BROAN ZB80L1 Multi Speed Ventilation Fan Installation Guide
- June 13, 2024
- Broan
Table of Contents
ZB80L1 Multi-Speed Ventilation Fan
Product Information
The ZB80L1 and ZB110L1 are multi-speed ventilation fans with dimmable light. They are designed for easy installation in both new construction and retrofit projects. The fans are suitable for general ventilating use and are not intended for exhausting hazardous or explosive materials and vapors. The product is equipped with a motor bearing that needs to be kept free from drywall spray, construction dust, and other debris to prevent damage and noise.
Warnings and Cautions
- Use the unit only as intended by the manufacturer.
- Before servicing or cleaning the unit, switch off the power and lock the service disconnecting means to prevent accidental power activation.
- Installation work and electrical wiring should be done by qualified personnel in compliance with applicable codes and standards.
- Ensure sufficient air for proper combustion and exhaust of gases through the flue of fuel-burning equipment.
- Avoid damaging electrical wiring and other hidden utilities when cutting or drilling into walls or ceilings.
- Ducted fans must always be vented to the outdoors.
- Use only ON/OFF switch, mechanical timer, or relay-switched control.
- When connected to a GFCI-protected branch circuit, the fan can be used over a tub or shower.
- The unit must be grounded.
Caution
- Do not use the product to exhaust hazardous or explosive materials and vapors.
- The product is designed for installation in ceilings up to a 12/12 pitch (45-degree angle). Do not mount it in a wall.
- Avoid getting drywall spray, construction dust, and other debris on the power unit to prevent motor bearing damage and noise.
- Refer to the product’s specification label for further information and requirements.
- The product is not suitable for use in a cooking area and should not be installed above or inside such an area.
Product Usage Instructions
Follow the steps below for the typical installation of the ZB80L1 or ZB110L1 ventilation fan:
- Place insulation around and over the fan housing.
- Install the fan housing in the desired location.
- Connect a power cable to the fan housing.
- Keep duct runs short and seal gaps around the housing.
- Install a roof cap with a built-in damper for ducting to the outside of the building.
- Alternatively, use round elbows and a wall cap with a built-in damper for ducting.
- Seal duct joints with tape.
Note : The ducting from the fan to the outside of the building significantly affects the air flow, noise, and energy use of the fan. It is recommended to use the shortest, straightest duct routing possible for optimal performance. Avoid installing the fan with smaller ducts than recommended. Insulating the ducts can reduce energy loss and inhibit mold growth. Existing ducts may not provide the rated airflow for the fan.
Ventilation Fan with Motion Sensor
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:
- Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or telephone number listed in the warranty.
- Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
- Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction codes and standards.
- Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
- When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
- Ducted fans must always be vented to the outdoors.
- Use only ON/OFF switch, mechanical timer or relay-switched control.
- Acceptable for use over a tub or shower when connected to a GFCI (Ground Fault Circuit Interrupter) – protected branch circuit.
- This unit must be grounded.
CAUTION
- For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
- 2. This product is designed for installation in ceilings up to a 12/12 pitch (45 degree angle). Duct connector must point up. DO NOT MOUNT THIS PRODUCT IN A WALL.
- To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.
- Please read specification label on product for further information and requirements.
Typical Installation
- Installation is the same for:
- Fits in 2″ x 8″ ceiling construction.
- Infinitely adjust the fan position between joists from 14″ to 24″ on center.
The ducting from this fan to the outside of the building has a strong effect on the air flow, noise and energy use of the fan. Use the shortest, straighest duct routing possible for best performance, and avoid installing the fan with smaller ducts than recommended. Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans installed with existing ducts may not achieve their rated airflow
A 6-inch round rigid metal duct is recommended for best performance.
New Construction Installation
Tools needed
- Power screwdriver with a Phillips bit
- Phillips screwdriver
- Flathead screwdriver
- Pliers
- Wire insulation stripper
- Wire cutter
Materials needed
- 6″ round metal ducting recommended for best performance. Use of other ducting is acceptable but may impact performance.
- Roof cap or wall cap (built-in damper recommended)
- Tape to seal duct connections
- Electrical wiring and supplies per local code requirements
- Remove Packaging
- Install Mounting Frame
- Snap-in and Secure Housing
- Attach Duct Connector and Ducting
- Connect Wires and Install Knockout Plate
- Run 120VAC electrical wiring to the installation location.
- Use proper UL-approved connectors to secure wiring to the Knockout Plate provided in Parts Bag.
- Connect wires as shown in wiring diagram.
- Insert Mask and Finish Ceiling
- Install ceiling material.
- Cut out around Housing. CAUTION: IN ORDER TO PREVENT MOTOR/CONTROL DAMAGE: If the blower was unplugged, power must be disconnected (see page 2, WARNING item 2) before inserting motor plugs into the control assembly.
- Install GrilleSee Page 12 for Operations, Cleaning and Maintenance, and Troubleshooting.
Retrofit Installation
Tools needed
- Power screwdriver with a Phillips bit
- Phillips screwdriver
- Flathead screwdriver
- Pliers
- Wire insulation stripper
- Wire cutter
- Ruler
- Pencil
- Drywall saw
- Claw hammer or pry bar
- Utility knife
Materials needed
- Tape to seal duct connections
- The existing rigid duct will require the addition of a short length of flexible duct
- Electrical wiring and supplies per local code requirements
-
Remove Packaging
-
Switch Off Power
WARNING : Before removing existing fan, switch the power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel. -
Enlarge Ceiling Opening and Remove Existing Fan
-
Examine WiringExamine the existing wiring to make sure it is not damaged. If any damage is found, DO NOT CONTINUE INSTALLATION of this product. Contact a qualified person(s) for repair.
-
Remove Blower Assembly
-
Remove Wiring Panel
-
Insert Mounting Frame
-
Secure Mounting Frame
-
Snap-in Housing
-
Attach Ducting and Duct Connector
-
Install Knockout Plate, Connect Wires and Reinstall Wiring Panel
- Use proper UL-approved connectors to secure wiring to the Knockout Plate provided in Parts Bag.
- Connect wires as shown in wiring diagram
-
Reinsert and Secure Blower Assembly CAUTION IN ORDER TO PREVENT MOTOR/CONTROL DAMAGE: Power must be disconnected (see page 2, WARNING item 2) before inserting motor plugs into control assembly
-
Install Grille
WARNING
Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
Operation
To Turn Fan ON
Turn the master switch ON. It is normal for this ventilation fan to take
approximately 5 seconds to start running after it is turned on.
• Fan will run at the certified airflow rate if the mode
select switch is ON.
• Fan will run at the user-adjustable airflow rate if the
mode select switch is OFF.
To Use Fan Time Delay Airflow Rate Change
-
Turn the master switch ON.
-
Turn the mode select switch ON – fan will run at the certified airflow rate.
-
When the mode select switch is turned OFF, fan will continue to run at the certified airflow rate until the user-adjustable time delay has elapsed, and then will automatically change to the user-adjustable airflow rate.
-
**To Set the User-Adjustable Airflow Rate***
Using a small, flat-blade screwdriver, carefully rotate the CFM adjustment until the arrow points to the desired airflow rate. -
**To Set the User-Adjustable Time Delay***
Using a small, flat-blade screwdriver, carefully rotate the TIME adjustment until the arrow points to the desired time delay, shown in minutes.
The user-adjustable controls are located in one corner of the Fan Housing, behind the Grille. -
To Turn Fan OFF
Turn the master switch OFF. -
To Operate Lights
The fan and light can be operated independently, using separate switches. The light may be operated with a dimmer switch. See wiring diagrams
-
Cleaning and Maintenance
CAUTION
IN ORDER TO PREVENT MOTOR/CONTROL DAMAGE:
- DO NOT remove motor plug to stop spinning motor.
- Power must be disconnected (see WARNING at top left of this page) before motor plug is removed or inserted into control assembly.
To Clean
- For quiet and efficient operation, long life and attractive appearance, remove Grille and vacuum interior of unit with a dusting brush attachment.
- The Motor is permanently lubricated and never needs oiling. If the motor bearings are making excessive or unusual noises, replace the Control Assembly and Motor.
Troubleshooting
Symptom: Fan does not run.
-
Check for an open fuse or circuit breaker in building’s service panel.
- Check two (2) plug-in connections for Motor and its Control are seated firmly in place.
-
Check that Blower Wheel spins freely.
Symptom : Motion mode does not operate fan at certified air flow rate. -
Check two (2) plug-in connections for Sensor and its Control are seated firmly in place.
Symptom: The fan runs erratically. -
Check that the Blower Wheel is firmly attached to the Motor shaft and both spin freely.
Symptom: The fan seems noisy. -
Check that the back draft damper in the fan’s Duct Connector pivots freely. Screws used to attach the duct to the Duct Connector may be preventing the damper from opening.
-
Check that the back draft damper in the wall or roof cap pivots freely. These dampers are sometimes mistakenly painted shut or obstructed by bird and insect debris.
Symptom: The fan does not properly ventilate the room. -
For spot ventilation, turn both the master switch and the mode select switch ON to enable the fan to run at the certified airflow rate.
-
For spot ventilation followed by continuous ventilation, increase the “TIME” setting of the user-adjustable time delay.
-
For continuous ventilation, increase the “CFM” setting of the user-adjustable airflow rate
Service Parts
PRODUCT DESCRIPTION
- 97018349 : Mounting Frame
- 97018721 : Knockout Plate & Screws
- 97018382 : Housing
- 97020893 : Wiring Panel/Harness Assembly
- 97020846 : Control Assembly & Motor (ZB80L1) 97020845 Control Assembly & Motor (ZB110L1)
- 97018331 : Duct Connector – 6″
- 99111513 : 6″ to 4″ Reducer (model ZB80L1 only)
- 99020301 : Blower Wheel
- 97018768 : Scroll Assembly (ZB110L1) 97019371 Scroll Assembly (ZB80L1)
- 97020827 : Grille Assembly (includes 11, 12)
- 99140208 : Grille Spring (2 req’d)
- 99111711 : Lens (2 req’d)
- 99271625 : LED Driver
Warranty
Broan Ventilation Fan/Lights Limited Warranty
WARRANTY PERIOD:
Broan warrants to the original consumer purchaser of its Broan Ventilation
Fan/Light (the “Fan”) that your Fan (excluding lamps/ bulbs) will be
materially free from defects in materials or workmanship for a period of three
(3) years from the date of original purchase. The warranty onthe lamps/bulbs
provided with the Fan is one (1) year and does not cover lamp/bulb breakage.
This warranty does not cover accessories, such as speed controls, that may be
purchased separately and installed with the Fan. The limited warranty period
for replacement parts, and for Fans repaired or replaced under this limited
warranty, shall continue for the remainder of the original warranty period.
NO OTHER WARRANTIES: THE FOREGOING WARRANTIES ARE EXCLUSIVE AND IN LIEU OF ANY OTHER WARRANTIES, EXPRESS ORIMPLIED. BROAN DISCLAIMS AND EXCLUDES ALL OTHER EXPRESS WARRANTIES, AND DISCLAIMS AND EXCLUDES ALL WARRANTIESIMPLIED BY LAW, INCLUDING WITHOUT LIMITATION THOSE OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. TO THE EXTENT THAT APPLICABLE LAW PROHIBITS THE EXCLUSION OF IMPLIED WARRANTIES, THE DURATION OF ANY APPLICABLE IMPLIED WARRANTY IS LIMITED TO THE PERIOD SPECIFIED FOR THE EXPRESS WARRANTY.
Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. Any oral or written description of the Fan is for the sole purpose of identifying it and shall not be construed as an express warranty.
REMEDY:
During the applicable limited warranty period, Broan will, at its option,
provide replacement parts for, or repair or replace, without charge, any Fan
or part thereof, to the extent Broan finds it to be covered by and in breach
of this limited warranty. Broan will ship the repaired or replaced Fan or
replacement parts to you at no charge. You are responsible for all costs for
removal, reinstallation and shipping, insurance or other freight charges
incurred in the shipment of the Fan or part to Broan. This warranty does not
cover (a) normal maintenance and service, (b) normal wear and tear, (c) any
Fans or parts which have been subject to misuse, abuse, abnormal usage,
negligence, accident, improper or insufficient maintenance, storage or repair
(other than repair by Broan), (d) damage caused by faulty installation, or
installation or use contrary to recommendations or instructions, (e) any Fan
that has been moved from its original point of installation, (f) damage caused
by environmental or natural elements, (g) damage in transit, (h) natural wear
of finish, (i) Fans in commercial or nonresidential use, or (j) damage caused
by fire, flood or other act of God. This warranty covers only Fans sold in the
United States or through U.S. distributors authorized by Broan.
EXCLUSION OF DAMAGES: BROAN’S OBLIGATION TO PROVIDE REPLACEMENT PARTS, OR REPAIR OR REPLACE, AT BROAN’S OPTION, SHALL BE YOUR SOLE AND EXCLUSIVE REMEDY UNDER THIS LIMITED WARRANTY AND BROAN’S SOLE AND EXCLUSIVE OBLIGATION. BROAN SHALL NOT BE LIABLE FOR INCIDENTAL, INDIRECT, CONSEQUENTIAL OR SPECIAL DAMAGES ARISING OUT OF OR IN CONNECTION WITH THE FAN, ITS USE OR PERFORMANCE.
Incidental damages include but are not limited to such damages as loss of time and loss of use. Consequential damages include but are not limited to the cost of repairing or replacing other property which was damaged if theFan does not work properly.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights, which vary from state to state.
This warranty supersedes all prior warranties and is not transferable from the original consumer purchaser.
BROAN SHALL NOT BE LIABLE TO YOU, OR TO ANYONE CLAIMING UNDER YOU, FOR ANY OTHER OBLIGATIONS OR LIABILITIES, INCLUDING, BUT NOT LIMITED TO, OBLIGATIONS OR LIABILITIES ARISING OUT OF BREACH OF CONTRACT OR WARRANTY, NEGLIGENCE OR OTHER TORT OR ANY THEORY OF STRICT LIABILITY, WITH RESPECT TO THE FAN OR BROAN’S ACTS OR OMISSIONS OR OTHERWISE.
This warranty covers only replacement or repair of defective Fans or parts thereof at Broan’s main facility and does not include the cost of field service travel and living expenses.
Any assistance Broan provides to or procures for you outside the terms, limitations or exclusions of this limited warranty will not constitute a waiverof such terms, limitations or exclusions, nor will such assistance extend or revive the warranty.
Broan will not reimburse you for any expenses incurred by you in repairing or replacing any defective Fan, except for those incurred with Broan’s prior written permission.
HOW TO OBTAIN WARRANTY SERVICE:
To qualify for warranty service, you must (a) notify Broan at the address or
telephone number stated below within seven (7) days of discovering the covered
defect, (b) give the model number and part identification and (c) describe the
nature of any defect in the Fan or part. At the time of requesting warranty
service, you must present evidence of the original purchase date.
Broan, 926 West State Street, Hartford, WI 53027 (1-800-637-1453) www.broan.com
If you must send the Fan or part to Broan, as instructed by Broan, you must properly pack the Fan or part—Broan is not responsible for damage in transit.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>