MEAN WELL DBR-3200 Rack Mountable Front End Battery Charger Instruction Manual
- June 12, 2024
- MEAN WELL
Table of Contents
3200W Rack Mountable Front End Battery Charger
DBR-3200 serieshttps://www.meanwell.com/webapp/product/search.aspx?prod=DBR-3200&pdf=RFJQLTMyMDAsREJSLTMyMDAsREhQLTFVLUUucGRm&a=4
DBR-3200 Rack Mountable Front End Battery Charger
Applications
- Large scale DC UPS or emergency backup system
- Marine battery charger module
- Electric scooter or vehicle charger station
- Wastewater treatment system
- Electrolysis system
Features
- Charger for lead-acid batteries (Gel, flooded and AGM) and Li-ion batteries (lithium iron and lithium manganese)
- Built-in default 3 stage charging curves and programmable curve
- Built-in I°C interface, PMBus protocol (Optional CANBus protocol)
- Output voltage and current programmable
- Universal AC input / Full range
- Built-in active PFC function
- Forced air cooling by built-in thermal controlled DC fans
- Built-in OR-ing FET, support hot swap (hot plug)
- Active current sharing up to 12800W for one 19” rack shelf
- Protections: Battery under voltage / Battery no connection / Short circuit / Over voltage / Over temperature
- Optional conformal coating
- 5years warranty
Description
DBR-3200 is a 3200W single output AC/DC front-end charger in 1U low profile
with high power density, 37W/inch’. It is an intelligent charger that has pre-
loaded programmable charging curves for different types of lead-acid and li-
ion batteries. Output programmable function allows user to adjust the
charging voltage and current via the built-in potentiometer or PMBus protocol.
Various protection mechanisms as well as the temperature compensation function
are provided to assure normal and safe system operation.
The rack-mountable attribute fits DBR-3200 perfectly for the charging, backup
or constant current source applications exploiting the rack architecture or
central power management.
Model Encoding / Order Information
Type | Communication Protocol | Note |
---|---|---|
Blank | PMBus protocol | In Stock |
CAN | CANBus protocol | By request |
SPECIFICATION
MODEL | DBR-3200-24 | DBR-3200-48 |
---|---|---|
OUTPUT | BOOST OUR & YCITAGE(VbcoeXelidl) | 28.8V |
FLOATORRGE VOLIkfiE(VIegi(defaill) | 27.6V | 55.2V |
CCEISTANTCURREIMCC)(default) | 110A | 55A |
VOLTAGE ADJ. RANGE | By buit-in potentiometer, SVR | |
23.5 – 30V | 47.5 -58.8V | |
RECOMMENDED BATTERY CAPACITY(AMP HOURS) Note.3 | 330 – 1000Ah | 180 – |
550Ah
LEAKAGE CURRENT FROM BATTERY (Tye.)| <1.5mA
INPUT| VOLTAGE RANGE NoteA| 90 – 264VAC 127 – 370VDC
FREQUENCY RANGE| 47 – 63Hz
POWER FACTOR (Typ.)| 0.97/230VAC at ful load
EFFICIENCY (Typ.)| 94.%| 195.%
AC CURRENT (Typ.) NoteA| 17A/230VAC
INRUSH CURRENT (Typ.)| COLD START 55A/230VAC
LEAKAGE CURRENT| <1.5mA/ 230VAC
PROTECTION| OVER VOLTAGE| 31.5 – 37.5V| 163 -75V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down o/p voltage, recovers automatically after
temperature goes down
FUNCTION| OUTPUTVOLTAGEPROGRAIIIIABLEIPY)| Adjustment of output
voltage is allowable to 75 – 125% of nominal output voltage. Please refer to
the Function Manual.
OU1PUTCURRENT PROGRAMMABLE”,| Adjustment of output voltage is allowable
to 20 – 100% of rated current. Please refer to the Function Manual.
AUXILIARY POWER| 5V © 0.3A, tolerance ±10%, ripple 150mVp-p, 12V @ 0.8A,
tolerance ±10%, ripple 450mVp-p
REMOTE ON-OFF CONTROL| By electrical signal or thy contact Power
ON:short Power OFF:open. Please refer to the Function Manual
TEMPERATURE COMPENSATION| -3mV / ‘(.: / cell /(12V = 6 cells ; 24V = 12
cells ; 48V = 24 cells)
DC OK SIGNAL| The isolated TTL signal out. Please refer to the
Installation Manual
AC OK SIGNAL| The isolated TTL signal out. Please refer to the
Installation Manual
ENVIRONMENT| WORKING TEMP.| -30 -+70°C (Refer to terating Curve’)
WORKING HUMIDITY| 20 – 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 – +85°C , 10 – 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03VC (0 – 50t )
VIBRATION| 10 – 500I-t, 2G 10min./1cyde, 60min. each along X, Y, Z axes
SAFETY & EMC
(Note 5)| SAFETY STANDARDS| UL62368-1, CSA C22.2 No. 62368-1, TUV
BS EN/EN62368-1, EAC TP TC 004 approved
WITHSTAND VOLTAGE| UP-0/P:3KVAC I/P-FG:2KVAC 0/P-FG:1.5KVAC
ISOLATION RESISTANCE| I/P-0/P, I/P-FG, 0/P-FG:100M Ohms / 500VDC / 25 t/
70% RH
EMC EMISSION| Parameter| Standard| Test Level! Note
Conducted| BS EN/EN55032 (CISPR32)| Class B
Radiated| BS EN/EN55032 (CISPR32)| Class A
Harmonic Current| BS EN/EN61000-3-2| —
Voltage Flicker| BS EN/EN61000-3-3| —
EMC IMMUNITY| BS EIWEN55024, BS EN/EN61000-6-2
Parameter| Standard| Test Level /Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 2, 4KV contact
Radiated| BS EN/EN61000-4-3| Level 3
EFT/ Burst| BS EN/EN61000-4-4| Level 3
Surge| BS EN/EN61000-6-2| 2KV/Line-line 4KV/Line-Earth
Conducted| BS EN/EN61000-4-6| Level 3
Magnetic Field| BS EN/EN61000-4-8| Level 4
Voltage Dips and Interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30%
dip 25 periods, >95% interruptions 250 periods
OTHERS| MTBF| 160.1K hrs min. Telcordia SR-332 (Belcore); 38.9K hrs
min. MIL-HDBK-217F (25°C)
DIMENSION| 325’107’41mm (L’WH)
PACKING| 2.65144pcs/11.6Kg/0.93CUFT
NOTE| 1. Modification for charger specificaion may be required for
different battery specificaion. Please contact battery vendor and MEAN WELL
for details.
2. All parameters NOT specially mentioned are measured at 230VAC input, rated
load and 25°C of ambient temperature.
3. This is MEAN WELL’s suggested range. Please consult your battery
manufacturer for their suggestions aboLt maximum charging current limitation.
4. Derating may be needed under low input voltages. Please check the derating
curve for more detais.
5. The charger is considered a component which will be installed into a final
equipment. Al the EMC tests are been exected by mourting the unit on a
00mm”900mm metal plate with 1mm of thickness. The final equipment must be re-
confirmed that it il meets EMC directives. For guidance on how to perform
these EMC tests, pi
6. The ambient temperature derating of 3.5’C/1000m with fanless models and of
5’C/1000m with fan models for operating attitude higher than 2000m(6500f).
Product Liabiliy Disciaimer lease refer 10 “EMI testing of component power
supplies.” (as available on http://www.meanwell.com) For detailed
information, please refer to hitps:/www.meanwell.comiserviceDisclaimer.aspx
BLOCK DIAGRAM
DERATING CURVE
STATIC CHARACTERISTICS
FUNCTION MANUAL
-
PMBus Communication Interface
DBR-3200 supports PMBus Rev. 1.1 with maximum 100KHz bus speed, allowing information reading, status monitoring, output trimming, etc. For detals, please refer to the Installation Manual. -
Charging Curve
By factory default, this charger performs the default curve which can be programmed via PMBus.
To disable / enable the charging curve, change to a2 stage curve, a different curve frequently used for certain types of batteries in the industry, and soon, please refer to the Installation Manual.
Toprogram the parameters of the charging curve, SBP-001, the smart battery charging programmer designed by MEAN WELL, and a personal
computer are needed. Please contact MEAN WELL for details.
Default3 stage charging curve
3Stage
Sutable for lead-acid batteries (flooded, Gel and AGM) and Li-ion batteries (ithiumiron and lthium manganese)
Embedded 3 stage charging curves
MODEL | Description | Vboost | \Moat | CC(default) |
---|---|---|---|---|
24V | Default, programmable | 29. | 28. | 110A |
Pre-defined, gel battery | 28 | 27. | ||
Pre-defined, flooded battery | 28. | 27. | ||
Pre-defined, AGM battery | 29 | 27 | ||
48V | Default, programmable | 58. | 55. | 55A |
Pre-defined, gel battery | 56 | 54. | ||
Pre-defined, flooded battery | 57. | 54. | ||
Pre-defined, AGM battery | 58 | 54 |
Note :
When using this charger unit, please configured the system with recommended
battery capacity defined by specification. Should battery capacily in use be
much smaller sothat user needs to seta low current for charging, under such
condition it might cause higher current ripple
-
- Remote ON-OFF Control
The charger can be turned ON/OFF individually or along with other units in parallel by using the “Remote ON-OFF” function.
Between Remole ON-OFF and +5V-AUX| Charger Status
---|---
Switch Short| oN
Suitch Open| OFF
- Remote ON-OFF Control
-
Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim)
In addtion to the adjustment via the built-in potentiometer, the output voltage can be trimmed to 75~125% of the nominal voltage by applying EXTERNAL VOLTAGE.
-
Output Current Programming (or, PC / remote current programming / dynamic current trim)
The output current can be trimmed to 20~100% ofthe rated current by applying EXTERNAL VOLTAGE.
- Temperature Compensation
To exploit the temperature compensation function, please attach the temperature sensor, NTC, to the battery or the battery’s vicinty.
The charger s able to work normally withoutthe NTC.
MECHANICAL SPECIFICATION
LED Status Indicators
LED | Description |
---|---|
Green | Float (stage 3) |
Orange | Charging (stage 1 or stage 2) |
Red | The LED will present a constant red light when the abnormal status (OTP, |
OLP, fan fail and charging timeout) arises.
Red (Flashing)| The LED will flash with the red light when the internal
temperature reaches 60°C; under this condition, the unit still operates
normally without entering OTP. (In the meantime, an alarm signal will be sent
out through the PMBus interface.)
※ Input / Output Connector Pin No. Assignment(CN1) : Positronic PCIM34W13M400A1
Mating Housing | Mating Housing |
---|---|
Pin No. | Function |
--- | --- |
1,2,3,4,6 | -V |
5,7,8,9,10 | +V |
11 | +12V-AUX |
12).
The maximum load current is 0.8A. This output has the built-in “Oring diodes”
and is not controlled by the Remote ON/OFF control.
12| GND-AUX| Auxiliary voltage output GND.
The signal return is isolated from the output terminals (+V & -V).
13| +5V-AUX| Auxiliary voltage output, 4.5-5.5V, referenced to GND-AUX (pin
12).
The maximum load current is 0.3A. This output has the built-in “Oring diodes’
and is not controlled by the Remote ON/OFF control.
14| SCL| For PMBus model: Serial Clock used in the PMBus interface. (Note.2)
CANL| For CANBus model: Data line used in CANBus interface. (Note.2)
15| SDA| For PMBus model: Serial Data used in the PMBus interface. (Note.2)
CANH| For CANBus model: Data line used in CANBus interface. (Note.2)
16| T-ALARM| High (4.5 – 5.5V) : When the internal temperature exceeds the
limit of temperature alarm, or when fan fails. Low (-0.1 – 0.5V) : When the
internal temperature is normal, and when fan works normally .
The maximum sourcing current is 10mAand only for output(Note.2)
17| Remote
ON-OFF| The unit can turn the output ON/OFF by electrical signal or dry
contact between Remote ON/OFF and +5V-AUX. (Note.2) Short (4.5 – 5.5V) : Power
ON ; Open (-0.1 – 0.5V) : Power OFF ; The maximum input voltage is 5.5V.
18| | High (4.5 – 5.5V) : When the Vout 16V/32V ± 1V.
Low (-0.1 – 0.5V) : When Vout a 16V/32V ± 1V. The maximum sourcing current is
10mA and only for output. (Note.2) DC OK is associated with battery low
protection.
DC-OK
19| AC-OK| High (4.5 – 5.5V) : When the input voltage is 87Vrms .
Low (-0.1 – 0.5V) : When the input voltage is -75Vrms.
The maximum sourcing current is 10mAand only for output. (Note.2)
20| DO| Interface lines for charging curve selection. (Note.1)
21,22,23| A2,A1,A0| PMBus interface address lines. (Note.1)
24,25| DB,DA| Differential digital signal for parallel control. (Note.1)
26| PC| Connection for output current programming. (Note.1)
27| PV| Connection for output voltage programming. (Note.1)
28| +V(signal)| Positive output voltage signal.
It cannot be connected directly to the load.
29| -V(signal)| Negative output voltage signal.
It is for certain function reference; it cannot be connected directly to the
load.
30| RTH+| Temperature sense associated with the temperature compensation
function.
31| RTH-
32| FG| AC Ground connection.
33| AC/L| AC Line connection.
34| AC/N| AC Neutral connection.
Note1: Non-isolated signal, referenced to [-V(signal)].
Note2: Isolated signal, referenced to GND-AUX.
Downloaded from Arrow.com.