MEAN WELL DRT-240 Series 240W Three Phase Industrial DIN RAIL Power Supply Instruction Manual
- June 4, 2024
- MEAN WELL
Table of Contents
240W Three Phase Industrial DIN RAIL Power Supply
DRT-240 series
Features :
- Three-Phase AC 340 ~ 550V wide range input
- High efficiency 89% and low dissipation
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Built-in constant current limiting circuit
- Can be installed on DIN rail TS-35/7.5 or 15
- UL 508(industrial control equipment)approved
- EN61000-6-2(EN50082-2) industrial immunity level
- 100% full load burn-in test
- Fixed switching frequency at 70KHz
- 3 years warranty
https://www.meanwell.com/Upload/PDF/General%20Type%20DIN%20rail%20with%20Three%20Phase.pdf
SPECIFICATION
MODEL | DRT•240-24 | DRT•240-48 |
---|---|---|
OUTPUT | DC VOLTAGE | 24V |
RATED CURRENT | 10A | 5A |
CURRENT RANGE | 0 – 10A | 0 – 5A |
RATED POWER | 240W | 240W |
RIPPLE & NOISE (max.) Note/ | 80mVp-p | 80mVp-p |
VOLTAGE ADJ. RANGE | 24 – 28V | 48 – 55V |
VOLTAGE TOLERANCE Note.3 | ±1.0% | ±1.0% |
LINE REGULATION | ±0.5% | ±0.5% |
LOAD REGULATION | ±0.5% | ±0.5% |
SETUP, RISE, HOLD UP TIME | 1200ms, 40ms, 20ms/400VAC 800ms. 40ms. 40ms/500VAC |
at full load
INPUT| VOLTAGE RANGE Note.3| Three-Phase 340 – 550VAC (Dual phase operation
possible) 480 – 780VDC
FREQUENCY RANGE| 47 – 63Hz
EFFICIENCY (Typ.)| 89%
AC CURRENT| 0.95A/400VAC 0.75A/500VAC
INRUSH CURRENT (max.)| COW START 50A
LEAKAGE CURRENT| <3.5mA/ 530VAC
PROTECTION| OVERLOAD| 105 – 150% rated output power
Protection type : Constant current limiting, recovers automatically after
fault condition is removed
OVER VOLTAGE| 30 – 36V| 159 – 66V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| 100 C±5 C (TSW) detect on heatsink of power switch
Protection type: Shut down o/p voltage, recovers automatically after
temperature goes down
ENVIRONMENT| WORKING TEMP.| -20 – +70 C (Refer to ‘Derating Curve’)
WORKING HUMIDITY| 20 – 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 – +85 C , 10 – 95% RH
TEMP. COEFFICIENT| ±0.03%1C (0 – 50 C )
VIBRATION| 10 – 500Hz, 2G 10min./1 cycle. 60min. each along X, Y, Z axes;
Mounting: Compliance to IEC60068-2-6
SAFETY 8
EMC (Note 4)| SAFETY STANDARDS| U1508, UL60950-1, EAC TP TC 004 approved
WITHSTAND VOLTAGE| I/P-0/P:3KVAC UP-FG:2.0KVAC 0/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-0/P, UP-FG, OIP-FG:100M Ohms / 500VDC / 25 C/ 70% RH
EMC EMISSION| Compliance to EN55032 (CISPR32), EN61204-3 Class B. EAC TP TC
020
EMC IMMUNITY| Compliance to EN61000-4-2,3,4,5,6,8,11, EN61204-3, EN61000-6-2
(EN50082-2), heavy industry level, criteria A, EAC TP TC 020
OTHERS| MTBF| 114.6K hrs min. MIL-HDBK-217F (25 C )
DIMENSION| 125.5’125.2100mm (Wilt)
PACKING| 1.3Kg: 12pcs/16.6Kg/1.49CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at 400VAC input,
rated load and 25 C of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted
pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance: includes set up tolerance, line regulation, and load
regulation.
4. The power supply is considered a component which will be installed into a
final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Dual phase operation: derating of 20% is required.
6. The ambient temperature derating of 3.5t /1000m with fanless models and of
5C/1000m with fan models for operating altitude higher than 2000m(6500ft)
• Product Liability Disclaimer: For detailed information, please refer to
https://www.meanwell.conVserviceDisdaimer.aspx
Mechanical Specification
Block Diagram
Derating Curve
Static Characteristics