GOODWE GW3000-ES-20 Solar Inverter Instruction Manual

June 12, 2024
GOODWE

GOODWE GW3000-ES-20 Solar Inverter

GOODWE GW3000-ES-20 Solar Inverter

Safety Precautions

General Disclaimer

  • The information in this quick installation guide is subject to change due to product updates or other reasons. This guide cannot replace the product labels or the safety precautions in the user manual unless otherwise specified. All descriptions here are for guidance only.
  • Before installations, read through the quick installation guide. For additional information, please see the user manual.
  • All operations should be performed by trained and knowledgeable technicians who are familiar with local standards and safety regulations.
  • Check the deliverables for correct model, complete contents, and intact appearance. Contact the manufacturer if any damage is found or any component is missing.
  • Use insulating tools and wear personal protective equipment when operating the equipment to ensure personal safety. Wear anti-static gloves, clothes, and wrist strip when touching electronic components to protect the inverter from damage. The manufacturer shall not be liable for any damage caused by static electricity.
  • Strictly follow the installation, operation, and configuration instructions in this guide and user manual. The manufacturer shall not be liable for equipment damage or personal injury if you do not follow the instructions. For more warranty details, please visit https://en.goodwe.com/warranty

Safety Disclaimer

Warning

PV panel safety:

  1. Ensure the component frames and the bracket system are securely grounded.
  2. Connect the DC cables using the delivered PV connectors. The manufacturer shall not be liable for equipment damage if other connectors are used.
  3. Ensure the DC cables are connected tightly, securely, and correctly. Inappropriate wiring may cause poor contacts or high impedances, and damage the inverter.
  4. Measure the DC cable using the multimeter to avoid reverse polarity connection. Also, the voltage should be under the max DC input voltage. The manufacturer shall not be liable for the damage caused by reverse connection and extremely high voltage.
  5. The PV strings cannot be grounded. Ensure the minimum insulation resistance of the PV string to the ground meets the minimum insulation resistance requirements before connecting the PV string to the inverter. R=Max. Input Voltage/30mA.
  6. The PV modules used with the inverter must have an IEC61730 class A rating.

Inverter safety:

  1. The voltage and frequency at the connecting point should meet the on-grid requirements.

  2. Additional protective devices like circuit breakers or fuses are recommended on the AC side. Specification of the protective device should be at least 1.25 times the rated AC output rated current.

  3. Make sure that all the groundings are tightly connected. When there are multiple inverters, make sure that all the grounding points on the enclosures are equipotential bonding.

  4. Do not start the BACK-UP function if there is no battery in the PV system. The manufacturer shall not be liable for the risks caused by not following this rule.

  5. Do not apply mechanical load to the terminals, otherwise the terminals can be damaged.

  6. All labels and warning marks should be visible after the installation. Do not scrawl, damage, or cover any label on the device.

  7. Do not touch the running equipment to avoid being hurt as its temperature may exceed 60°C. Do not install the equipment at a place within children’s reach.

  8. Unauthorized dismantling or modification may damage the equipment, the damage is not covered under the warranty.

  9. If there is any radio or wireless communication equipment below 30MHz near the inverter, you have to:
    • Install the inverter at least 30m far away from the wireless equipment.
    • Add a low pass EMI filter or a multi winding ferrite core to the DC input cable or AC output cable of the inverter.

  10. Warning labels on the inverter are as follows.

| High-temperature hazard. Do not touch the product under operation to avoid being burnt.| | Delayed discharge. Wait 5 minutes after power off until the components are completely discharged.
---|---|---|---
| Read through the user manual before any operations.| | Potential risks exist. Wear proper PPE before any operations.
| High-temperature hazard. Do not touch the product under operation to avoid being burnt.| | Do not dispose of the inverter as household waste. Discard the product in compliance with local laws and regulations, or send it back to the manufacturer.
| CE marking| | RCM marking
| UKCA marking| | Grounding point.

Battery safety:

  1. The battery used with the inverter shall be approved by the inverter manufacturer. The approved battery list can be obtained through the official website.
  2. Before installations, read through the corresponding battery’s User Manual to learn about the product and the precautions. Strictly follow its requirements.
  3. If the battery discharged completely, please charge it in strict accordance with the corresponding model’s User Manual.
  4. The battery current may be influenced by temperature, humidity, weather condition, etc., which may limit the current and affect the load capacity.
  5. If the battery cannot start properly, contact the After-sales Service as soon as possible. Otherwise, the battery will be damaged permanently.
  6. Measure the DC cable using the multimeter to avoid reverse polarity connection. Also, the voltage should be under the permissible range.
  7. To avoid damage the inverter, do not connect one battery pack to multi inverters.\

Check before Power-on

No Check Item
1 The product is firmly installed at a clean place that is well-ventilated

and easy-to operate
2| The PE, DC input, AC output, and communication cables are connected correctly and securely.
3| Cable ties are intact, routed properly and evenly
4| Unused ports and terminals are sealed.
5| The voltage and frequency at the connection point meet the inverter grid connection requirements. The voltage and frequency at the connection point meet the inverter grid connection requirements.

EU Declaration of Conformity

Good We Technologies Co., Ltd. hereby declares that the inverter with wireless communication
modules sold in the European market meets the requirements of the following directives:

  • Radio Equipment Directive 2014/53/EU (RED)
  • Restrictions of Hazardous Substances Directive 2011/65/EU and (EU) 2015/863 (RoHS)
  •  Waste Electrical and Electronic Equipment 2012/19/EU
  • Registration, Evaluation, Authorization and Restriction of Chemicals (EC) No 1907/2006 (REACH)

Good We Technologies Co., Ltd. hereby declares that the inverter without wireless communication modules sold in the European market meets the requirements of the following directives:

  • Electromagnetic compatibility Directive 2014/30/EU (EMC)

  • Electrical Apparatus Low Voltage Directive 2014/35/EU (LVD)
    Restrictions of Hazardous Substances Directive 2011/65/EU and (EU) 2015/863 (RoHS)

  • Waste Electrical and Electronic Equipment 2012/19/EU

  • Registration, Evaluation, Authorization and Restriction of Chemicals (EC) No 1907/2006 (REACH) You can download the EU Declaration of Conformity on https://en.goodwe.com.

LED Indicators

Indicator Status Description
The inverter is power on and in the standby mode.
The inverter is starting up and in the self-check mode.
The inverter is in normal operation under grid-tied or off-grid

modes.

| BACK-UP output overload
| A fault has occurred.
| The inverter is powered off.
| | The grid is abnormal and the inverter is in off-grid mode.
| The grid is normal and the inverter is in grid-tied mode.
| BACK-UP is off.
| | The monitoring module of the inverter is resetting.
| The inverter fails to connect with the communication terminal device.
| Faults between the communication terminal device and Server.
| The monitoring of the inverter operates well.
| The monitoring module of the inverter has not been started yet.

Product Introduction

Parts

Parts

  1. Battery Terminal (BAT +/-)
  2. BMS Communication Port (BMS)
  3. Communication Module Port (COM1)
  4. METER Communication Port (METER)
  5. Communication Port (COM2)
  6. PV Input Terminal (PV1/ PV2)*1
  7. DC Switch*2
  8. DC switch Locking Hole*3
  9. AC Terminal (BACKUP)
  10. AC Terminal (ON-GRID)
  11. PE Terminal
  12. LED Indicators
  13. Mounting Plate
  14. Heat Sink

*1:* SBP series inverter: 0 x PV+/PV-; GW3000-ES-20: 1 x PV+/PV-; Others: 2 x PV+/PV-.
2:** For ES series inverter only.
*3: For Australia inverters only

Dimensions

Dimensions

Inverter Installation

Inverter Installation

Space Requirements

Space Requirements
Space Requirements

Angle Requirements

Angle Requirements

Installing the Inverter

Installing the Inverter
Installing the Inverter

Electrical Connection

PE Cable

PE Cable

AC Cable (ON-GRID &BACK-UP

AC Cable \(ON-GRID&BACK-UP

Type One

For GW3600-ES-20, GW5000-ES-20, GW6000-ES-20, GW3600-SBP-20, GW5000-SBP-20, and GW6000- SBP-20 inverters.

Type OneType
One

Type Two

For GW3000-ES-20, GW3600M-ES-20, GW5000M-ES-20, and GW6000M-ES-20 inverters.

Type Two
Type Two

DC Cable (PV

  • For ES series only.
    DC Cable \(PV\)

MC4

MC4
MC4
MC4

Vaconn

MC4
Vaconn
Vaconn

Battery Cable (BAT)

Battery Cable \(BAT
Battery Cable \(BAT

Communication Connection

Communication Connection
Communication Connection
Communication Connection

No.| Color|

EMS/PAR

---|---|---

1

| Orange and White| RS485A (EMS)
2| Orange|

RS485B (EMS)

3

| Green and White| NC
4| Blue|

GND

5

| Blue and White| CAN_H(PAR)
6| Green|

CAN_H(PAR)

7

| Brown and White| BUS1 (PAR)
8| Brown|

BUS2(PAR)

BMS or Smart Meter

BMS or Smart Meter |

No. Color BMS Smart Meter
1 Orange & White NC NC
2 Orange NC NC
3 Green & White NC NC
4 Blue CAN_H NC
5 Blue & White CAN_L NC
6 Green NC NC
7 Brown & White NC 485_B1
8 Brown NC 485_A1

BMS or Smart Meter |

Communication Module

Communication Module

Power On and Of

Self Consumption System (ES Inverter Scenario)

Power On and Of

Self Consumption System (SBP Inverter Scenario)

Power On and Of

Commissioning via PV Master APP

| Symbol| Symbol|
---|---|---|---

|

Monitoring via SEMS Portal App

| Symbol| Symbol|
---|---|---|---

|

For more detailed instructions, scan the QR codes below.

| QR Code| | |
---|---|---|---|---

ES, SBP Series 3.0- 6.0kW G2 User Manual

|

Solar Go App User Manual

|

WiFi Quick Installation Guide

|

SEMS Portal User Manual

|

Parallel Inverter System Solution User Manual

|

340-00800-01

|
---|---|---

Offical Website

|

340-00800-01

|