V; 8A up to 100V
The EUT, AC power source should be fused or protected for a maximum of 100
amperes. The over current protection of the CM-3CDEFT-32 includes detection of
imbalanced phasecurrents. When using the CM-3CDEFT-32 with a one-phase load, a
two phase load, or a load with extreme imbalance between phase currents, the
over current protection will trip at a load current of 85% of the CM-3CDEFT-32
rating. The EUT power source must have adequate capacity for full power-
follow2 in the event that testing causes an equipment failure. Using a supply
without sufficient capacity may result in a failure being masked.
Acceptable power sources include:
- A dedicated branch circuit
- The dedicated output of a motor-generator (MG) set.
- The output of a properly rated and installed isolation transformer.
2 Power-follow is a condition where the pulsed event causes a low-impedance path through which fault level mains current may then flow: possibly hundreds of amperes or greater. One example of this is a gas-tube arrestor, which maintains a high impedance until a surge event switches it to a low-impedance state; the low-impedance state is maintained until the mains voltage drops below a critical threshold. Similar effects can be seen due to electrical arcs or exploded components.
Use of the CM-3CDEFT-32 with Ground-Fault Interrupters (GFI)
- Problems may result when using the CM-3CDEFT-32 on AC mains protected by Ground- Fault Interrupters (GFIs).
- The problem is due to a clamp circuit, protecting the building Mains from excessive voltage during surge, and from the coupling network which connects the generator to the AC mains during the event, and creates a short pulse of mains current in PE, tripping the GFI. There are two solutions to this problem:
- The first solution is to power the EUT from a source that does not have a GFI device installed. This solution may not be practical in some locations due to building codes or safety regulations.
- The second solution is to install an isolation transformer between the AC mains and CM- 3CDEFT-32. The isolation transformer should be rated for the current of the EUT load.
Note: A solid-state regulated line source such as an uninterruptable power supply (UPS) or a power frequency amplifier will generally not have the instantaneous capacity or full power-follow required for Surge and PQF testing, and therefore should not be used as the AC power source for any equipment being tested.
Physical Environment
The CM-3CDEFT-32 systems are intended for operation in a laboratory environment, protected from excess dust, humidity, and temperature.
- No condensing humidity or standing water on the floor or work surfaces.
- No significant dust or other contamination.
Operating limits
- Temperature: 15 – 40° C
- Humidity: 10 – 85%, non-condensing
- Altitude: 10,000 feet max.
Storage limits
- Temperature: 0 – 60° C
- Humidity: 10 – 90%, non-condensing
- Altitude: 10,000 feet max
Test Area Considerations and Site Preparation
Conduct Immunity testing under sound laboratory conditions. Verify the
following:
- No condensing humidity or standing water on the floor or work surfaces
- No significant dust or other contaminants
- Clear and unobstructed vision
- Adequate ventilation, including ventilating hoods and blowers to remove gases
- Nonflammable walls and floors
- Barriers surrounding the EUT to contain exploding parts and flames
- Appropriate fire extinguishers for electrical and chemical fires. DO NOT USE WATER TO EXTINGUISH AN ELECTRICAL FIRE.
- No flammable materials or debris inside the test area. The area must be well marked, preferably by physical barriers
- Keep unauthorized personnel out of the area during testing
Allow at least six inches clearance from the wall or other equipment on both
sides of the instrument for proper air flow. The system must be mounted on a
level surface. For EFT testing the EFT generator and CM-3CDEFT-32 should be
mounted on the floor, on the ground reference plane. For other testing, the
EFT generator and CM-3CDEFT-32 may be placed on a table that can support the
weight of the units. They may also be placed on a sturdy cart. However, since
the unit is heavy, make certain that the instrument and cartcombination is
stable, and cannot be easily tipped – particularly if the wheels strike a bump
on the floor such as the edge of a rug, a pebble or a small piece of hardware.
Special Considerations for Immunity Testing
Immunity testing is best done in an area cleared of obstructions. Clearly mark
the boundaries of the area. There is the possibility that the surge may flash
over to circuits or metal objects not directly under test, and that components
in the equipment being tested may explode or ignite under the stress of the
test. Whenever possible, enclose the equipment under test within a fireproof
and explosion-proof barrier having insulation capable of withstanding at least
twice the maximum surge voltage. Never allow direct line-of-site view of
components that may explode or ignite. If visual observation is required, use
a robust transparent barrier of suitable thickness for protection. Immunity
testing should only be carried out by fully trained personnel who are informed
of the hazards of such testing, and who have full control over all of the test
equipment in the area.
Special Considerations for EFT Testing
EFT testing involves the use of very high frequency pulses. For this reason the testing standards specify the use of a ground reference plane in the area where EFT testing is performed. In addition, the standards specify the minimum and maximum spacings among the various equipment present in the test area. This device complies with the requirements of the EMC Directive, 89/336/EEC, as stated in the declaration of Conformity. However, EFT test pulses are by nature an interference test and can therefore create a possible source of disturbance to other electronic equipment that is not intended for test. This device should be used in an environment free of other equipment that could be affected by these emissions, or in a shielded room.The floor of the test area is to be covered with copper or aluminum with a minimum thickness of 0.01 inch, which must be bonded to building Protective Earth (PE) ground. In addition, the cabinet of the EFT generator and CM-3CDEFT-32 must be directly tied to the ground reference plane. Provision for a mounting bracket is made on the rear and bottom of the CM-3CDEFT-32 and the bracket and screws are provided. See the EMCPRO manual, for further information on EFT testing.
Handling, Transportation, Storage
Save all shipping materials (shipping boxes, foam pieces, bags, and special instructions) for possible future shipments. The CM-3CDEFT-32 requires two people for unpacking. Follow the instructions in the INSTALLATION section of this manual and any special instructions shipped with the unit. Issues related to transportation of CM-3CDEFT-32 models are identical to those for installation; the weight of the unit requires that two people help in packing and movement. When packing the unit for transportation the original shipping materials should be used, or new materials of equivalent strength and durability. For long storage intervals, unplug the power cords of the instrument and cover the instrument to protect from dust and liquid spills.
Introduction
A Coupler/Decoupler is required to apply surge and EFT to the AC Mains of the Equipment Under Test. The Coupler/Decoupler connects the output of a surge generator to the EUT AC Mains [Coupler] and minimize surge or EFT energy which may couple to the AC Mains of the building [Decoupler]. The circuitry to perform this is very simple. The generator is connected to the EUT output. Filter inductors and capacitors in each line attenuate EFT and surge energy and reduce the amount of energy escaping into the building AC Mains. The complications in this circuitry are in the details: constructing filter inductors which can block the volt-second product of a 6000 volt, 1.2x50uS pulse, yet which have very low coupling capacitance to avoid passing EFT energy. They must also safely couple the surge or EFT generator to a high- voltage AC Mains For EFT, the CM-3CDEFT-32 is designed to operate with the EMCPro series. The coupling network required to connect the surge to the AC Mains is built into the CM-3CDEFT-32. Operating the CM-3CDEFT-32 with any equipment other than those recommended may damage equipment, create a shock hazard, and create a fire risk! Thermo Scientific CM-3CDA 3-Phase Coupler/Decoupler The CM-3CDEFT-32 is programmed from the front panel, and all connections to the Equipment Under Test (EUT) are made from the front panel. The front panel controls and features are broken into three major groups: EMCPro to CM-3CDEFT-32 Interconnections, Equipment Under Test Connections and the User Interface (Programming).
EMCPro to CM-3CDEFT-32 Interconnections
- From the front Panel of the EMCPro and CM-3CDEFT-32 an HN-coax connects the
- CM-3CDEFT-32 EFT inlet to the EMCPro EFT Output to CCL jack.
- This cable screws tight to each connection. Maximum programmed voltage should not exceed the rating of the CM-3CDEFT-32 — 4400V).
Equipment Under Test Connections:
Connection to the Equipment Under Test (EUT) is via five safety sockets on the
lower right of the CM-3CDEFT-32 front panel. Five, unassembled safety socket
connectors are provided with the CM-3CDEFT-32; additional connectors are
available from MultiContact. The cable to the Equipment Under Test must be
built to the customer requirements. This wiring should be done to meet all
applicable, local, safety requirements. In general — but not exclusively —
these requirements include the following:
- The wiring to the EUT must be rated to withstand the applied mains voltage.
- The wiring to the EUT should be rated to withstand twice the applied pulse voltage, or the wiring should be isolated from the operator and ground so that insulation breakdown is not a problem.
- The wiring to the EUT should be rated for the expected fault current of the CM- 3CDEFT-32 (32 amperes) or additional current limiting and protection should be added.
- WHERE CONNECTION TO PE IS REQUIRED FOR SAFETY, A PE CONNECTION MUST BE PROVIDED.
User Interface (Programming)
Feedback to the operator is provided by three indicators on the front of the
unit:
- SYSTEM POWER is lit when the unit is powered — the rear power switch is set to ON and the system power cord connected. This indicator must be lit for the unit to operate.
- EUT POWER is lit when the EUT power switch on the front panel is set to ON — the EUT is energized.
- OVERLOAD is lit when there is an over temperature or over current fault and the EUT power switch on the front panel is set to ON. The unit will not operate while this indicator is lit.
Warning! EUT load may restart automatically!
The thermal protection within the CM-3CDEFT-32 is selfresetting. In the event
of an Overload, as indicated by the chassismount Overload indicator, switch
the EUT power switch off or remove EUT Mains input and wait for Overload to
clear.
Programming EFT
To program EFT, first connect the CM-3CDEFT-32 and EFT generator using the
coax cable provided with the CM-3CDEFT-32.
Connect EFT Output on the EFT generator to the coax connector of the CM- 3CDEFT-32. Use the cables supplied with the CM- 3CDEFT-32 — do not substitute. The EFTcable should be disconnected from both the CM-3CDEFT-32 and the EFT generator when not performing tests. The CM-3CDEFT-32 supports single- line to 5-line COMMON MODE EFT coupling per IEC 61000-4-4. The CM-3CDEFT-32 is manually programmed by setting the EFT COUPLING MODE switches to the desired coupling mode. The EFT can be coupled from 1 to 5 lines (L1, L2, L3, N, PE) in any combination.
All EFT events are with respect to the ground plane. The polarity of the event
is always as set at the EFT generator.
NOTE! EMCPRO Firmware v6.00 and up adds two new output modes for EFT
testing to accommodate separate calibrations for using the CM3CDEFT external
coupler/decoupler in Normal and Common mode. The previously-labeled “Direct”
output mode has been changed to “CCL” (the capacitive coupling clamp), because
all three modes use the “Direct” output connector.
Programming EFT
- For CM-3CDEFT-32 EFT operation the EMCPRO must be programmed with
- Output: Coupling set to — CM3CD NORMAL or CM3CD COMMON.
- Depending if performing single line or multiple line testing.
- This sets the EFT output to the EMCPRO front panel coax connector.
For all pre-programmed tests, remember that you are only testing the single coupling mode that you have programmed at the CM-3CDEFT-32 front panel. In many cases, for a complete test, you will have to change coupling mode and continue until all modes have been tested. The CM-3CDEFT-32 is a manual unit. it is programmed by switches on the front panel.Since the EMCPro is an automatic unit, some care must be taken on interfacing the two units and in programming. The CEWare software provides pauses and prompt features which can prompt the operator with pre-programmed messages and instructions for setting the CM-3CDEFT-32 switches, allowing semi-automatic testing.
Maintenance
-
Service and Maintenance Issues
There are no user serviceable parts within the CM-3CDEFT-32. Service is solely by Thermo -
Fisher Scientific trained, authorized technicians.
The system power connector contains a fuse block, holding two, 5mm, 1.0A 250V timedelay fuses. These may be replaced by removing the mains cordset from the power connector and prying the cover off the fuse holder with a small screw driver. -
Factory Inspection and Refurbishment
Factory Inspection and Refurbishment is available. Consult factory for terms and conditions. -
Calibration
Yearly calibration of the CM-3CDEFT-32 is recommended. -
Decommission Issues
There are no hazardous materials within the CM-3CDEFT-32 and no special issues in decommissioning.
Troubleshooting
This section aids in finding and solving any problems you may experience.
Troubleshooting Guide
In the event of a problem with the CM-3CDEFT-32 please follow the following
procedure.
- Verify that you have properly selected all test parameters on the EMCPRO.
- Check that the CM-3CDEFT-32 and EMCPRO are properly connected to the AC Mains.
- Check that the EUT is properly connected to the CM-3CDEFT-32.
- Check all interconnections for loose connections.
- Try cycling power to the EUT, EMCPRO and CM-3CDEFT-32.
- Check the following trouble-shooting guide, for your symptoms.
- Contact Customer Service for guidance.
CM-3CDEFT-32 Troubleshooting Guide
The EUT cannot be powered| Check that:
* The SYSTEM POWER indicator is lit.
* The SYSTEM POWER switch is ON (rear)
* The System power line cord is inserted and connected to the building AC mains
* The OVERLOAD indicator is not lit
* The EUT POWER switch is ON
* The EUT POWER indicator is lit
---|---
The OVERLOAD indicator is lit| Either there was an over-current condition on
the EUT load, or an internal over temperature condition within the unit. Both
conditions are self-resetting.
Turn the EUT POWER switch to off. Check the EUT load for possible shorts. Check that the units fans are operating. Wait 2 minutes and retry the EUT POWER switch.
WARNING! If the EUT POWER switch is ON, the EUT may start unexpectedly when the over temperature condition resets.
The SYSTEM POWER indicator is NOT lit.| Check that:
* The SYSTEM POWER switch is ON (rear)
* The System power line cord is inserted and connected to the building AC mains
* The voltage configuration block in the System power inlet receptacle is set to the proper Mains voltage.
* The fuses in the System power inlet receptacle are good.
Filing a Problem Report
When reporting a problem to Thermo Fisher Scientific Customer Service, please
include the serial number and model number from the rear panel of the CM-
3CDEFT-32.
CONTACT
- Mail, Fax, or phone your problem report to:
- Customer Service
- Thermo Fisher Scientific Corporation,
- 200 Research Drive
- Wilmington, MA01887-4442 USA
- Tel: 978-275-0800
- Fax: 978-275-0850
- http://www.thermo.com/esd. or your local, authorized service representative.
- Advanced Test Equipment Corp.
- www.atecorp.com.
- 800-404-ATEC (2832)
WEEE Compliance:
This product is required to comply with the European Union’s Waste Electrical
and Electronic Equipment (WEEE) Directive 2002/96/EC. It is marked with the
following symbol: Thermo Fisher Scientific has contracted with one or more
recycling/disposal companies in each EU Member State, and this product should
be disposed of or recycled through them. Further information on Thermo Fisher
Scientific’s compliance with these Directives, the recyclers in your country,
and information on Thermo Fisher Scientific products that may assist the
detection of substances subject to the RoHS Directive are available at
www.thermo.com/WEEERoHS. Thermo Scientific
CM-3CDEFT-32 3-Phase Coupler/Decoupler
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>