saxby lighting 103259 LED Anti Corrosive Batten Instruction Manual
- June 13, 2024
- saxby lighting
Table of Contents
saxby lighting 103259 LED Anti Corrosive Batten Instruction Manual
- Non-replaceable light source
- Replaceable conirol gear by a 2 professional
- Conformity with al relevant UKCA Directive requirements
- Conformity with al relevant EC Directive requirements.
- This product is Class 1, must be connected to earth.
- Waste electrical products should not be disposed of with household waste. Please recycle where facilities exist. Check with your Local Authority of local store for recycling advice.
- This product is not suitable for dimming,
- This product is rated at IP65. NI R EICIANE S
- Caution! Risk of electric shock!
Duration: 3 hours (180 Minutes)
Operating Temperature: 0°C -55°C
Mains input current : 22mA
input power in mains operation : 2.5W
Emergency power : 1W (Battery)
Battery Specification: LiFeP04 3.2V 1500mAH
Battery Charge Time: 24 Hours
Battery charge current: 200mA
Battery warranty: 2 years
Care and Safety
Live Voltages may be present in this unit even when turned off or when
completely disconnected. We recommend cleaning with a soft dry cloth. Do not
use solvents or abrasive cleaners as these could damage the finish For your
safety, always switch off the power supply before cleaning.
Thank you for purchasing this light fitting. Please read the instructions carefully before use to ensure safe and satisfactory operation of this product. Please retain these instructions for future reference.
Warning
This is a Class 1 product and must be earthed. Please read these instructions carefully before commencing any work This unit must be fitted by a competent and qualified electrician. Check the pack and make sure you have all the parts listed. Install in accordance with the IEE Wiring regulations and current Building Regulations. To prevent electrocution switch off at mains supply before installing or maintaining this fitting. Ensure other persons cannot restore the elecrical supply without your knowledge. If you are in any doubt, please consult a qualified electrician This light fitting should be connected to a fused circuit. If replacing an existing fitting, make a careful note of the connections. This product contains non-replaceable parts and cannot be serviced. If damage occurs the part should be scrapped. Waste electrical products should not be disposed of with household waste. Please recycle where facilities exist. Check with your local authority or retailer for recycling advice.
Layout
Plan the desired layout of these fittings carefully, ensuring the cables will reach the distances between the junction box and the each light ftting Avoid locating any cables in positions that would cause a hazard. Position cables and outdoor rated junction boxes (not supplied) away from areas where they may be atris from being cut, rapped or damaged. We recommend that you use HOSRN-F specification cable (not supplied) which is an outdoor grade, rubber sheathed cable. The mains supply cable must have a minimum cross section area of 1.0mm2 Cables must be protected using suitable conduit or plastic trunking. Take care not to drill nto any pipes or mains cables beneath the surface during mounting holes preparation This product can be installed on the ceiling or wall
Installation
Existing fitings must be completely removed before installation of a new product. Before removing the existing fitting, carefully note the position of each set of wires. Note that the switch is turned off before installation. The mounting surface must be flat and smooth to ensure a good fit.
- Hold the product in place and mark the position of the fixing holes. This may require the help of an assistant. If wall mounting, ensure that the product is level
- Take care to avoid damaging any concealed wiring and pipes. The correct fixings should be used for brick, cavity walls or plasterboard
- Ensure the ceiling or wallis capable of holding the wight of the product and then fix brackels in place.
- Open the diffuser cover by unfastening securing clips.
- Feed the supply cable through the end grommet and fix the light fitting into position. Alternatively, the grommet can be removed and the supplied cable gland fitted
- Connect the supply cable to the quick fit terminal block as detailed wiring diagram.
- Connect the battery output cable to the EM driver.
- Closs diffuser cover by clipping it into place
- Fix two suspension brackets into the position with the installation plugs and screws.
- Fix the light fitting by suspension brackets in place.
- + Replace fuse or circuit breaker and switch on. Your light is now ready for use.
Wiring
This product is Class | product must be earthed. They must be joined together and well insulated with good quality insulation tape. This is to ensure earth continuity throughout your property. Having correctly identified the wiring from your existing light fitting and connect to the connection block inside the product in the way on the right:
SUPPLY
Check that
- You have correctly identified the wires.
- The connections are tight.
- No loose strands have been left out of the connection block.
Maintained(Unswitched) Wiring :
The product on permanently and comes on during a power failure.
Maintained (Switched) Wiring:
The product is used as a normal light – switch on/off, light turns on/off.
Comes on during a power failure
Technical data
Supply Voltage: SUl 920,240V, 50 :
Bulb 103259 : 19W LED module (SMD), 4000K
Type: 103260 : 24W LED module (SMD), 4000K
103261: 35W LED module (SMD), 4000K
103262 : 30W LED module (SMD), 4000K
103263: 5OW LED module (SMD), 103264: 4000K 57W LED module (SMD),
4000K
103267: 24W LED module (SMD), 6500K
103268: 50W LED module (SMD), 6500K
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>