Test Remote for LED fixtures with integrated EBB
Operation Instructions
Part # TR01
Instructions for Remote Control
Please note: Remote must be pointed at red indicator light and be within
a 45 degree angle to receive a signal/command. Remote needs two AAA batteries
to operate (not included).
Testing: To test emergency functionality, press the TEST/+ button. The
light will switch to its emergency state for 3 seconds and the indicator light
will flash red. After 3 seconds, the fixture will return to normal operation.
Demonstration: To demonstrate the emergency functionality, start with the
fixture powered on and in normal operation. Press the DEMO button, then press
the On/OFF button. The fixture will switch to it’s emergency state. Repeat
this operation and the fixture will return to normal operation.
For use with LED Light Panel (PTEM Series)
The red indicator light on the LED Light Panel is located behind the lens and
will only be visible when in emergency or test mode. For use with LED Emergency Light (HBEM
Series)
Automatic Self-testing
The fixture includes an automatic monthly self-testing function, which
operates at 30-day intervals for 5 minutes and 360-day intervals for 90
minutes. During testing, the red indicator light will remain on.
Using Optional Test Remote #TR01
Using the optional handheld Test Remote TR01, (sold separately), fixture may
be manually tested as desired.
Please note: There is no test remote functionality within the first five
minutes after normal power is restored. Decrease output power for increased emergency
light time
By default, the HBEM uses 30W and delivers 90 minutes of light in times of
power loss. However, this can be adjusted to output 70% of full power (21W)
for a total of 120 minutes.
To adjust output, using the optional TR01 test remote, press and hold the
ON/OFF button for 5 seconds. The green indicator light will flash and the
change will be saved. Repeat this operation and the fixture will revert back
to 100% load (30W) for 90 minutes. at 90 minutes. This information is subject to change without