NEUTRIK NAC3FXXA-W Series powerCON Locking 3 Pole Power Connector Instruction Manual

June 12, 2024
NEUTRIK

NAC3FXXA-W Series powerCON Locking 3 Pole Power Connector

Product Information

The product is a locking 3 pole powerCON connector used for
electrical connections. It has two non-interchangeable types of
connectors, A type (color coding blue) for power input and B type
(color coding gray) for power output. The connectors are designed
to prevent short circuits.

The product is approved based on the IEC/EN 60320-1 standard and
has a rating of 250 V AC / 16 A. It is suitable for use with wire
sizes ranging from 1.5 to 2.5 mm2 and cable outer diameters ranging
from 6.0 to 12.0 mm (for A type) and 10.0 to 16.0 mm (for B
type).

The product can be used with various types of cables, including
IEC/EN 60320-1 cables such as H07RN-F, H05RN-F, and H05VV-F, as
well as UL 60320-1 and CAN/CSA-C22.2 No. 60320-1 cables such as
SOOW, SJOOW, SJTOOW.

Product Usage Instructions

Assembly Instruction: Locking 3 pole powerCON

  1. Place the bushing (1) and chuck (2) over the cable. Note: This
    should be done before assembling the insert.

  2. For easier assembly, use a cable lubricant.

  3. Prepare the cable as shown.

  4. Slide the cable into the contacts and clamp it with the screw
    using a Torx size T8.

Typical Wiring

The typical wiring for the powerCON connector is as follows:

  • IEC/EN 60230-1: brown – live, blue – neutral, green/yellow –
    earth/ground

  • UL60320-1 CAN/CSA-C22.2 No. 60320-1: black – live, white –
    neutral, green – earth/ground

Disassembly Instruction

To disassemble the connector:

  1. Use the Neutrik tool HTLACB.
  2. Position the tool on the surfaces of the connector and open the
    clamping sleeve.

Safety Information

Caution: To ensure protection, do not expose the connection to
bending forces or attach loads to the cable.

Safety Warning: The connector must be replaced in case of any
broken parts or excessive wear and tear for safety and
certification reasons.

For more information, visit www.neutrik.com.

R
APPLICATION & ASSEMBLY INSTRUCTION
powerCON® | Locking 3 pole Power Connector NAC3FXXA-W- & NAC3FXXB-W-

A APPLICATION & SAFETY INSTRUCTION
APPLICATION:
· The powerCON system is certified as a connector with breaking capacity according IEC / EN / UL / CSA-C22.2 No. 60320-1.
· It is intended for use as an appliance coupler and interconnection coupler. · It serves to supply power to an appliance and from an appliance to other equipment. · To be installed by qualified person only.

Connector Combination & Keyways: With the two non-interchangeable types of connectors (A type and B type) it is impossible to produce a short circuit.
Mating connectors (combination) are identified by mechanical keyways and by color.

APPLIANCE INLET

APPLIANCE OUTLET

A type (color coding blue) Power IN

B type (color coding gray) Power OUT

NAC3FXXA-W-*

Approval based:

IEC/EN 60320-1

Rating:

Wire size:

Cable O.D.:

*-S:

*-L:

250 V ac / 16 A 1.5 – 2.5 mm2 6.0 – 12.0 mm (0.24 – 0.47″) 10.0 – 16.0 mm (0.39 – 0.63″)

CABLE LIST

Cable: IEC/EN 60320-1

3 x 1.5 mm2

H07RN-F

-S

H05RN-F

-S

H05VV-F

-S

Cable: UL 60320-1, CAN/CSA-C22.2 No. 60320-1

SOOW SJOOW SJTOOW

3 x 2.5 mm2
– L -S

BDA 639

NAC3FXXB-W-*
UL 60320-1 CAN/CSA-C22.2 No. 60320-1
127 V ac / 20 A 16 – 12 AWG 6.0 – 12.0 mm (0.24 – 0.47″) 10.0 – 16.0 mm (0.39 – 0.63″)

16/3 AWG
-S -S -S

14/3 AWG
-L -S -S

12/3 AWG
-L -L
ð -S
Page 1

ASSEMBLY INSTRUCTION I Locking 3 pole powerCON

B ASSEMBLY INFORMATION

A

  1. B IEC/EN 60320-1
    Cable O.D.: S: 6.0 – 12.0 mm (0.24 – 0.47″) L: 10.0 – 16.0 mm (0.39 – 0.63″)

24 mm
[0.94″]

9 mm
[0.35″]

Place the bushing (1) and chuck (2) over the cable.
Important: Chuck and Bushing cannot be placed over the cable after the assembly of the insert.
(3) For easier assembly please use a cable lubricant.

Prepare cable as shown.
UL60320-1 CAN/CSA-C22.2 No. 60320-1
Cable O.D.: S: 6.0 – 12.0 mm (0.24 – 0.47″) L: 10.0 – 16.0 mm (0.39 – 0.63″)

24 mm
[0.94″]

9 mm
[0.35″]

C IEC/EN 60230-1

N

L

UL60320-1 CAN/CSA-C22.2 No. 60320-1

N

L

PE 27 mm [1.06″] Torx size T8 Torque Value 0.7 Nm (6.2 inch pound / 0.52 lb.ft)

PE 27 mm [1.06″]

Slide the cable into the contacts and clamp with the screw with Torx size T8.

Typical Wiring
L Þ N Þ
Þ

IEC/EN 60230-1
brown blue green / yellow

UL60320-1 CAN/CSA-C22.2
No. 60320-1
black
white
green

D

Important:

Push and turn

simultaneously.

4

BDA 639

3 2.

Position chuck (1) on insert (2).

Slide insert (2) with chuck (1) together into housing (3).
Important: Align the chuck by positioning the nose into keyway.

Slide bushing (4) over chuck (1).

ð
Page 2

ASSEMBLY INSTRUCTION I Locking 3 pole powerCON

E

27 mm 1 1/8 inch

Hex bit

Neutrik HTLACA 5

7 Torque Value 2.5 Nm (22 inch pound / 1.8 lb-ft)

4 6

Neutrik HTLACB

Hold the connector with the NEUTRIK tool (5) and tighten bushing with the NEUTRIK tool (6) as shown.
For an exact mounting position use a torque wrench with 27 mm (1 1/8 inch) hex bit (7) and tighten it with 2.5 Nm (22 inch pound / 1.8 lb-ft).
NEUTRIK tool Information:
(5) HTLACA
(6) HTLACB

C DISASSEMBLY INFORMATION
FOR DISASSEMBLY!
1. Use the Neutrik tool HTLACB. 2. Position the tool on the surfaces and open the
clamping sleeve.

HTLACB

BDA 639

ð
Page 3

ASSEMBLY INSTRUCTION I Locking 3 pole powerCON
D SAFETY INFORMATION CAUTION To ensure protection category, do not expose the connection to bending forces (e.g. do not attach loads to the cable, no freedangling cable windings etc.).
SAFETY WARNING For safety and certification reasons the connector must be replaced in case of any broken parts or excessive wear and tear.
E More Information on the www.neutrik.com
https://www.neutrik.com/products/audio/powercon

LIECHTENSTEIN
FORCE

Neutrik AG Neutrik USA Inc. Neutrik (UK) Ltd. Neutrik Vertriebs GmbH

LI USA UK DE / NL / AT/DK

T: +423 / 237 24 24 T: +1 704 / 972 3050 T: +44 1983 / 811 441 T: +49 8131 / 280 890

F: +423 / 232 53 93 F: +1 704 / 438 9202 F: +44 1983 / 811 439 F: +49 8131 / 280 830

Neutrik France

FR

Neutrik Tokyo Ltd.

JP

Neutrik Hong Kong Ltd. HK

T: +33 1 / 4131 6750 T: +81 3 / 3663 4733 T: +852 / 2687 6055

F: +33 1 / 4131 0511 F: +81 3 / 3663 4796 F: +852 / 2687 6052

I I Draft. Nr.: BDA 639 V1 Update: 2022-11-16 Data subject to change without prior notice. © 2022 NEUTRIK®. NEUTRIK® are registered trademark of Neutrik AG. ALL RIGHTS RESERVED.

R

www.neutrik.com

Page 4

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals