NOVUS TxIsoRail Isolated Transmitter User Guide
- June 13, 2024
- Novus
Table of Contents
TxIsoRail
ISOLATED TRANSMITTER – USER GUIDE − V1.0x A
SPECIFICATIONS
Sensor input: User defined. The supported sensors are listed in Table 1, along
with their maximum ranges.
Thermocouples: Types J, K, R, S, T, N, E, and B, according to IEC 60584
(ITS-90). Impedance >> 1 MΩ Pt100: 3-wire connection, Excitation: 180 µA, α =
0.00385, according to IEC 60751 (ITS-90).
For 2-wire Pt100, tie terminals 2 and 3 together.
Voltage: 0 to 50 mVdc, 0 to 10 Vdc. Impedance >> 1 MΩ.
Current: 0 to 20 mA, 4 to 20 mA. Impedance 15.0 Ω (+ 1.9 Vdc).
SENSOR TYPE | RANGE | MINIMUM MEASUREMENT SPAN |
---|---|---|
Thermocouple K | -150 to 1370 °C 1-238 to 2498 °F | 100 °C/ 212 °F |
Thermocouple J | -100 to 760 °C / -148 to 1400 °F | 100 °C / 212 °F |
Thermocouple R | -50 to 1760 °C / -58 to 3200 °F | 400 °C / 752 °F |
Thermocouple S | -50 to 1760 ‘Cl -58 to 3200 °F | 400 ‘Cl 752 °F |
Thermocouple T | -160 to 400 °C / -256 to 752 °F | 100 °C / 212 °F |
Thermocouple N | -270 to 1300 °C / -454 to 2372 °F | 100 °C / 212 °F |
Thermocouple E | -90 to 720 °C 1-130 to 1328 °F | 100 °C/ 212 °F |
Thermocouple B | 500 to 1820 °C 1932 to 3308 °F | 400 °C / 752 °F |
Pt100 | -200 to 600 °C 1-328 to 1112 °F | 40 ‘Cl 104 °F |
Voltage | 0 to 50 mV | 5 mV |
Oto1OV• | 1V | |
Current | 0 to 20 mA | 2 rnA |
4 to 20 mA | 2 rnA |
Table 1 – Transmitter input sensors
- Note: 0-10 Vdc input type requires an internal jumper switching.
Response time: < 500 ms
Electrical isolation: 1000 V for 1 minute between input and output.
Maximum load (RL): RL (max.)= (Vdc – 12) / 0.02 [Ω] Where: Vdc = Power supply voltage
Operating temperature: -40 to 85 °C / -40 to 185 °F
Humidity: 0 to 90 % UR
Electromagnetic compatibility: EN 50081-2, EN 50082-2
Internal protection against polarity inversion.
Cold Junction compensation for thermocouples.
Certifications: CE, UKCA.
1.1 4-20 mA MODEL
Output: 4-20 mA or 20-4 mA current, 2-wire type; linear to input signal.
Output resolution: 0.001 mA (14 bits)
Total accuracy: 0.30 % of maximum range for thermocouples, ±1 °C; 0.20 % of maximum range for Pt100, voltage, and current.
Power supply: 12 to 35 Vdc, voltage applied to the transmitter.
1.2 0-10 VDC MODEL
Output: Voltage 0 to 10 Vdc or 10 to 0 Vdc; linear to input signal.
Output resolution: 0.0006 V (14 bits)
Total accuracy: 0.25 % of maximum range for thermocouples, ±1 °C; 0.15 % of maximum range for Pt100, voltage, and current.
Power supply: 18 to 30 Vdc, voltage applied to the transmitter.
CONFIGURATION
When the transmitter is used with the factory setting, no further action is
required, and the transmitter is ready to be installed. When it is necessary
to change the configuration of the equipment, you should use SigNow software,
TxConfig software, or SigNow app.
To configure the equipment through any of the software, you must connect the
TxConfig Configuration Interface (purchased from the manufacturer or its
authorized representatives) to the USB port of the computer used and run the
selected software, as shown in Figure 1:
To configure the device via SigNow app, you need to use an OTG cable with the
TxConfig Configuration Interface and proceed with the recognition process (see
SMARTPHONE CONNECTIONS chapter).
On NOVUS website, you can download the configuration software for free. To
install it, simply run the file SigNowSetup.exe or the file TxConfigSetup.exe
and follow the instructions in the installer. The SigNow setup application can
be downloaded for free from the Google Play Store.
2.1 SOFTWARE AND APP
2.1.1 SIGNOW SOFTWARE
When running the SigNow software and connecting to the device, the following
screen will appear:
The bottom part of the screen displays information about the model, serial
number, and firmware version.
The configuration screen is divided into 4 sections: General,
Settings, Diagnostics and Firmware Update.
In the General (see above) and Settings screens, you can configure the device
by setting values and information for the following parameters:
- Sensor Type: Allows you to select the sensor to be used. See Table 1.
- Temperature Unit: Allows you to select the temperature unit to be used.
- Lower Limit: Allows you to define the minimum desired temperature for the configured output type.
- Upper Limit: Allows you to define the maximum desired temperature for the configured output type.
- Sensor Failure: Allows you to establish the output behavior when the transmitter indicates a failure: Minimum: Output current goes to < 3.6 mA (down-scale), typically used for refrigeration. Maximum: Output current goes to > 22.0 mA (up-scale), typically used for heating.
- Network Frequency: Allows you the network frequency to be used.
- Output Type: Displays the output type of the equipment, which will change according to the model (TxIsoRail 4-20 mA or TxIsoRail 0-10 Vdc).
- Zero Correction: Allows you to correct small deviations presented in the transmitter output, such as when changing a sensor.
In the SigNow manual, available on NOVUS website, you can get more specific information about the buttons and the process of diagnostics and firmware update.
2.1.2 TXCONFIG SOFTWARE
When running the TxConfig software and connecting to the device, the following
screen will appear:
The fields in the screen mean:
- Input Sensor: Allows you to select the sensor to be used. See Table 1.
- Measuring Range: Allows you to define the measurement range of the transmitter, showing a Lower Limit value and an Upper Limit value. When configuring the Lower Limit with a value higher than the Upper Limit, the output current operates from 20 to 4 mA. The chosen values cannot exceed the Sensor Range shown in this same field. It is not possible to set the span narrower than the Minimum Range value shown below in this same field. See Table 1.
- Line Noise Rejection: Allows you to filter the measurements made by the transmitter, eliminating interferences from the electrical network that feeds the process.
- Sensor Failure: Allows you to establish the output behavior (upscale or downscale) when the transmitter indicates a failure.
- Zero Correction: Allows you to correct small deviations presented in the transmitter output, such as when changing a sensor.
- Device Information: This field shows data that identifies the transmitter, including the model (TxIsoRail 4-20 mA or TxIsoRail 0-10 Vdc). This information should be sent to the manufacturer in an eventual request for technical assistance.
- Apply: Allows you to send a new configuration to the transmitter.
- Read Device: Allows you to read the configuration present in the connected transmitter. The screen will display the current configuration, which can be changed.
2.1.3 SIGNOW APP
When using an OTG cable and the TxConfig Configuration Interface to connect
the equipment to your smartphone and run the SigNow app (see SMARTPHONE
CONNECTIONS chapter), you must first enable the use of TxConfig.
The interface will act as an intermediary for the connection:
After that, the app will recognize TxConfig and show the main screen:
To configure the equipment, just click the Configuration button. Then, the app will show the main screen of the TxIsoRail Configuration section:
This screen shows information about the equipment, such as name, serial
number, and firmware version.
When you open the Config section, you can configure the parameters displayed
in the SIGNOW SOFTWARE section.
In the SigNow manual, available on NOVUS website, you can find more
information about the buttons and the diagnostic process.
2.2 FACTORY SETTINGS
If the specific configuration is not defined in the purchase order, the
following configuration will be adopted:
- Pt100 input, 0 to 100 °C (32 to 212 °F).
- 60 Hz filtering and upscale (20 mA) output for sensor fail.
2.3 POWER SUPPLY
During configuration, the transmitter needs to be electrically powered. The
TxConfig Interface itself provides the power supply, but this depends on the
computer used.
To ensure constant communication between the transmitter and the computer, an
external power supply must be provided.
It is also possible to configure the transmitter by keeping it connected to
the process, using energy from the very source that feeds this process (loop).
See Figure 7.
The TxConfig Interface has a complex electronic circuit. Do not use any other interface or cable connection to USB. This will damage the product and this damage is not covered under warranty.
SMARTPHONE CONNECTIONS
Smartphones with On the Go (OTG) technology can be directly connected to the
device via the Micro-USB input. Using the TxConfig Configuration Interface, it
is possible to recognize and configure a TxIsoRail by running the SigNow app.
To do this, as shown in Figure 8, you need to observe how to connect the OTG
cable to the equipment:
Incorrect positioning of the cable tip can cause the equipment not to be recognized by the app.
MECHANICAL INSTALLATION
The transmitter is designed to be installed on a 35 mm DIN rail.
ELECTRICAL CONNECTIONS
Figure below shows the transmitter connections to the sensor and power supply.
Terminals 1, 2, and 3 are used for sensor input. When using 2-wire Pt100,
terminals 2 and 3 shall be tied together.
5.1 4-20 mA MODEL
The LOAD represents the input shunt of an instrument measuring the 4-20
current loop.
5.2 0-10 VDC MODEL
The LOAD represents the input shunt of an instrument measuring the 4-20
current loop.
5.3 0-10 VDC INPUT
To use the 0-10 Vdc input type, you must perform a small intervention in the
transmitter circuitry. To do so, it is necessary to open the transmitter and
change a jumper position. See Figure 10.
- For input type 0-10 Vdc, place the jumper in positions 1 and 2.
- For all other input types, place the jumper in positions 2 and 3.
OPERATION
The transmitter leaves the factory perfectly calibrated and with standardized
sensors. It does not require any adjustment by the user.
When necessary, it is possible to make small corrections to the output signal
directly at the transmitter. To do this, simply press the ZERO key on the
front of the transmitter. To prevent accidental adjustments, this key is
located just below the front label. It can be accessed with a small 2 mm
diameter tool. For the 4-20 mA TxIsoRail model, after holding down the key for
two seconds, the output current will increase up to 0.80 mA beyond the
starting value. Then it will quickly drop to 0.80 mA below the initial value
and start a new rise. You need to monitor the output current and, when the
current reaches the desired value, release the key.
For the 0-10 Vdc TxIsoRail model, after holding down the key for two seconds,
the output voltage will increase up to 0.25 V beyond the starting value. Then
it will quickly drop to 0.25 V below the initial value and start a new rise.
You need to monitor the output voltage and, when the current reaches the
desired value, release the key.
These small corrections can also be made using SigNow or TxConfig software
(now in measured units of magnitude) or SigNow app.
Even with the equipment connected to the process and operating, the TxConfig
Interface can be connected to the transmitter. See Figure 2 or Figure 3 and
the Zero Correction fields on the SigNow or TxConfig software screens.
It is necessary to choose the input type and range that best suits the
process. The chosen measurement range must not exceed the maximum range
defined for the input type and must not be smaller than the minimum range.
It is important to note that the accuracy of the transmitter is always based
on the maximum measurement range of the input type used, even when an
intermediate measurement range has been set. Example:
- The Pt100 sensor has a maximum range of -200 to +600 °C and an overall accuracy of 0.2 %.
- Maximum error: 1.2 °C (0.2 % of 800 °C)
- This error is possible in a wide range such as the maximum (-200 to 600 °C) or in a narrower range defined as 0 to 100 °C.
Note: When checking the transmitter, make sure that the excitation current of Pt100 required by the calibrator used is compatible with the excitation current of Pt100 used in the transmitter: 0.18 mA.
WARRANTY
Warranty conditions are available on our website www.novusautomation.com/warranty.
NOVUS AUTOMATION
Documents / Resources
|
NOVUS TxIsoRail Isolated
Transmitter
[pdf] User Guide
TxIsoRail Isolated Transmitter, TxIsoRail, Isolated Transmitter, Transmitter
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>