FLEXIT SP445 Smoke Detector for Duct Mounting Instruction Manual
- June 12, 2024
- FLEXIT
Table of Contents
SP445
110933-10
2023-03
Installation instructions
Smoke detector for duct mounting
All electrical connections must be carried out by qualified electricians.
Product description
Unigard Super flow is designed to detect smoke gas in ventilation ducts. It
consists of a smoke detector as well as an adapting system designed for
optimal air flow through the detector.
The system meets all fire safety requirements at air flow speeds between 0,2
m/s and 20 m/s.
SP445 contains an intelligent controlling circuit. This circuit is adjusting
the sensitivity to give an optimal function during the whole life time of the
detector.
Detector cleaning by cloth or vacuum cleaner is recommended on an annual
basis.
The detector is fastened with a bayonet connector, making mounting and
unmounting easy.
Installation
The aluminium pipe can easily be cut for adaption to the diameter of the ventilation duct. The hole in the duct should have a diameter of 38mm. If the ducts are circular or covered with isolation, use the enclosed mounting bracket and grommet. The hole should then have a diameter of 51 mm. In case of an outdoor or low-temperature loft installation, the detector must be protected with an isolated cover type UG3-Cover.
Technical data
Operating voltage | 230V AC +/-20% |
---|---|
Connection smoke alarm | Relay, 2 potential free, alternating 250V, 5A |
Connection service alarm | Relay, 1 potential free, NC |
Ambient temperature | -20 to + 50°C |
Max air humidity | 99% RH |
Protection class | IP 54 |
Dimensions (L x W x H) | See drawing |
Max drawing | 18 mA |
Connection
Principal drawing, connection to air handling unit
3.1. Connection Pro Nordic and Albatros
CS2500 and CS2000 Connect the detector according to the connection table and
wiring diagram for the detector
Connection table
Detector | Unit |
---|---|
1L | 1 |
2N | 2 |
4C | 27 |
5NC | 28 CS2000 |
32 CS2500
Connection of external fire/smoke detector:
Block | Function |
---|---|
27 | Fire/smoke [DI] |
28 | Fire/smoke – GO |
32 | Fire/smoke – 24V AC |
The function must be activated in the control unit.
This is done via the following menu option:
Login password: 2000
Main index > Configuration > Configuration 1 > Fire alarm
Then select ‘Alarm’
It is possible to connect various types of switch/sensor that have pulse or fixed positions. The contact function can also be changed. By default the control unitis set for switches with fixed values. This can be changed via the menu option:
Main index > Unit > Inputs > Alarms
Then select the desired input and adjust it as required
Main curcuit CS2000 and (52500
3.2. Connection units 300-700 m³
To connect this accessory art.no 116405 “Cord set accessories” is needed
Start with manual for 116405, and complete the installation with this manual
(110933)
**Terminal*** | Smoke detector |
---|---|
GO | 5NC |
X8 | 4C |
L(230V) | 1L |
N(230V) | 2N |
*See wiring diagram
The supply voltage (230 VAC) can also be connected at the installation spot.
Configuration of air handling units for SP445 Smoke detektor
Prerequisite: Your mobile unit has to be connected to the same network as the
air handling unit.
CS500
Remove the J4-3/J4-6 jumper before connecting.
Connect the detector according to the connection table and connection diagram
that comes with the ventilation unit.
Connection table
Detector | Centralunit |
---|---|
No 5NC | J4(PIN3) |
No4 C | J4(PIN6) |
1L | J1-9 |
2N | J1-10 |
CS60
Remove the P6-5/P6-6 Jumper before connecting.
Connect the detector according to the connection table and connection diagram
that comes with the ventilation unit.
Connection table
Detector | Centralunit |
---|---|
No 5NC | P6-5 |
No 4 C | P6-6 |
1 L | P1-9 |
2 N | P1-10 |
3.3. Connection other units
Connect the detector according to the connection table and connection diagram that comes with the ventilation unit.
Function test
When the installation is completed, a test should be performed to make sure that everything works according to spec. The test can be performed with test spray DI 7003
Normal operation:
On the circuit board, the green LED should light up. All relays are active
connected between C and NC. The service alarm relay is connected between 9 and
10.
|
Smoke alarm:
The red LEDs on both the circuit board and the detector should light up. The
smoke alarm relay is connected between C and NO.
| Reset:
Press the reset button to reset the detector.|
Service alarm:
The green LED on the detector and the yellow LED on the circuit board should
light up. The service alaram relay disconnects between switch 9 and 10.
|
Error:
In case of an error, the green LED on the circuit board is not lit, and no
relays are active. This might occur in case of a power dirsuption, removed
detector etc
---|---|---|---|---