MI-HEAT 17/5 Black Gold Heating Mat User Manual
- June 12, 2024
- MI-HEAT
Table of Contents
17/5 Black Gold Heating Mat
User Manual
GENERAL INFORMATION TO INSTALLATION
- Never electrically connect or turn the heating mats on while coiled.
- Only the heating mat cold lead wires are allowed to be lengthened or shortened during the installation.
- Never electrically connect or shorten the heating wires.
- Always install the electrical underfloor heating mat strictly using an all pole disconnection (e.g. relay, power contacted) with a contact opening of minimum 3 mm.
- Multiple heating mats must be connected parallel in a recessed electrical box.
- Always connect the braided shield or screen to the PE ground conductor.
- Always install the thermostat outside of the protected zone 2, according to VDE 0100.
- Always connect the electrical underfloor heating mat, by means of an electrical box, firmly to the power supply 230 VAC (3×1,5mm²). Electrical installation is only allowed according to DIN-VDE or local regulations and installation by a qualified electrician.
- Never exceed the total amperage of the thermostat (refer to thermostat specifications) by parallel connected heating mats.
- Never cross or fold the heating wires.
- Never bend the heating cables less than 30 mm radius at the turnings.
- Always operate the electrical underfloor heating mat with a ground fault circuit breaker (30mA).
- Never impact the termination joints more than 120 N.
- The connation’s cannot be folded or damaged.
- Never install the heating cable over a building expansion joint.
- The minimum installation temperature is +5°C.
- Never install the mats through or behind insulation material, under cabinets, under fixed objects or in small closets. Excessive heat will build up in these small spaces and the fasteners (nails, screws, etc.) used to install the fixed objects could damage the mat.
- The minimum distance of the heating mat to the wall or to ascending components (e.g. bathtubs, shower trays) must be 5 cm. The distance to conductive building parts (e.g. hot water pipes) must be at least 3 cm. In order to remain flexible in the positioning of the furniture, or in cases where the final position of the furniture is not yet known (especially in rental apartments and houses), a distance of 60 cm to the partition wall should be kept free.
- Always record the mat resistance readings before and after the installation.
- Always make sure all electrical work is executed by qualified persons in accordance with the local building regulations, electrical codes and the latest VDE regulations (for example VDE 0700 Part 753, VDE 0700 Part 701 and DIN VDE 1264-3).
- Always verify that the existing floor thermal insulation complies with the latest technical standards and regulations. Therefore, a high energy consumption is excluded.
- It is not allowed to change the surface area of the subfloor, on which the heating mat is installed. Underlaying materials other than mortar or screed are not allowed to be used.
- Never install the electrical heating mat in walls or ceilings.
- We guarantee that our products are free from defects in materials and workmanship. Products that have been mechanically damaged due to incorrect connection or due to disregard of the terms of operating rules and servicing, are not subject to warranty repairs, replacement or return.
- The subfloor should be even, secure, solid and with an appropriate load capacity. The surface has to be dry, clean, free of grease, dust and sharp objects.
- If the subfloor is uneven, it is necessary to level it, using a self-leveling floor compound before installation of the heating section in order to avoid air cavities underneath the heating section.
- Completely cover the termination sleeves with mortar, screed or tile glue.
- Never put the underfloor heating system into operation before the tile adhesive, mortar or screed is fully dry.
- Always use materials for the installation which are certified by the manufacturer for underfloor heating systems.
- Always install the cold lead cable of the heating mat inside a seperate corrugated tube (DIN EN 61386-1).
- Always install the floor temperature sensor cable inside a separate corrugated tube (DIN EN 61386-1).
- The heating mat should not be exposed to temperatures above 80°C.
INSTALLATION PLAN
Draw the layout of the electrical underfloor heating mat and write down the
zones free of the heating mat and spacings at the surrounding walls. The
distance of the electrical heating mat and any conductive parts of the
building have to be at a minimum of 30 mm. (for example, water pipe).
INSTALLATION
SUBFLOOR PREPARATION
The subfloor should be even, secure, solid and with an appropriate load
capacity. The surface has to be dry, clean, free of grease, dust and sharp
objects. If the subfloor is uneven, it is necessary to level it, using a self
leveling floor compound before installation of the heating mat, in order to
avoid air cavities underneath the heating mat. Never install the heating cable
over a building expansion joint.
THERMOSTAT INSTALLATION PREPARATION
Chisel out channels for the power supply wires, cold leads and temperature
sensor in the wall and floor (Attention! Cold leads and sensor cable have to
be installed into two separate corrugation tubes!). A standard plastic round
recessed electrical box with 230 VAC power supply is preferred for
installation at the chosen thermostat location. A ground fault circuit breaker
(30 mA) should be used for the 230 VAC heating mat circuit.
MAT ADJUSTMENT
Fix the heating mat with the fibre mesh side down to the subfloor according to
your layout. Adjust the mat to the heating area layout by cutting and turning
the fibre mesh (Attention! Do not cut or damage the heating cable!). After
positioning the heating mat into the intended form, press the heating mat
firmly to the subfloor. The fibre mesh has to be laid without any folds. The
heating mat should be fixed using 4 to 6 dowels per m² to prevent the heating
mat from swimming when using leveling screed.
KEEPING THE SAFETY DISTANCE
Keep a safety distance of around 4-6 cm (it is not permitted to install
under the minimum distance of 3 cm.) between the turnings of the mat. Wear
soft elastic sole shoes and cover the mat surface with plywood boards or other
material in order to prevent damage of the heating mat cables during
installation. Take caution not to drop sharp objects or stepping on the
heating cables in order to avoid damage to the heating mat.
INSTALLATION WITH DIFFERENT FLOOR FINISHINGS
PVC and carpet floor finishings: The electrical underfloor heating has to
be covered with around 5-10 mm leveling material. Insulation values and
thicknesses of floor finishing should not exceed those stated under THERMOSTAT
INSTALLATION AND FLOOR CONSTRUCTION.
If the subfloor is uneven, it is necessary to level it using a self-leveling
floor compound, before installation of the heating mat in order to avoid air
pockets underneath the heating mat. Never install the heating cable over a
building expansion joint.
FLOOR TEMPERATURE SENSOR INSTALLATION
Sensor installation
The floor temperature sensor cable has to be placed into a separate corrugated
tube according to EN 61386-1.
The sensor should be placed centrally between the heating conductor. Route the
heating mat cold lead through the second corrugated tube. Do not cross the
cold lead over or place it closer than about 2 cm to the mat heating wires! A
standard plastic round recessed electrical box with 230 VAC power supply is
preferred for installation at the chosen thermostat location. A ground fault
circuit breaker (30 mA) should be used for the 230 VAC heating mat circuit.
Ensure that the sensor can be placed into and removed from the corrugated tube
(Ø16mm); once during installation of the tubing and again before installation
of the floor finish!
TILE ADHESIVE OR SCREED LAYING
Be careful not to damage the heating conductor insulation with the tile trowel
during the laying of the tile adhesive or screed. The heating wire has to be
completely covered over the full extent of the heating mat. If necessary after
the laying of the tile adhesive or screed, the heating mat may be adjusted by
slightly lifting and then pressing it firmly back into the laying material
again.
For different coverings, e.g. PVC or carpet, the electrical underfloor heating
section has to be completely covered with a self-leveling floor compound about
5-10 mm. The heat transition coefficient (conductance) of the leveling
material is not permitted to exceed Rλ= 0,15 m² K/W and the leveling material
exposure temperature resistance has to be minimum 50°C. The appropriate
conductance of the floor finishing is found under THERMOSTAT INSTALLATION AND
FLOOR CONSTRUCTION in Fig. 4.
After the laying of the floor finish, measure and record the heating section
and insulation resistance. Please retain the resistance readings record.
Once the tile adhesive is cured, grout the tiles with appropriate material.
Tile expansion joints shall be provided at all adjoining building units and
built-ins. These expansion joints are to be grouted by means of silicone. The
product identification label (located at the cold lead) has to be placed at
the electrical box.
THERMOSTAT INSTALLATION AND FLOOR CONSTRUCTION
-
Electrical thermostat; Power supply distribution cable NYM 3 x 1,5 mm²
-
Corrugated tube for the temperature sensor or the cold lead (both are not to be installed inside the same tube)
-
Recessed electrical box
(only necessary for more than one heating mat) -
Floor Finish
Floor Finish| | R λ
---|---|---
Tile| ≤ 13 mm| 0.012 m2K/W (0.12 TOG)
Carpet| ≤ 10 mm| 0.09 m2K/W (0.90 TOG)
PVC| ≤ 2 mm| 0.01 m2K/W (0.10 TOG)
Cork| ≤ 11 mm| 0.13 m2K/W (1.30 TOG)
Parquet| ≤ 22 mm| 0.11 m2K/W (1.10 TOG)
APPLICATION EXAMPLES
SAFETY WARNINGS
Only qualified electricians are allowed to work on electrical connections and
the electric supply of the device according to national laws and regulations.
Otherwise, the warranty invalidates. Switch off power from all wiring before
installing, testing or replacing the thermostat. Only use plastic electrical
wall mounting boxes for the thermostat installation. Ensure that the sensor
can be placed into and removed from the corrugated tube (Ø 16mm); once during
installation of the tubing and again before installation of the floor finish.
CLAIMS
In case of failure during the warranty period, please contact the seller.
WARRANTY
The manufacturer guarantees the conformity of the heating mat with the design
description, assuming compliance with the assembly and operating instructions.
Warranty period – 2 years from date of purchase.
In case of a failure during guarantee period caused by a manufacturing defect,
the customer has the right to supplementary performance. The warranty does not
cover any damages due to inadequate handling, damages through a third party,
wrong installation (not following the manual) or its consequential damages.
Please keep your receipt.
For any warranty claims you have to show your sales receipt.
| Follow the installation manual instructions
---|---
| Protect against damage
| Minimum installation temperature
| Power supply
GUARANTEE CARD
The filled out resistance acceptance test certificate is necessary for
warranty claims.
Name|
---|---
Street|
Postal Code, City|
Country|
Tel|
Purchase date|
Installation date|
e-mail|
Installer|
Signature|
Heating mat type:|
First measurement: Before and after installation of the heating mat.
The sensor can be removed through the corrugated tube (Ø 16mm) during
installation of the heating mat.
Total resistance in | Isolation resistance in MW ( >20 MΩ) |
---|---|
before installation | after installation |
installation
| | |
Second measurement: Before and after installation of the flooring.
The sensor can be removed through the corrugated tube (Ø 16mm) before
installation of the flooring .
Total resistance in | Isolation resistance in MW ( >20 MΩ) |
---|---|
before installation | after installation |
installation
| | |
NOTES
The double core heating mats WCM consist of a screened two wire heating
cable that is fixed to a flexible self-adhesive carrier mat. The heating mat
is provided with one cold lead, including reliable termination sleeve, and one
reliable end termination sleeve.
WCM
- Glass fibre mat
- Heating circuit
- Termination sleeves
- Cold lead
- End termination sleeve
All information given are believed to be reliable and correct according to the best of our knowledge. Modifications, mistakes and printing errors do not justify claims for compensation. The manufacturer‘s and supplier‘s only obligations for this product are those in the general business terms of delivery. Specifications are subject to change without prior notice.
Mi-Heat Heizsysteme GmbH
Ol Streek 39a
D-26607 Aurich, Germany
Tel.: +49 (0)4941-6971930
Email: info@infrarot-fussboden.de
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>